2026 Changes Part 1- AK Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 51 – 2026 Changes Part 11In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.) All raceways Nonferrous metal enclosures Ferrous metal cable armor raceways All metallic raceways Reference:250.64 E1 2. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Ordinary Temporary table 501.10 A 1. & Restricted Commercial Reference:501.1 3. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) can now be located outside of the laundry area shall be located inside the laundry area adjacent to the door shall be marked at the switch must be located outside of the laundry area Reference:210.70 A ex 3 4. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) In crawl spaces When fished between acess points and concealed Directly buried in the earth When bundled Reference:334.12 5. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) D. No bonding is required if each section has its own feeder disconnect They must be bonded together with a solid copper conductor not smaller than #8 AWG They must be bonded together using a solid copper conductor sized per Table 250.122 They must be bonded with a minimum #12 copper conductor if GFCI protection is provided Reference: 545.20 D 545.26 6. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) All occupancies Emergency service facility sleeping quarters like police stations Break and quiet rooms All commercial occupancies Reference:215.18 A 7. 167 – 2026 Changes Part 11 Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Only adjacent to the dispensing device Inside Only inside the dispensing device Other than inside or adjacent to the dispensing device Reference:514.13 8. 163 – 2026 Changes Part 11 Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Unclassified locations only Class I, Division 2 or Zone 2, as applicable Class II Class I Reference:512.21 9. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) All types of roof decking Any wood decking only A metal-corrugated roof decking only A plywood-type roof decking only Reference:300.6 E 10. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Coating the raceway Sealing the raceway Adding caution tape Using galvanized steel Reference:342.10 B 11. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Commercial amusement parks with permanent rides Industrial manufacturing plants Permanent theatrical stages only Carnivals Reference:525.1 12. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection can be located at the first switch AFCI protection shall be installed at the overcurrent protection device The entire circuit shall now be protected AFCI protection shall be marked at the first device Reference:210.12 E 13. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Only applies to rigid conduit methods Only applies to each raceway type in the run Does not apply to flexible conduits Applies even when you transition and combine raceway types Reference:300.24 14. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade level Regardless of grade level Only that have a floor located at grade or below grade level Only that have a floor located below grade level Reference:210.8 A 15. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Conductive pavement heating systems Only embedded concrete heating mats Only factory?assembled heating systems . Only roof?mounted heating cables Reference:Article 424, 425, 426 and 427 16. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) Over 500 volts DC Over 500 volts AC For utilities That supply portable or mobile equipment Reference:270.20 C 17. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Can not Shall Shall not May Reference:342.29 18. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Staples 2 hole straps only Hangers only Straps only Reference:334.2 19. 168 – 2026 Changes Part 11 In addition to the off‑site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Only generators listed for emergency systems Power production sources, fuel cell systems, energy storage systems, and healthcare microgrids Photovoltaic systems only Only energy storage systems listed for standby use Reference:517.4 20. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Be installed according to 1 subpart Combine any 2 subparts to comply Comply with all 3 subparts Comply with at least 2 subparts Reference:242.14 21. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Arc-Flash ratings Interrupting capacity Switchboards Locations Reference:230.71 B 22. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Any metal framed container Open aquatic vessels or containers Only bait wells Any aquatic vessels Reference:210.8 B 23. 66 – 2026 Changes Part 11A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.) Conductors to services Conductors not over 1000 Volts AC Class 4 circuits Conductors not over 1500 Volts DC Reference:300.1 24. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It may expose uninsulated live parts when opened without any additional restrictions It must be located at least 15 ft from the operator station to prevent accidental operation It must be located inside a locked room accessible only to qualified personnel It must be within sight and within 6 ft of the operator station and readily accessible during operation Reference:525.21 A 25. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 80 amperes or less 70 amperes or less 100 amperes or less 60 amperes or less Reference:210.8 F 26. 149 – 2026 Changes Part 11 Which of the following correctly describes the requirements for grounding switches used in medium‑ and high‑voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding, and cannot be closed while the grounding switch is in the grounded position Grounding switches are required to be load‑break rated and may be used as the primary disconnecting means Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches only need to be interlocked with the service disconnect, not with other power sources feeding the equipment Reference:495.26 27. 