2026 Changes Part 1- AK Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 175 – 2026 Changes Part 11 According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Emergency lighting systems in non-healthcare buildings Optional standby systems Essential electrical systems in healthcare facilities Legally required standby systems Reference:517.26 2. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Conduit length Entry height Marking requirement Reference:300.9 A 3. 163 – 2026 Changes Part 11 Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Class I Unclassified locations only Class I, Division 2 or Zone 2, as applicable Class II Reference:512.21 4. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 115% of the generator nameplate current rating 125% of the generator nameplate current rating 80% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions Reference:445.13 5. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) Commercial and industrial only One- and two-family dwelling and multifamily only One- and two-family dwelling units only All types of Reference:230.70 D 6. 130 – 2026 Changes Part 11 A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design B(E) and Design C(E) motors Design S and Design T motors Design F and Design G motors Design A and Design D motors Reference:Recognition throughout article 430 7. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where ignitable fibers are manufactured Any location containing Class I or Class II materials Only locations where combustible dusts are present in suspension Reference:500.5 8. 189 – 2026 Changes Part 11 Which of the following is REQUIRED for the disconnecting means of a non‑moving attraction or portable structure such as a tent, concession, inflatable, or slide? It must be located inside or outside the structure within 6 ft It must be located at the service equipment supplying the carnival It must be located exactly 6 ft inside the structure It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 B 9. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It permits field?installed overcurrent devices to replace listed transformer protection It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating It eliminates primary?side overcurrent protection for transformers under 1 kVA Reference:450.3 10. 103 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? GFCI‑type switching devices Dimmer switches General‑use snap switches Knife switches Reference:404.3 11. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 5 2 4 3 Reference:406 12. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are never allowed are permitted if a warning label is also provided are allowed are not permitted unless with a manual bypass Reference:210.70 C3 13. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Does not apply to flexible conduits Only applies to rigid conduit methods Only applies to each raceway type in the run Applies even when you transition and combine raceway types Reference:300.24 14. 117 – 2026 Changes Part 11 Tamper‑resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Health care patient rooms Assembly occupancies Parks and recreation Commercial garages Reference:406.26 15. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. 501.10(A)(1) only 501.3 and 505.3 Article 430 Part IV . 500.8 only Reference:513.3 A 16. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 14 AWG 16 AWG 18 AWG 20 AWG Reference:Table 210.24(2) 17. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Hangers Straps and hangers Staples Straps Reference:332.3 18. 157 – 2026 Changes Part 11Section 501.3(B) of the 2026 NEC is ____________. A new requirement for intrinsically safe systems Reserved for future use A requirement for wiring methods in Class I A prohibition on reconditioned equipment in hazardous locations Reference:501.3 B 19. 8 – 2026 Changes Part 11For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.) Assured Grounding GFCI protection is only suggested now. There are no longer exceptions; it shall be GFCI protected. Listed Class C SPGFCI protection is permitted instead of GFCI Reference:210.8 F ex 3 20. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of copper or brass All listed fittings are Identified bimetallic couplings Bonding jumpers made of brass Reference:342.14 21. 139 – 2026 Changes Part 11According to the 2026 NEC the terminology for generator remote emergency shutdown has been modernized by replacing an old term emergency stop switch with_______. (This update reflects the evolution of generator control technologies which increasingly rely on digital systems programmable interfaces and network control circuits rather than physical traditional switches ) Emergency disconnect Generator lockout switch Shutdown device Remote trip mechanism Reference:445.19 B 22. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed with AHJ guidance Can be installed Shall not be installed Can be installed if the enclosure is indoors Reference:250.64 G 23. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Only generators rated over 15 kW Alternating?current power distribution boxes Only equipment installed in permanent studio structures Only luminaires used for egress lighting Reference:530.2 24. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel Equipment design not compatible with GFCI protection These are all requirements for a GFCI exception. Reference:210.8 B ex 2 25. 126 – 2026 Changes Part 11Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that ) Continuous load only for branch circuit conductors Classification was removed Continuous load As cold water heaters Reference:422.13 26. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 0.1 second 0.01 second 0.05 second 1.0 second Reference:517.42 F 27. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? . Battery?equipped emergency luminaires Battery?equipped emergency luminaires Energy storage systems Reference:517.28 A ex. 28. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Bonding is not required if the system voltage is under 50 volts Threaded couplings/hubs made up wrench?tight Only wire?type equipment grounding conductors installed in every raceway Any mechanical connection Reference:500.3 29. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A metal-corrugated roof decking only All types of roof decking A plywood-type roof decking only Any wood decking only Reference:300.6 E 30. 32 – 2026 Changes Part 11A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.) Verified by testing in the field Improvised in the field Orange in color Identified (listed or labeled) Reference:230.62 C 31. 148 – 2026 Changes Part 11 According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches must always be load?break rated and are required for all equipment regardless of design Isolating means are required unless the equipment can be deenergized by other methods such as draw out units non load break isolating switches must be interlocked with a series interrupting device or field marked with a warning Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Reference:495.22 32. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A metering center A switchboard Service disconnects rated under 30 amperes The disconnection of surge-protection devices Reference:230.71 A 33. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Must have a red text Letters shall be at least 1/2 inch high Shall be located adjacent to the disconnect Must have a black background Reference:230.70 B2 34. 156 – 2026 Changes Part 11 Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? All reconditioned equipment must be listed and marked Explosion Proof regardless of original classification Reconditioned equipment is prohibited in all hazardous locations unless field evaluated by the AHJ Only equipment located outside the hazardous location requires reconditioning evaluation Reconditioned equipment is permitted Reference:501.3 35. 115 – 2026 Changes Part 11 Receptacles shall not be installed in a face‑up position in which of the following locations? (The NEC prohibits installing receptacles face‑up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) On work surfaces Under raised floors in IT rooms On walls adjacent to countertops In a laundry area Reference:406.14 G 36. 197 – 2026 Changes Part 11 Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) GFCI protection is optional if the receptacle is within sight of the panelboard Only outdoor receptacles require GFCI protection GFCI protection must be provided as required in 210.8 Receptacle outlets must be GFCI protected only when installed in bathrooms Reference:550.13 B 37. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 inch thick 2 inches thick 1 3/4 inch thick 1 1/2 inch thick Reference:300.6 E 38. 104 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General‑use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) Manual bypass/isolation switches Automatic transfer switches Transfer switches Molded-case switches (Breaker type switches) Reference:404.3 B 39. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Color painted on Double stripe Green colored stripe Single colored stripe other than green Reference:200.7 A 40. 42 – 2026 Changes Part 11A new code section for overcurrent protection now covers and introduces the new term “transformer secondary conductors,” and they are permitted to be ________. (This change separates feeder tap conductor from the transformer secondary rules.) Considered protected without overcurrent protection at the secondary Always installed without protection regardless of length Tapped without restrictions Considered protected without overcurrent protection Reference:240.21 B3 and 240.21 C 41. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Electrical mechanical supports All electrical equipment Meter socket enclosures Fittings Reference:312.3 42. 190 – 2026 Changes Part 11Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does ) . It may be run on the ground if marked with caution tape It may be loosely supported if used only during daylight hours It must be securely installed It must be installed only on the exterior of the tent or concession Reference:525.22 43. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? shall have a plan review Field?assembled systems supervised by the installer Site?specific engineered designs by both civil and electrical engineers Standard off?the?shelf listed assemblies Reference:426.64 44. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 12 amperes 8 amperes 10 amperes 15 amperes Reference:Table 210.24(1) 45. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. All of the answers are true Service equipment Pull out switches 3-way "snap" switches Reference:404.1 A 46. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Felexible sealtight and fittings Non-flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Flexible metallic raceways and fittings Reference:250.102 A 47. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? All equipment over 1 Equipment rated not over 15 Only equipment over 52 Reference:495.2 AB 48. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) can now be located outside of the laundry area shall be marked at the switch must be located outside of the laundry area shall be located inside the laundry area adjacent to the door Reference:210.70 A ex 3 49. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 2000 square feet 1750 square feet 1500 square feet 2400 square feet Reference:334.1 50. 153 – 2026 Changes Part 11 According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 μm wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only optical fiber equipment located outside the hazardous location Only equipment specifically listed for Class I Laser equipment Only laser equipment located inside the hazardous location Reference:500.8 G 51. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts all these answers are true Reference:404.13 C 52. 47 – 2026 Changes Part 11The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.) Used for dissipation of surges Used for dissipation of lightning Considered a ground-fault path Used for a voltage reference Reference:250.4 A5 53. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Internal cable clamps Equipment grounding conductors Terminal blocks Wire nuts (splicing connectors) Reference:314.16 B 54. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The temporary source may be smaller than the on?site source if load shedding is used Interlocking is optional if the temporary source is supervised by qualified personnel The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements Reference:517.30 E 4 55. 31 – 2026 Changes Part 11Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.) SVC SUS SSS SLS Reference:230.46 note 56. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) Only one is needed if it complies with 225.41 Both disconnects shall be installed An emergency disconnecting means is no longer required The disconnects shall be installed inside out of the weather Reference:225.31 A, 4 1 57. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 80 amperes or less 70 amperes or less 60 amperes or less 100 amperes or less Reference:210.8 F 58. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? . Only roof?mounted heating cables Conductive pavement heating systems Only embedded concrete heating mats Only factory?assembled heating systems Reference:Article 424, 425, 426 and 427 59. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. Off?site and capable of supplying only the life?safety branch Off?site and sized to supply the entire EES On?site and sized to supply the entire EES On?site but permitted to supply only the critical branch Reference:517.30 A 60. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The motor nameplate data and conductor ampacity tables The manufacturers instructions The installers field evaluation or local AHJ preference The reconditioning contractors documented quality?control program Reference:430.3 61. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) Any engineer A qualified individual A master electrician A licensed administrator Reference:266.4 C 62. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site and sized to supply the entire EES; either on?site or off?site Off?site; off?site only Off?site and sized to supply the entire EES; on?site only On?site but sized only for the life?safety branch; on?site only Reference:517.41 A 63. 108 – 2026 Changes Part 11In the electrical trade, the term wiring devices commonly refers to which of the following? Only circuit breakers Only switches switches and receptacles Only luminaires Reference:Article 406 and Definitions 64. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Marked suitable for damp locations Installed by a qualified person and approved by the manufacturer Installed in accordance with Article 410 only Listed for the location and listed for field installation with the luminaire being retrofitted Reference:501.130 C 65. 166 – 2026 Changes Part 11 Emergency electrical disconnects for fuel‑dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) Intrinsically safe electrical equipment All remote pumps serving the dispensing devices All dispensing devices not supplied by intrinsically safe circuits All associated power Reference:514.11 A 66. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 90 percent 100 percent 110 percent 125 percent Reference:265.20 A 67. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Class II Class I Unclassified Reference:513.8 68. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) Any jacket covering Aluminum conductors A messenger A copper-alloy armor Reference:330.10 A 69. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards Any split-bolt lug All set-screw style connectors A listed mechanical grounding connector Reference:250.64 C 70. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The ceiling height . The nearest doorway The floor or working platform The top of the equipment enclosure Reference:404.10 A 2 71. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Severe cold Smoke damage Water damage Aged over 50 years Reference:300.4 C 72. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Only fixed cabinets that are not recessed Only fixed cabinets with countertops Any fixed cabinet Only fixed cabinets with a work surface Reference:210.52 A2(1) 73. 132 – 2026 Changes Part 11 Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center? 430.102 — Disconnecting means for motors 408.4 — Circuit directory and identification 110.21(B) — Field‑applied hazard markings 110.16 — Arc‑flash hazard warning Reference:430.98 A 74. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Can not Shall not May Shall Reference:342.29 75. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located inside a locked room accessible only to qualified personnel It must be within sight and within 6 ft of the operator station and readily accessible during operation It must be located at least 15 ft from the operator station to prevent accidental operation It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 A 76. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 50 feet 100 feet 75 feet 60 feet Reference:225.41 A1 77. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Rejuvenation Cable removal Cable terminations Cable relocation Reference:315.3 78. 112 – 2026 Changes Part 11A nongrounding?type receptacle with no grounding conductor present may be replaced with which of the following? A grounding?type receptacle supplied through a GFCI device all of these anwsers are true Any grounding?type receptacle as long as it is labeled No Equipment Ground only a non-grounding receptacle Reference:406.12 D 1 79. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 20 AWG 18 AWG 16 AWG 14 AWG Reference:210.24(1) 80. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 150 volts to ground 50 volts to ground 300 volts to ground 120 volts to ground Reference:410.184 A B 81. 102 – 2026 Changes Part 11A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switchessuch as snap switches, dimmers, and electronic controlswere moved to Article 406 as part of a structural reorganization.) The increase of allowable switch voltage ratings to 2000 volts The expansion of Article 404 to include all wiring devices such as receptacles and GFCIs The elimination of Article 404 and redistribution of its content into Chapter 2 The relocation of most device?type switches Reference:404.1 B 82. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 90 degree C 75 degree C 140 degree F 60 degree C Reference:310.16 83. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 12 inches 18 inches 10 inches 6 inches Reference:392.18 F 84. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Wet locations Corrosive locations only Hazardous (Class I Reference:495.4 85. 135 – 2026 Changes Part 11 According to 2026 NEC the outdoor disconnecting means for a split‑system HVAC unit in other than one‑ and two‑family dwellings must be marked with which of the following? The minimum circuit ampacity and maximum fuse size for the outdoor unit The location of all indoor units it supplies, in accordance with 110.22(A) The manufacturer’s installation instructions for both indoor and outdoor units The location of the branch-circuit overcurrent device supplying the outdoor unit, in accordance with 110.22(A) Reference:440.15 86. 12 – 2026 Changes Part 11___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.) Commercial break rooms Holding tanks Dormitories (16 individuals or more) Industrial and commercial break rooms Reference:210.17 87. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Be installed according to 1 subpart Combine any 2 subparts to comply Comply with all 3 subparts Comply with at least 2 subparts Reference:242.14 88. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Field evaluated only Listed as suitable for service only Listed or field evaluated Additionally certified Reference:230.2 B 89. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Imaging suites used for diagnostic procedures Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Patient care areas used for direct preparation and care Category 1 treatment rooms used for invasive procedures Reference:517.10 B 90. 122 – 2026 Changes Part 11 Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 210.12 — AFCI protection 406.12 — Tamper‑resistant receptacles section 410.184 A and/or B 250.114 — Equipment grounding conductor requirements Reference:410.184 91. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Open aquatic vessels or containers Any aquatic vessels Only bait wells Any metal framed container Reference:210.8 B 92. 171 – 2026 Changes Part 11Part II of Article 517 applies to which of the following? Only Category 1 and Category 2 treatment rooms Only hospitals and ambulatory surgical centers Only facilities with essential electrical systems Patient care spaces of all healthcare facilities Reference:517.10 A 93. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Non-Powered-Limited Signaling circuits Power-Limited Remote-Control Circuits Overvoltage protection All circuits under 100 volts Reference:206.1 94. 20 – 2026 Changes Part 11As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.) 6 inches 12 inches 24 inches 18 inches Reference:210.52 C4 95. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is installed by the utility All NEC conditions for location It is mounted on the roof It is installed in a bedroom closet Reference:550.51 B 1-7 96. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class A Class B fuses Class C fuses Class A fuses Reference:240.7 97. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Permanent theatrical stages only Commercial amusement parks with permanent rides Carnivals Industrial manufacturing plants Reference:525.1 98. 11 – 2026 Changes Part 11Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.) 1500 2000 2400 2500 Reference:210.13 A&B 99. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery chargers associated with the system Conductive battery stands Only battery enclosures located outdoors nly metallic battery terminals Reference:480.8 100. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) United Laboratories (UL) Article 250 The National Electrical Safety Code Article 266 Reference:265.1 Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish