2026 Changes Part 1- AK Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 72 – 2026 Changes Part 1

    1
    A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.)
    Reference:300.9 A
  2. 2. 148 – 2026 Changes Part 1

    1
    According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)?
    Reference:495.22
  3. 3. 142 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors?
    Reference:470.3 A B
  4. 4. 39 – 2026 Changes Part 1

    1
    The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.)
    Reference:230.82
  5. 5. 27 – 2026 Changes Part 1

    1
    Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.)
    Reference:225.31 A, 4 1
  6. 6. 169 – 2026 Changes Part 1

    1
    Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________.
    Reference:517.4 B
  7. 7. 153 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay )
    Reference:500.8 G
  8. 8. 56 – 2026 Changes Part 1

    1
    Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.)
    Reference:250.119 A2
  9. 9. 107 – 2026 Changes Part 1

    1
    Knife switches used for isolating rated less than ______ shall be considered general?use switches.
    Reference:404.13 C
  10. 10. 86 – 2026 Changes Part 1

    1
    A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.)
    Reference:330.10 A
  11. 11. 69 – 2026 Changes Part 1

    1
    Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.)
    Reference:300.6 E
  12. 12. 128 – 2026 Changes Part 1

    1
    The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following?
    Reference:424.2
  13. 13. 114 – 2026 Changes Part 1

    1
    On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met?
    Reference:406.14 G
  14. 14. 105 – 2026 Changes Part 1

    1
    Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position?
    Reference:404.10 A 2
  15. 15. 2 – 2026 Changes Part 1

    1
    New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.)
    Reference:206.1
  16. 16. 81 – 2026 Changes Part 1

    1
    Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.)
    Reference:314.16 B
  17. 17. 146 – 2026 Changes Part 1

    1
    According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies?
    Reference:495.2 AB
  18. 18. 22 – 2026 Changes Part 1

    1
    When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.)
    Reference:210.70 A ex 3
  19. 19. 132 – 2026 Changes Part 1

    1
    Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center?
    Reference:430.98 A
  20. 20. 133 – 2026 Changes Part 1

    1
    Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit )
    Reference:440.2
  21. 21. 127 – 2026 Changes Part 1

    1
    Conductive pavement heating systems shall be designed as which of the following?
    Reference:426.64
  22. 22. 61 – 2026 Changes Part 1

    1
    New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.)
    Reference:266.4 C
  23. 23. 131 – 2026 Changes Part 1

    1
    Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following?
    Reference:430.3
  24. 24. 172 – 2026 Changes Part 1

    1
    Part II of Article 517 does NOT apply to which of the following spaces?
    Reference:517.10 B
  25. 25. 38 – 2026 Changes Part 1

    1
    The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.)
    Reference:230.71 B
  26. 26. 126 – 2026 Changes Part 1

    1
    Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that )
    Reference:422.13
  27. 27. 8 – 2026 Changes Part 1

    1
    For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.)
    Reference:210.8 F ex 3
  28. 28. 1 – 2026 Changes Part 1

    1
    A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.)
    Reference:200.7 A
  29. 29. 200 – 2026 Changes Part 1

    1
    Service equipment is permitted to be installed in or on a manufactured home only if which condition is met?
    Reference:550.51 B 1-7
  30. 30. 193 – 2026 Changes Part 1

    1
    Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.)
    Reference:530.2
  31. 31. 144 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded)
    Reference:480.8
  32. 32. 124 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment?
    Reference:422.12 ex.#1
  33. 33. 134 – 2026 Changes Part 1

    1
    If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened?
    Reference:440.11
  34. 34. 9 – 2026 Changes Part 1

    1
    When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.)
    Reference:210.8 F ex 3
  35. 35. 120 – 2026 Changes Part 1

    1
    As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section?
    Reference:408.10 2
  36. 36. 167 – 2026 Changes Part 1

    1
    Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________.
    Reference:514.13
  37. 37. 63 – 2026 Changes Part 1

    1
    New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.)
    Reference:268.42 C
  38. 38. 118 – 2026 Changes Part 1

    1
    Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation?
    Reference:408.3 A
  39. 39. 173 – 2026 Changes Part 1

    1
    Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads )
    Reference:517.15
  40. 40. 154 – 2026 Changes Part 1

    1
    The 2026 NEC requires which of the following bonding methods for normally non–current?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations?
    Reference:500.3
  41. 41. 66 – 2026 Changes Part 1

    1
    A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.)
    Reference:300.1
  42. 42. 110 – 2026 Changes Part 1

    1
    In the 2026 NEC, wiring?device–type switch requirements were relocated from Article 404 to which Article?
    Reference:406
  43. 43. 37 – 2026 Changes Part 1

    1
    The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.)
    Reference:230.71 A
  44. 44. 159 – 2026 Changes Part 1

    1
    Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________.
    Reference:501.130 C
  45. 45. 176 – 2026 Changes Part 1

    1
    A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement?
    Reference:517.28 A ex.
  46. 46. 98 – 2026 Changes Part 1

    1
    A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.)
    Reference:392.18 F
  47. 47. 87 – 2026 Changes Part 1

    1
    A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.)
    Reference:330.30 A
  48. 48. 199 – 2026 Changes Part 1

    1
    Which of the following is TRUE regarding service equipment for a mobile home under Article 550?
    Reference:550.51
  49. 49. 47 – 2026 Changes Part 1

    1
    The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.)
    Reference:250.4 A5
  50. 50. 103 – 2026 Changes Part 1

    1
    When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code?
    Reference:404.3
  51. 51. 165 – 2026 Changes Part 1

    1
    All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one )
    Reference:513.8
  52. 52. 196 – 2026 Changes Part 1

    1
    The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings )
    Reference:547.44 C
  53. 53. 18 – 2026 Changes Part 1

    1
    A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.)
    Reference:210.52 A2(1)
  54. 54. 92 – 2026 Changes Part 1

    1
    Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.)
    Reference:334.12
  55. 55. 78 – 2026 Changes Part 1

    1
    In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.)
    Reference:310.16
  56. 56. 89 – 2026 Changes Part 1

    1
    The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.)
    Reference:332.3
  57. 57. 30 – 2026 Changes Part 1

    1
    Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.)
    Reference:230.2 B
  58. 58. 101 – 2026 Changes Part 1

    1
    There is a significant change to the scope of NEC article 404 by including __________.
    Reference:404.1 A
  59. 59. 62 – 2026 Changes Part 1

    1
    The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.)
    Reference:267.1
  60. 60. 95 – 2026 Changes Part 1

    1
    Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.)
    Reference:342.10 B
  61. 61. 31 – 2026 Changes Part 1

    1
    Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.)
    Reference:230.46 note
  62. 62. 188 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525?
    Reference:525.21 A
  63. 63. 91 – 2026 Changes Part 1

    1
    A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering.
    Reference:334.1
  64. 64. 145 – 2026 Changes Part 1

    1
    According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum )
    Reference:480.14
  65. 65. 19 – 2026 Changes Part 1

    1
    The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.)
    Reference:210.52 A5
  66. 66. 94 – 2026 Changes Part 1

    1
    An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.)
    Reference:340.104
  67. 67. 33 – 2026 Changes Part 1

    1
    Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.)
    Reference:230.70 B
  68. 68. 35 – 2026 Changes Part 1

    1
    In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.)
    Reference:230.70 D
  69. 69. 5 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.)
    Reference:210.8 B
  70. 70. 14 – 2026 Changes Part 1

    1
    In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard)
    Reference:210.24(1)
  71. 71. 140 – 2026 Changes Part 1

    1
    A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision?
    Reference:450.3
  72. 72. 79 – 2026 Changes Part 1

    1
    A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.)
    Reference:312.3
  73. 73. 100 – 2026 Changes Part 1

    1
    Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.)
    Reference:393.14 A
  74. 74. 182 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________.
    Reference:517.41 A
  75. 75. 198 – 2026 Changes Part 1

    1
    Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes )
    Reference:550.13 D
  76. 76. 85 – 2026 Changes Part 1

    1
    New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.)
    Reference:330.2
  77. 77. 17 – 2026 Changes Part 1

    1
    If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.)
    Reference:Table 210.24(2)
  78. 78. 73 – 2026 Changes Part 1

    1
    When raceways are installed in a wet location above grade level they now shall _______. (Moisture accumulation can be an issue in environments such as food processing plants, car washes, and swimming pools.)
    Reference:300.11 B
  79. 79. 186 – 2026 Changes Part 1

    1
    Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential)
    Reference:525.1
  80. 80. 150 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor?
    Reference:495.36
  81. 81. 77 – 2026 Changes Part 1

    1
    The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.)
    Reference:310.15 E
  82. 82. 183 – 2026 Changes Part 1

    1
    The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content )
    Reference:517.42 A
  83. 83. 6 – 2026 Changes Part 1

    1
    An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.)
    Reference:210.8 B ex 2
  84. 84. 54 – 2026 Changes Part 1

    1
    The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.)
    Reference:250.102 A
  85. 85. 166 – 2026 Changes Part 1

    1
    Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency )
    Reference:514.11 A
  86. 86. 109 – 2026 Changes Part 1

    1
    According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment )
    Reference:406.3
  87. 87. 194 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes )
    Reference: 545.20 D 545.26
  88. 88. 60 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.)
    Reference:265.63 B
  89. 89. 158 – 2026 Changes Part 1

    1
    In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed )
    Reference:501.1
  90. 90. 141 – 2026 Changes Part 1

    1
    According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”)
    Reference:460.3
  91. 91. 175 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 )
    Reference:517.26
  92. 92. 41 – 2026 Changes Part 1

    1
    A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.)
    Reference:240.7
  93. 93. 10 – 2026 Changes Part 1

    1
    Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.)
    Reference:210.12 E
  94. 94. 102 – 2026 Changes Part 1

    1
    A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switches—such as snap switches, dimmers, and electronic controls—were moved to Article 406 as part of a structural reorganization.)
    Reference:404.1 B
  95. 95. 4 – 2026 Changes Part 1

    1
    Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.)
    Reference:210.8 A
  96. 96. 137 – 2026 Changes Part 1

    1
    If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges )
    Reference:445.13
  97. 97. 93 – 2026 Changes Part 1

    1
    There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.)
    Reference:338.24
  98. 98. 90 – 2026 Changes Part 1

    1
    Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.)
    Reference:334.2
  99. 99. 65 – 2026 Changes Part 1

    1
    The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.)
    Reference:270.20 C
  100. 100. 123 – 2026 Changes Part 1

    1
    The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold?
    Reference:410.184 A B
Back