177 – 2026 Changes Part 11 A warning sign is required where removal of a grounding or bonding connection in power source equipment would interrupt the grounding- electrode-conductor or grounded conductor connection to another energized source. What must the sign state? “Caution — Multiple power sources supplied from separate feeders” “Disconnect all sources before servicing equipment” “Hazardous voltage may be present even when equipment is off” “Warning — Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized” Reference:517.28 B 28. 109 – 2026 Changes Part 11 According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are permitted if listed by a third‑party refurbisher Reconditioned wiring devices are not permitted to be used Reconditioned wiring devices are permitted only in non‑dwelling occupancies Reference:406.3 29. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 100% of the generator nameplate current rating under all conditions 125% of the generator nameplate current rating 80% of the generator nameplate current rating 115% of the generator nameplate current rating Reference:445.13 30. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Class I Unclassified Class II Reference:513.8 31. 21 – 2026 Changes Part 11The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________. so the receptacle shall be located within another room to now only require for dwelling units the verbiage to mandate it not be located on the load side (this requirement has been deleted) to address both dwelling and non-dwelling units Reference:210.63 B 32. 36 – 2026 Changes Part 11The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.) Does not qualify Can qualify if listed SVC Qualifiers Can qualify if listed Reference:230.70 F 33. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) Any jacket covering A messenger Aluminum conductors A copper-alloy armor Reference:330.10 A 34. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) The panel circuit breaker shall be marked with a warning label Marking labels are recommended The HVAC disconnect shall be marked with a warning label Both the panel circuit breaker and HVAC shall be marked with a warning label Reference:210.8 F ex 3 35. 114 – 2026 Changes Part 11 On work surfaces, receptacles shall not be installed in a face‑up position unless which condition is met? The receptacle is located more than 12 inches from a sink and AFCI, GFCI's are used The receptacle is part of a listed assembly specifically designed for face‑up installation It's in a work Surface It's in an area below a sink Reference:406.14 G 36. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 16 AWG 18 AWG 20 AWG 14 AWG Reference:Table 210.24(2) 37. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Only fixed cabinets with countertops Any fixed cabinet Only fixed cabinets that are not recessed Only fixed cabinets with a work surface Reference:210.52 A2(1) 38. 32 – 2026 Changes Part 11A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.) Improvised in the field Verified by testing in the field Orange in color Identified (listed or labeled) Reference:230.62 C 39. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Bonding is not required if the system voltage is under 50 volts Any mechanical connection Threaded couplings/hubs made up wrench?tight Only wire?type equipment grounding conductors installed in every raceway Reference:500.3 40. 122 – 2026 Changes Part 11 Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? section 410.184 A and/or B 406.12 — Tamper‑resistant receptacles 250.114 — Equipment grounding conductor requirements 210.12 — AFCI protection Reference:410.184 41. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 14 AWG 16 AWG 18 AWG 20 AWG Reference:210.24(1) 42. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 1000 amperes 500 amperes 800 amperes 600 amperes Reference:215.10 B 43. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 60 feet 100 feet 75 feet 50 feet Reference:225.41 A1 44. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 12 inches 18 inches 24 inches 6 inches Reference:210.52 A5 45. 146 – 2026 Changes Part 11 According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Only equipment over 52,000 volts must be listed, effective January 1, 2027 Only equipment over 52,000 volts must be listed, effective January 1, 2032 Equipment rated not over 15,000 volts must be listed by January 1, 2029, and equipment rated over 15,000 volts up to 52,000 volts must be listed by January 1, 2032 Reference:495.2 AB 46. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To eliminate all requirements for oil?filled equipment below 15 kV To expand transformer oil?testing requirements to all electrical equipment To specify requirements for oil?filled equipment other than transformers To allow reconditioned oil?filled equipment to be installed without listing Reference:article495 parts VI andVII 47. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Any control conductors associated with the same building Only grounding and bonding conductors associated with the service Only conductors intended for termination within that section Any feeder conductors passing through to adjacent equipment Reference:408.10 2 48. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of brass Identified bimetallic couplings All listed fittings are Bonding jumpers made of copper or brass Reference:342.14 49. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It cannot serve as the emergency disconnect It must be located at least 50 ft from the mobile home It shall not be mounted in or on the mobile home and must be within sight of the home it serves It may be mounted on the exterior wall of the mobile home if weatherproof Reference:550.51 50. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only the category assigned by the authority having jurisdiction Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only Category 1 and Category 2 spaces Only Category 3 and Category 4 spaces Reference:517.7 & Informational note 51. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Water damage Aged over 50 years Severe cold Smoke damage Reference:300.4 C 52. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) . Each source must have an isolated equipment grounding conductor The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 Only the largest source must be bonded to the structures grounding electrode Bonding is optional if all generators are rated less than 15 kW Reference:525.12 53. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Any hangers Jacketing Blocking Cable cleats Reference:330.30 A 54. 103 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? General‑use snap switches Dimmer switches GFCI‑type switching devices Knife switches Reference:404.3 55. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Can be installed if refurbished Are resettable Must not be refurbished Can be reused Reference:242.3 56. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure At the generator or the first disconnecting means supplied by the generator At the load terminals of the transfer switch Only at the service disconnect Reference:525.31 57. 160 – 2026 Changes Part 11 According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Identified for extra-hard usage Limited to a maximum length of 3 ft Suitable for damp locations only Permitted only when installed in rigid metal conduit Reference:511.10 B 58. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Any power source approved by the authority having jurisdiction Photovoltaic systems Generating units Only on?site generators listed for emergency systems Reference:517.30 B 59. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 800 amperes 1000 amperes 400 amperes 600 amperes Reference:230.95 60. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Connected loads The nameplate rating of the largest single piece of equipment only Prudent demand factors and historic data Feeder calculations Reference:517.4 B 61. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A switchboard The disconnection of surge-protection devices A metering center Service disconnects rated under 30 amperes Reference:230.71 A 62. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Straps Hangers Staples Straps and hangers Reference:332.3 63. 29 – 2026 Changes Part 11The NEC requirement to list service equipment as suitable as service has been consolidated into a list format and now includes _________. (An increasing emphasis on listing ensuring product safety through third party certification. AVTs are used to verify that circuits are de-energized.) Power distribution blocks only Permanently mounted absence of voltage testers (AVTs) All meter sockets Utility power company owned transfer switches Reference:230.2 A 64. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is in an isolated area Within the same room or area Unless the system is supervised Unless the system is outdoors Reference:265.63 B 65. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 3/4 inch thick 1 1/2 inch thick 1 inch thick 2 inches thick Reference:300.6 E 66. 171 – 2026 Changes Part 11Part II of Article 517 applies to which of the following? Only facilities with essential electrical systems Only Category 1 and Category 2 treatment rooms Only hospitals and ambulatory surgical centers Patient care spaces of all healthcare facilities Reference:517.10 A 67. 108 – 2026 Changes Part 11In the electrical trade, the term wiring devices commonly refers to which of the following? Only circuit breakers Only luminaires switches and receptacles Only switches Reference:Article 406 and Definitions 68. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. 20 amp grounding type receptacles Grounding type receptacles AFCI receptacles All of these answers are false Reference:406.12 D 1 69. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? Both reconditioned reactors and reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed . Reconditioned resistors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed Reference:470.3 A B 70. 143 – 2026 Changes Part 11 Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only standby battery systems used for emergency power ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only battery systems connected to renewable-energy equipment Only lithium?ion battery systems installed indoors Reference:480.1 71. 126 – 2026 Changes Part 11Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that ) Classification was removed Continuous load only for branch circuit conductors Continuous load As cold water heaters Reference:422.13 72. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Section 408.3 Support and arrangement of busbars Reference:408.10 F 73. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Yellow insulated conductor with a green stripe Green covered conductor Green conductor with a yellow stripe Light green insulated conductor Reference:250.119 A2 74. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Life safety branch and equipment branch; division occurs at the transfer switches Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and critical branch; division occurs at the service disconnect Critical branch and equipment branch; division occurs at the panelboards Reference:517.42 A 75. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Marking requirement Entry height Conduit length Reference:300.9 A 76. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded with a #12 copper conductor to any nearby metal object It may be bonded with aluminum conductors if not subject to corrosion It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be connected only to the service neutral Reference:547.44 B 77. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Shall be marked with the location Can be located elsewhere Shall be located but immediately adjacent to the equipment. Can be located downstream Reference:268.91 B 78. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 6 ft 0 in 6 ft 7 in 5 ft 6 in 7 ft 0 in Reference:404.10 A 2 79. 117 – 2026 Changes Part 11 Tamper‑resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Health care patient rooms Parks and recreation Commercial garages Assembly occupancies Reference:406.26 80. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Electrical disconnect Service disconnect Utility disconnect Service switch Reference:230.70 B 81. 175 – 2026 Changes Part 11 According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Optional standby systems Essential electrical systems in healthcare facilities Legally required standby systems Emergency lighting systems in non-healthcare buildings Reference:517.26 82. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Color painted on Green colored stripe Double stripe Single colored stripe other than green Reference:200.7 A 83. 134 – 2026 Changes Part 11 If the disconnecting means for air‑conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must be locked or require a tool to be opened It must automatically de‑energize the equipment when opened It must be marked with a warning label indicating that energized parts are present It must be interlocked with the controller to prevent operation Reference:440.11 84. 190 – 2026 Changes Part 11Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does ) It must be installed only on the exterior of the tent or concession . It may be run on the ground if marked with caution tape It may be loosely supported if used only during daylight hours It must be securely installed Reference:525.22 85. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment shall be evaluated and approved by the original manufacturer The equipment shall be replaced unless the installer certifies it The equipment must be reinspected by the AHJ only The equipment may be reused if insulation resistance tests pass Reference:408.3 A 86. 104 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General‑use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) Automatic transfer switches Transfer switches Manual bypass/isolation switches Molded-case switches (Breaker type switches) Reference:404.3 B 87. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site and sized to supply the entire EES; either on?site or off?site On?site but sized only for the life?safety branch; on?site only Off?site and sized to supply the entire EES; on?site only Off?site; off?site only Reference:517.41 A 88. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 2 4 5 3 Reference:406 89. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 2000 square feet 1750 square feet 2400 square feet 1500 square feet Reference:334.1 90. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards A listed mechanical grounding connector All set-screw style connectors Any split-bolt lug Reference:250.64 C 91. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 300.5 210.52 406.9 550.13 only Reference:550.13 D 92. 42 – 2026 Changes Part 11A new code section for overcurrent protection now covers and introduces the new term “transformer secondary conductors,” and they are permitted to be ________. (This change separates feeder tap conductor from the transformer secondary rules.) Tapped without restrictions Considered protected without overcurrent protection Considered protected without overcurrent protection at the secondary Always installed without protection regardless of length Reference:240.21 B3 and 240.21 C 93. 138 – 2026 Changes Part 11 According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors are installed in rigid metal conduit Only if the tap conductors comply with 240.21(B), and taps are not permitted for portable generators rated 15 kW or less where field wiring terminals are not accessible Only if the tap conductors are less than 10 ft in length Only if the tap conductors are supervised by an AHJ‑approved maintenance program Reference:445.13 B 94. 145 – 2026 Changes Part 11 According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A secondary disconnecting means located within sight of the battery room Overcharge control provisions to prevent the batteries from becoming overcharged A timer‑based charging system that limits charging to off‑peak hours A cooling fan that operates whenever the battery is charging Reference:480.14 95. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Non-Powered-Limited Signaling circuits All circuits under 100 volts Power-Limited Remote-Control Circuits Overvoltage protection Reference:206.1 96. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They cannot be effectively grounded after reconditioning They are no longer manufactured in standard voltage classes They require special labeling that is not recognized by the NEC Their dielectric materials and protective mechanisms degrade over time Reference:460.3 97. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable relocation Cable removal Cable terminations Rejuvenation Reference:315.3 98. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) 1000 volts AC or more only All feeder and service Service In areas with rocks only Reference:300.7 D3 99. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Electric baseboard heaters Ductless mini?split systems Wall?mounted room air conditioners Similar equipment Reference:422.12 ex.#1 100. 174 – 2026 Changes Part 11 Receptacles and fixed equipment in wet‑procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple ) A system supplied from an isolated power source without GFCI protection Individual GFCI devices installed at each receptacle only A power distribution system in which the entire system is protected by a single GFCI device A system protected only by an equipment grounding conductor Reference:517.20 A 3 a b Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish