2026 Changes Part 1- ID Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 4 – 2026 Changes Part 11Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.) Indoor damp and/or wet locations Outdoor wet and damp locations only Outdoor wet locations only Indoor wet locations (damp locations were removed) Reference:210.8 A 2. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) Directly buried in the earth When bundled In crawl spaces When fished between acess points and concealed Reference:334.12 3. 114 – 2026 Changes Part 11On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met? The receptacle is located more than 12 inches from a sink and AFCI The receptacle is part of a listed assembly specifically designed for face?up installation Reference:406.14 G 4. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The reconditioning contractors documented quality?control program The motor nameplate data and conductor ampacity tables The installers field evaluation or local AHJ preference The manufacturers instructions Reference:430.3 5. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? 110.21 B Identification of disconnecting means Section 250.8 Equipment grounding conductor identification Section 408.3 Support and arrangement of busbars Section 90.7 Examination of equipment for safety Reference:408.10 F 6. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Only embedded concrete heating mats Conductive pavement heating systems . Only roof?mounted heating cables Only factory?assembled heating systems Reference:Article 424, 425, 426 and 427 7. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 6 ft 0 in 6 ft 7 in 5 ft 6 in 7 ft 0 in Reference:404.10 A 2 8. 112 – 2026 Changes Part 11A nongrounding?type receptacle with no grounding conductor present may be replaced with which of the following? A grounding?type receptacle supplied through a GFCI device all of these anwsers are true only a non-grounding receptacle Any grounding?type receptacle as long as it is labeled No Equipment Ground Reference:406.12 D 1 9. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Meter socket enclosures Fittings All electrical equipment Electrical mechanical supports Reference:312.3 10. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 10 ampere 15 ampere 30 ampere 20 ampere Reference:210.22 ex 11. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 90 degree C 75 degree C 140 degree F 60 degree C Reference:310.16 12. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 800 amperes 600 amperes 500 amperes 1000 amperes Reference:215.10 B 13. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Isolating switches must always be load?break rated and are required for all equipment regardless of design Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Reference:495.22 14. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Emergency service facility sleeping quarters like police stations Break and quiet rooms All occupancies All commercial occupancies Reference:215.18 A 15. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Fastening devices Reduced-Wall-Thickness Boxes Wagos Mounting screws Reference:314.2 16. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located below grade level Only that have a floor located at grade or below grade level Only that have a floor located at grade level Regardless of grade level Reference:210.8 A 17. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are permitted if a warning label is also provided are never allowed are not permitted unless with a manual bypass are allowed Reference:210.70 C3 18. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? . A ductless mini?split indoor unit A supplemental electric baseboard heater A whole?house humidifier Lighting outlets required by 210.70 C and receptacles required by 210.63 A Reference:422.12 19. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? Neither reconditioned reactors nor reconditioned resistors are permitted to be installed . Reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed Both reconditioned reactors and reconditioned resistors are permitted to be installed Reference:470.3 A B 20. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Only fixed cabinets that are not recessed Any fixed cabinet Only fixed cabinets with a work surface Only fixed cabinets with countertops Reference:210.52 A2(1) 21. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Branch circuits with AFCI protection Individual branch circuits Multiwire branch circuits Branch circuits supplied from emergency sources Reference:517.15 22. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Staples Straps and hangers Straps Hangers Reference:332.3 23. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 16 AWG Copper-Clad Aluminum 18 AWG Copper 14 AWG Aluminum 14 AWG Copper-Clad Aluminum Reference:340.104 24. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 1500 square feet 2400 square feet 1750 square feet 2000 square feet Reference:334.1 25. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Non-Powered-Limited Signaling circuits Overvoltage protection All circuits under 100 volts Power-Limited Remote-Control Circuits Reference:206.1 26. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Service disconnect Electrical disconnect Utility disconnect Service switch Reference:230.70 B 27. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? All NEC conditions for location It is installed by the utility It is mounted on the roof It is installed in a bedroom closet Reference:550.51 B 1-7 28. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Letters shall be at least 1/2 inch high Must have a red text Shall be located adjacent to the disconnect Must have a black background Reference:230.70 B2 29. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible in commercial applications only Strictly prohibitted Permissible in residential applications only Permissible Reference:240.24 E 30. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Any power source approved by the authority having jurisdiction Generating units Photovoltaic systems Only on?site generators listed for emergency systems Reference:517.30 B 31. 32 – 2026 Changes Part 11A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.) Verified by testing in the field Identified (listed or labeled) Orange in color Improvised in the field Reference:230.62 C 32. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Parks and recreation Assembly occupancies Commercial garages Health care patient rooms Reference:406.26 33. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Are in addition to Reduce Overrides Substitute Reference:225.1 Note 2 34. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Single colored stripe other than green Green colored stripe Double stripe Color painted on Reference:200.7 A 35. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Internal cable clamps Terminal blocks Equipment grounding conductors Wire nuts (splicing connectors) Reference:314.16 B 36. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection shall be installed at the overcurrent protection device AFCI protection shall be marked at the first device AFCI protection can be located at the first switch The entire circuit shall now be protected Reference:210.12 E 37. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Flexible metallic raceways and fittings Non-flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Felexible sealtight and fittings Reference:250.102 A 38. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Listed bonding bushings with bonding jumpers Tight threadless couplings used with metal raceways Threaded couplings made up wrench?tight Locknuts Reference:500.30 B 39. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where combustible dusts are present in suspension Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where ignitable fibers are manufactured Any location containing Class I or Class II materials Reference:500.5 40. 31 – 2026 Changes Part 11Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.) SVC SSS SUS SLS Reference:230.46 note 41. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements Interlocking is optional if the temporary source is supervised by qualified personnel The temporary source may be smaller than the on?site source if load shedding is used Reference:517.30 E 4 42. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. 501.10(A)(1) only Article 430 Part IV . 500.8 only 501.3 and 505.3 Reference:513.3 A 43. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Unclassified Class I Class II Reference:513.8 44. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The top of the equipment enclosure The floor or working platform . The nearest doorway The ceiling height Reference:404.10 A 2 45. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 110 article 406 Article 314 Article 210 Reference:406 46. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Imaging suites used for diagnostic procedures Patient care areas used for direct preparation and care Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Category 1 treatment rooms used for invasive procedures Reference:517.10 B 47. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) The disconnection of surge-protection devices Service disconnects rated under 30 amperes A switchboard A metering center Reference:230.71 A 48. 160 – 2026 Changes Part 11According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Identified for extra?hard usage Limited to a maximum length of 3 ft Suitable for damp locations only Permitted only when installed in rigid metal conduit Reference:511.10 B 49. 145 – 2026 Changes Part 11According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A timer?based charging system that limits charging to off?peak hours A cooling fan that operates whenever the battery is charging Overcharge control provisions to prevent the batteries from becoming overcharged A secondary disconnecting means located within sight of the battery room Reference:480.14 50. 103 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? Dimmer switches Knife switches General?use snap switches GFCI?type switching devices Reference:404.3 51. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) One- and two-family dwelling and multifamily only All types of One- and two-family dwelling units only Commercial and industrial only Reference:230.70 D 52. 149 – 2026 Changes Part 11Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches are required to be load?break rated and may be used as the primary disconnecting means Grounding switches only need to be interlocked with the service disconnect Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding Reference:495.26 53. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside branch circuits and feeders Indoor branch circuits and feeders All branch circuits and feeders Outside services Reference:267.1 54. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 2 inches thick 1 3/4 inch thick 1 inch thick 1 1/2 inch thick Reference:300.6 E 55. 156 – 2026 Changes Part 11Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Reconditioned equipment is prohibited in all hazardous locations unless field?evaluated by the AHJ All reconditioned equipment must be listed and marked Explosion?Proof regardless of original classification Only equipment located outside the hazardous location requires reconditioning evaluation Reconditioned equipment is permitted Reference:501.3 56. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded together using a solid copper conductor sized per Table 250.122 D. No bonding is required if each section has its own feeder disconnect They must be bonded with a minimum #12 copper conductor if GFCI protection is provided They must be bonded together with a solid copper conductor not smaller than #8 AWG Reference: 545.20 D 545.26 57. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) The National Electrical Code tables only A qualified person A local utility company The authority having jurisdiction (AHJ) Reference:268.42 C 58. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) All feeder and service In areas with rocks only 1000 volts AC or more only Service Reference:300.7 D3 59. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Electric baseboard heaters Ductless mini?split systems Wall?mounted room air conditioners Similar equipment Reference:422.12 ex.#1 60. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Alternating?current power distribution boxes Only generators rated over 15 kW Only luminaires used for egress lighting Only equipment installed in permanent studio structures Reference:530.2 61. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 15 amperes 8 amperes 10 amperes 12 amperes Reference:Table 210.24(1) 62. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Does not apply to flexible conduits Only applies to rigid conduit methods Only applies to each raceway type in the run Applies even when you transition and combine raceway types Reference:300.24 63. 108 – 2026 Changes Part 11In the electrical trade, the term wiring devices commonly refers to which of the following? Only switches Only luminaires switches and receptacles Only circuit breakers Reference:Article 406 and Definitions 64. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It shall not be mounted in or on the mobile home and must be within sight of the home it serves It cannot serve as the emergency disconnect It may be mounted on the exterior wall of the mobile home if weatherproof It must be located at least 50 ft from the mobile home Reference:550.51 65. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? Battery?equipped emergency luminaires . Battery?equipped emergency luminaires Energy storage systems Reference:517.28 A ex. 66. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) Their dielectric materials and protective mechanisms degrade over time They are no longer manufactured in standard voltage classes They require special labeling that is not recognized by the NEC They cannot be effectively grounded after reconditioning Reference:460.3 67. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) All types of roof decking A metal-corrugated roof decking only Any wood decking only A plywood-type roof decking only Reference:300.6 E 68. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Within the same room or area Unless the system is supervised Unless the system is outdoors Unless the system is in an isolated area Reference:265.63 B 69. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 10 amperes 12 amperes 8 amperes 15 amperes Reference:Table 210.24(2) 70. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of brass Identified bimetallic couplings Bonding jumpers made of copper or brass All listed fittings are Reference:342.14 71. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Only equipment over 52 Equipment rated not over 15 All equipment over 1 Reference:495.2 AB 72. 83 – 2026 Changes Part 11Armored Cable is now required to be supported with approved and listed _________. (Non listed devices can degrade with time under heat.) 2 hole straps only Straps only Staples Hangers only Reference:320.2 73. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At the load terminals of the transfer switch At the generator or the first disconnecting means supplied by the generator Only at the service disconnect At any convenient point in the portable structure Reference:525.31 74. 104 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General?use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) molded-case switches (Breaker type switches) Automatic transfer switches Manual bypass/isolation switches Transfer switches Reference:404.3 B 75. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be within sight and within 6 ft of the operator station and readily accessible during operation It must be located at least 15 ft from the operator station to prevent accidental operation It may expose uninsulated live parts when opened without any additional restrictions It must be located inside a locked room accessible only to qualified personnel Reference:525.21 A 76. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 1000 amperes 400 amperes 800 amperes 600 amperes Reference:230.95 77. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) A minimum 6 AWG copper grounding electrode conductor Any location inside A non-metallic enclosure A satellite electrode Reference:250.94 A 78. 135 – 2026 Changes Part 11According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following? The minimum circuit ampacity and maximum fuse size for the outdoor unit The location of all indoor units it supplies The manufacturers installation instructions for both indoor and outdoor units Reference:440.15 79. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. . Only inside the dispensing device Other than inside or adjacent to the dispensing device Inside Only adjacent to the dispensing device Reference:514.13 80. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) Intrinsically safe electrical equipment All associated power . All dispensing devices not supplied by intrinsically safe circuits All remote pumps serving the dispensing devices Reference:514.11 A 81. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 300 volts to ground 150 volts to ground 50 volts to ground 120 volts to ground Reference:410.184 A B 82. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Counted unless under engineering supervision Considered as current carrying and shall be counted Considered as current carrying but does not need to be counted Not considered as current carrying Reference:310.15 E 83. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) can now be located outside of the laundry area shall be marked at the switch must be located outside of the laundry area shall be located inside the laundry area adjacent to the door Reference:210.70 A ex 3 84. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 18 inches 24 inches 6 inches 12 inches Reference:210.52 A5 85. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 80% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions 125% of the generator nameplate current rating 115% of the generator nameplate current rating Reference:445.13 86. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 70 amperes or less 60 amperes or less 100 amperes or less 80 amperes or less Reference:210.8 F 87. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Only grounding and bonding conductors associated with the service Any control conductors associated with the same building Any feeder conductors passing through to adjacent equipment Reference:408.10 2 88. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only lithium?ion battery systems installed indoors ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only standby battery systems used for emergency power Only battery systems connected to renewable?energy equipment Reference:480.1 89. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 300.5(A) through (A)(4) 110.26(A)(1) through (A)(3) 250.8(A)(1) through (A)(6) 547.44(C)(1) through 547.44(C)(4) Reference:547.44 C 90. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) The disconnects shall be installed inside out of the weather Both disconnects shall be installed Only one is needed if it complies with 225.41 An emergency disconnecting means is no longer required Reference:225.31 A, 4 1 91. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel These are all requirements for a GFCI exception. Equipment design not compatible with GFCI protection Reference:210.8 B ex 2 92. 29 – 2026 Changes Part 11The NEC requirement to list service equipment as suitable as service has been consolidated into a list format and now includes _________. (An increasing emphasis on listing ensuring product safety through third party certification. AVTs are used to verify that circuits are de-energized.) Power distribution blocks only Permanently mounted absence of voltage testers (AVTs) Utility power company owned transfer switches All meter sockets Reference:230.2 A 93. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Prudent demand factors and historic data Feeder calculations Connected loads The nameplate rating of the largest single piece of equipment only Reference:517.4 B 94. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be bonded with a #12 copper conductor to any nearby metal object It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion Reference:547.44 B 95. 130 – 2026 Changes Part 11A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) . Design F and Design G motors Design B(E) and Design C(E) motors Design A and Design D motors Design S and Design T motors Reference:Recognition throughout article 430 96. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. All of these answers are false 20 amp grounding type receptacles Grounding type receptacles AFCI receptacles Reference:406.12 D 1 97. 66 – 2026 Changes Part 11A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.) Class 4 circuits Conductors not over 1500 Volts DC Conductors to services Conductors not over 1000 Volts AC Reference:300.1 98. 51 – 2026 Changes Part 11In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.) All metallic raceways Nonferrous metal enclosures Ferrous metal cable armor raceways All raceways Reference:250.64 E1 99. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Straps only 2 hole straps only Hangers only Staples Reference:334.2 100. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) Article 266 The National Electrical Safety Code United Laboratories (UL) Article 250 Reference:265.1 Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish