2026 Changes Part 1- ID Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery chargers associated with the system nly metallic battery terminals Only battery enclosures located outdoors Conductive battery stands Reference:480.8 2. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Wall?mounted room air conditioners Electric baseboard heaters Similar equipment Ductless mini?split systems Reference:422.12 ex.#1 3. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. Off?site and sized to supply the entire EES; on?site only On?site and sized to supply the entire EES; either on?site or off?site On?site but sized only for the life?safety branch; on?site only Off?site; off?site only Reference:517.41 A 4. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) All set-screw style connectors A listed mechanical grounding connector Connectors that do not comply with ANSI/UL 467 standards Any split-bolt lug Reference:250.64 C 5. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only grounding and bonding conductors associated with the service Only conductors intended for termination within that section Any control conductors associated with the same building Any feeder conductors passing through to adjacent equipment Reference:408.10 2 6. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 100 amperes or less 80 amperes or less 70 amperes or less 60 amperes or less Reference:210.8 F 7. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) Service In areas with rocks only All feeder and service 1000 volts AC or more only Reference:300.7 D3 8. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 210 Article 314 Article 110 article 406 Reference:406 9. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 1750 square feet 2400 square feet 2000 square feet 1500 square feet Reference:334.1 10. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All associated power Intrinsically safe electrical equipment All remote pumps serving the dispensing devices . All dispensing devices not supplied by intrinsically safe circuits Reference:514.11 A 11. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only equipment specifically listed for Class I Only optical fiber equipment located outside the hazardous location Laser equipment Only laser equipment located inside the hazardous location Reference:500.8 G 12. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure Only at the service disconnect At the load terminals of the transfer switch At the generator or the first disconnecting means supplied by the generator Reference:525.31 13. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They are no longer manufactured in standard voltage classes Their dielectric materials and protective mechanisms degrade over time They require special labeling that is not recognized by the NEC They cannot be effectively grounded after reconditioning Reference:460.3 14. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Substitute Reduce Overrides Are in addition to Reference:225.1 Note 2 15. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 100% of the generator nameplate current rating under all conditions 115% of the generator nameplate current rating 125% of the generator nameplate current rating 80% of the generator nameplate current rating Reference:445.13 16. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. On?site and sized to supply the entire EES Off?site and sized to supply the entire EES On?site but permitted to supply only the critical branch Off?site and capable of supplying only the life?safety branch Reference:517.30 A 17. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. Article 430 Part IV . 500.8 only 501.10(A)(1) only 501.3 and 505.3 Reference:513.3 A 18. 177 – 2026 Changes Part 11A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state? Warning Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized Disconnect all sources before servicing equipment Hazardous voltage may be present even when equipment is off Caution Multiple power sources supplied from separate feeders Reference:517.28 B 19. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Any power source approved by the authority having jurisdiction Only on?site generators listed for emergency systems Photovoltaic systems Reference:517.30 B 20. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 90 degree C 140 degree F 60 degree C 75 degree C Reference:310.16 21. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) can now be located outside of the laundry area must be located outside of the laundry area shall be marked at the switch shall be located inside the laundry area adjacent to the door Reference:210.70 A ex 3 22. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Be installed according to 1 subpart Comply with all 3 subparts Combine any 2 subparts to comply Comply with at least 2 subparts Reference:242.14 23. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where combustible dusts are present in suspension Any location containing Class I or Class II materials Only locations where ignitable fibers are manufactured Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Reference:500.5 24. 84 – 2026 Changes Part 11__________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.) Brackets Wraps Screws Staples Reference:320.30 A 25. 137 – 2026 Changes Part 11If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges ) 115 percent 125 percent None of these answers are correct except this one 100 percent Reference:445.13 26. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 16 AWG Copper 16 AWG Copper-Clad Aluminum 14 AWG Aluminum 18 AWG Copper Reference:310.5 A 27. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed with AHJ guidance Can be installed if the enclosure is indoors Can be installed Shall not be installed Reference:250.64 G 28. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Conduit length Listed fittings Entry height Marking requirement Reference:300.9 A 29. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? Energy storage systems Battery?equipped emergency luminaires . Battery?equipped emergency luminaires Reference:517.28 A ex. 30. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A master electrician Any engineer A licensed administrator A qualified individual Reference:266.4 C 31. 114 – 2026 Changes Part 11On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met? The receptacle is located more than 12 inches from a sink and AFCI The receptacle is part of a listed assembly specifically designed for face?up installation Reference:406.14 G 32. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Staples Hangers only Straps only 2 hole straps only Reference:334.2 33. 185 – 2026 Changes Part 11Diagnostic imaging and treatment equipment shall be installed in accordance with which portion of the NEC?(The 2026 NEC revision clarifies and expands the scope of part five vertical 517 by stating that it applies to all diagnostic imaging and treatment equipment not just x-ray systems ) Article 517 Article 760 Article 645 Article 700 Reference:517.7 34. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Locations Switchboards Interrupting capacity Arc-Flash ratings Reference:230.71 B 35. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) An emergency disconnecting means is no longer required Only one is needed if it complies with 225.41 The disconnects shall be installed inside out of the weather Both disconnects shall be installed Reference:225.31 A, 4 1 36. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Prudent demand factors and historic data Feeder calculations The nameplate rating of the largest single piece of equipment only Connected loads Reference:517.4 B 37. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable terminations Cable relocation Cable removal Rejuvenation Reference:315.3 38. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Shall Can not Shall not May Reference:342.29 39. 48 – 2026 Changes Part 11The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.) Is allowed at all times Is no longer allowed Is allowed if a rock bottom is encountered when a rod is driven at a 45 degree angle Is allowed only with express consent from the AHJ Reference:250.53 A4 40. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To eliminate all requirements for oil?filled equipment below 15 kV To allow reconditioned oil?filled equipment to be installed without listing To expand transformer oil?testing requirements to all electrical equipment To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 41. 162 – 2026 Changes Part 11Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies? Assembly Industrial or storage occupancies only Business occupancies only Mercantile occupancies only Reference:512.6 42. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Commercial amusement parks with permanent rides Carnivals Industrial manufacturing plants Permanent theatrical stages only Reference:525.1 43. 181 – 2026 Changes Part 11When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service? Interlocking is optional if the temporary source is monitored by qualified personnel The temporary connection must be sized to accommodate the largest power source The temporary source may be connected only after modifying permanent wiring Integration of the temporary source may delay transfer switch timing if supervised Reference:517.30 F 1 44. 190 – 2026 Changes Part 11Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does ) . It may be run on the ground if marked with caution tape It must be installed only on the exterior of the tent or concession It may be loosely supported if used only during daylight hours It must be securely installed Reference:525.22 45. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. 3-way "snap" switches Service equipment Pull out switches All of the answers are true Reference:404.1 A 46. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Optional standby systems Essential electrical systems in healthcare facilities Legally required standby systems Emergency lighting systems in non?healthcare buildings Reference:517.26 47. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Utility disconnect Electrical disconnect Service switch Service disconnect Reference:230.70 B 48. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be installed only in dwelling-unit bedrooms It shall be listed as a combination faceplate assembly It shall be a blank faceplate with no openings It shall be supplied only by a Class 2 power source only Reference:406.16 D 49. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Any metal framed container Only bait wells Open aquatic vessels or containers Any aquatic vessels Reference:210.8 B 50. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Reference:495.22 51. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 406.9 300.5 210.52 550.13 only Reference:550.13 D 52. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Hangers Staples Straps Straps and hangers Reference:332.3 53. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Assembly occupancies Commercial garages Parks and recreation Health care patient rooms Reference:406.26 54. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Any conductor Surge protection devices Copper-Clad Aluminum Conductors Pneumatic lines Reference:392.22 B 55. 149 – 2026 Changes Part 11Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches are required to be load?break rated and may be used as the primary disconnecting means Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding Grounding switches only need to be interlocked with the service disconnect Reference:495.26 56. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) United Laboratories (UL) Article 266 The National Electrical Safety Code Article 250 Reference:265.1 57. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Only applies to rigid conduit methods Only applies to each raceway type in the run Does not apply to flexible conduits Applies even when you transition and combine raceway types Reference:300.24 58. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 15 amperes 8 amperes 10 amperes 12 amperes Reference:Table 210.24(1) 59. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Class I Class II Unclassified Reference:513.8 60. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Commercial Ordinary Temporary table 501.10 A 1. & Restricted Reference:501.1 61. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 20 AWG 18 AWG 16 AWG 14 AWG Reference:210.24(1) 62. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The floor or working platform . The nearest doorway The top of the equipment enclosure The ceiling height Reference:404.10 A 2 63. 145 – 2026 Changes Part 11According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A timer?based charging system that limits charging to off?peak hours A secondary disconnecting means located within sight of the battery room Overcharge control provisions to prevent the batteries from becoming overcharged A cooling fan that operates whenever the battery is charging Reference:480.14 64. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The connection point must be marked with phase rotation and system bonding requirements The temporary source may be smaller than the on?site source if load shedding is used Interlocking is optional if the temporary source is supervised by qualified personnel The connection may require modification of permanent wiring if approved by the AHJ Reference:517.30 E 4 65. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Multiwire branch circuits Branch circuits with AFCI protection Branch circuits supplied from emergency sources Individual branch circuits Reference:517.15 66. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of copper or brass Identified bimetallic couplings All listed fittings are Bonding jumpers made of brass Reference:342.14 67. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Corrosive locations only Hazardous (Class I Wet locations Reference:495.4 68. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) Based on temperature rise Provided under engineering supervision In a campus environment Located outdoors Reference:265.19 B 69. 11 – 2026 Changes Part 11Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.) 1500 2000 2500 2400 Reference:210.13 A&B 70. 168 – 2026 Changes Part 11In addition to the off?site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Only generators listed for emergency systems Only energy storage systems listed for standby use Photovoltaic systems only Power production sources Reference:517.4 71. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Regardless of grade level Only that have a floor located below grade level Only that have a floor located at grade or below grade level Only that have a floor located at grade level Reference:210.8 A 72. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is outdoors Unless the system is in an isolated area Within the same room or area Unless the system is supervised Reference:265.63 B 73. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 3/4 inch thick 1 1/2 inch thick 2 inches thick 1 inch thick Reference:300.6 E 74. 156 – 2026 Changes Part 11Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Reconditioned equipment is prohibited in all hazardous locations unless field?evaluated by the AHJ Only equipment located outside the hazardous location requires reconditioning evaluation All reconditioned equipment must be listed and marked Explosion?Proof regardless of original classification Reconditioned equipment is permitted Reference:501.3 75. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 6 inches 12 inches 18 inches 24 inches Reference:210.52 A5 76. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) AVTs (absence of voltage testers) Type 3 surge-protection devices Listed smoke detection systems Video monitoring systems Reference:230.82 77. 128 – 2026 Changes Part 11The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Electric baseboard heaters Baseboard heater raceways Unit heater fan motors Embedded snow?melting mats Reference:424.2 78. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Motor control centers . Switchboards Panelboards Switchgear Reference:408,3 B 79. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 30 ampere 15 ampere 20 ampere 10 ampere Reference:210.22 ex 80. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 400 amperes 600 amperes 800 amperes 1000 amperes Reference:230.95 81. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Installed by qualified persons Inspected annually by a third party Installed in a neat and workman-like manner Inspected by a third party again after installation Reference:393.14 A 82. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 11 Type 2C or 11C Type 25 or 21 S Type 21C Reference:300.13 E 83. 161 – 2026 Changes Part 11According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5. Class III Unclassified Class II Class I Reference:511.10 B 2 84. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Smoke damage Severe cold Water damage Aged over 50 years Reference:300.4 C 85. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) All commercial occupancies Emergency service facility sleeping quarters like police stations All occupancies Break and quiet rooms Reference:215.18 A 86. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) Any location inside A satellite electrode A non-metallic enclosure A minimum 6 AWG copper grounding electrode conductor Reference:250.94 A 87. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A supplemental electric baseboard heater A whole?house humidifier . A ductless mini?split indoor unit Lighting outlets required by 210.70 C and receptacles required by 210.63 A Reference:422.12 88. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Jacketing Cable cleats Any hangers Blocking Reference:330.30 A 89. 135 – 2026 Changes Part 11According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following? The manufacturers installation instructions for both indoor and outdoor units The minimum circuit ampacity and maximum fuse size for the outdoor unit The location of all indoor units it supplies Reference:440.15 90. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Only fixed cabinets that are not recessed Any fixed cabinet Only fixed cabinets with a work surface Only fixed cabinets with countertops Reference:210.52 A2(1) 91. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) EEE Chapter 7 Section 300.11 NECA publication 1-23 NEMA GD 1-2019 Reference:300.4 C 92. 138 – 2026 Changes Part 11According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors comply with 240.21(B) Only if the tap conductors are less than 10 ft in length Only if the tap conductors are supervised by an AHJ?approved maintenance program Only if the tap conductors are installed in rigid metal conduit Reference:445.13 B 93. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Power-Limited Remote-Control Circuits All circuits under 100 volts Non-Powered-Limited Signaling circuits Overvoltage protection Reference:206.1 94. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Equipment rated not over 15 All equipment over 1 Only equipment over 52 Reference:495.2 AB 95. 103 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? Knife switches GFCI?type switching devices Dimmer switches General?use snap switches Reference:404.3 96. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) Only the largest source must be bonded to the structures grounding electrode The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 . Each source must have an isolated equipment grounding conductor Bonding is optional if all generators are rated less than 15 kW Reference:525.12 97. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be connected only to the service neutral It must be bonded with a #12 copper conductor to any nearby metal object It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It may be bonded with aluminum conductors if not subject to corrosion Reference:547.44 B 98. 4 – 2026 Changes Part 11Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.) Indoor wet locations (damp locations were removed) Outdoor wet and damp locations only Indoor damp and/or wet locations Outdoor wet locations only Reference:210.8 A 99. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating It permits field?installed overcurrent devices to replace listed transformer protection It eliminates primary?side overcurrent protection for transformers under 1 kVA Reference:450.3 100. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 14 AWG 20 AWG 18 AWG 16 AWG Reference:Table 210.24(2) Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish