2026 Changes Part 1- AK Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Marking requirement Conduit length Entry height Reference:300.9 A 2. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Reference:495.22 3. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? . Reconditioned resistors are permitted to be installed Both reconditioned reactors and reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed Reference:470.3 A B 4. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) Video monitoring systems Listed smoke detection systems AVTs (absence of voltage testers) Type 3 surge-protection devices Reference:230.82 5. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) An emergency disconnecting means is no longer required The disconnects shall be installed inside out of the weather Both disconnects shall be installed Only one is needed if it complies with 225.41 Reference:225.31 A, 4 1 6. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Prudent demand factors and historic data Connected loads The nameplate rating of the largest single piece of equipment only Feeder calculations Reference:517.4 B 7. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only equipment specifically listed for Class I Laser equipment Only optical fiber equipment located outside the hazardous location Only laser equipment located inside the hazardous location Reference:500.8 G 8. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Green covered conductor Yellow insulated conductor with a green stripe Light green insulated conductor Green conductor with a yellow stripe Reference:250.119 A2 9. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. all these answers are true 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 10. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) A copper-alloy armor Aluminum conductors Any jacket covering A messenger Reference:330.10 A 11. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A metal-corrugated roof decking only All types of roof decking Any wood decking only A plywood-type roof decking only Reference:300.6 E 12. 128 – 2026 Changes Part 11The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Baseboard heater raceways Embedded snow?melting mats Electric baseboard heaters Unit heater fan motors Reference:424.2 13. 114 – 2026 Changes Part 11On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met? The receptacle is located more than 12 inches from a sink and AFCI The receptacle is part of a listed assembly specifically designed for face?up installation Reference:406.14 G 14. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 6 ft 0 in 7 ft 0 in 5 ft 6 in 6 ft 7 in Reference:404.10 A 2 15. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Overvoltage protection All circuits under 100 volts Non-Powered-Limited Signaling circuits Power-Limited Remote-Control Circuits Reference:206.1 16. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Equipment grounding conductors Wire nuts (splicing connectors) Internal cable clamps Terminal blocks Reference:314.16 B 17. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Equipment rated not over 15 All equipment over 1 Only equipment over 52 Reference:495.2 AB 18. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) can now be located outside of the laundry area shall be located inside the laundry area adjacent to the door shall be marked at the switch must be located outside of the laundry area Reference:210.70 A ex 3 19. 132 – 2026 Changes Part 11Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center? 430.102 Disconnecting means for motors 408.4 Circuit directory and identification 110.16 Arc?flash hazard warning 110.21(B) Field?applied hazard markings Reference:430.98 A 20. 133 – 2026 Changes Part 11Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit ) None of these answers are correct Inspected by the AHJ (Authority having jurisdiction ) Listed as a field installable accessory Purchased from the manufacturer of the HVAC unit being worked on Reference:440.2 21. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? shall have a plan review Field?assembled systems supervised by the installer Standard off?the?shelf listed assemblies Site?specific engineered designs by both civil and electrical engineers Reference:426.64 22. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A qualified individual Any engineer A master electrician A licensed administrator Reference:266.4 C 23. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The reconditioning contractors documented quality?control program The installers field evaluation or local AHJ preference The motor nameplate data and conductor ampacity tables The manufacturers instructions Reference:430.3 24. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Imaging suites used for diagnostic procedures Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Category 1 treatment rooms used for invasive procedures Patient care areas used for direct preparation and care Reference:517.10 B 25. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Locations Switchboards Arc-Flash ratings Interrupting capacity Reference:230.71 B 26. 126 – 2026 Changes Part 11Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that ) As cold water heaters Continuous load only for branch circuit conductors Classification was removed Continuous load Reference:422.13 27. 8 – 2026 Changes Part 11For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.) GFCI protection is only suggested now. Assured Grounding There are no longer exceptions; it shall be GFCI protected. Listed Class C SPGFCI protection is permitted instead of GFCI Reference:210.8 F ex 3 28. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Single colored stripe other than green Double stripe Color painted on Green colored stripe Reference:200.7 A 29. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is mounted on the roof It is installed by the utility All NEC conditions for location It is installed in a bedroom closet Reference:550.51 B 1-7 30. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Only luminaires used for egress lighting Only generators rated over 15 kW Only equipment installed in permanent studio structures Alternating?current power distribution boxes Reference:530.2 31. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery chargers associated with the system Only battery enclosures located outdoors Conductive battery stands nly metallic battery terminals Reference:480.8 32. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Ductless mini?split systems Wall?mounted room air conditioners Similar equipment Electric baseboard heaters Reference:422.12 ex.#1 33. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must be locked or require a tool to be opened It must be interlocked with the controller to prevent operation It must automatically de?energize the equipment when opened Reference:440.11 34. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) The HVAC disconnect shall be marked with a warning label The panel circuit breaker shall be marked with a warning label Marking labels are recommended Both the panel circuit breaker and HVAC shall be marked with a warning label Reference:210.8 F ex 3 35. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Any control conductors associated with the same building Only conductors intended for termination within that section Any feeder conductors passing through to adjacent equipment Only grounding and bonding conductors associated with the service Reference:408.10 2 36. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. . Only inside the dispensing device Only adjacent to the dispensing device Other than inside or adjacent to the dispensing device Inside Reference:514.13 37. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) The authority having jurisdiction (AHJ) The National Electrical Code tables only A local utility company A qualified person Reference:268.42 C 38. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment shall be evaluated and approved by the original manufacturer The equipment must be reinspected by the AHJ only The equipment shall be replaced unless the installer certifies it The equipment may be reused if insulation resistance tests pass Reference:408.3 A 39. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Branch circuits with AFCI protection Branch circuits supplied from emergency sources Individual branch circuits Multiwire branch circuits Reference:517.15 40. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Any mechanical connection Only wire?type equipment grounding conductors installed in every raceway Threaded couplings/hubs made up wrench?tight Bonding is not required if the system voltage is under 50 volts Reference:500.3 41. 66 – 2026 Changes Part 11A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.) Conductors not over 1000 Volts AC Class 4 circuits Conductors not over 1500 Volts DC Conductors to services Reference:300.1 42. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 314 article 406 Article 110 Article 210 Reference:406 43. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) The disconnection of surge-protection devices A metering center A switchboard Service disconnects rated under 30 amperes Reference:230.71 A 44. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Listed for the location and listed for field installation with the luminaire being retrofitted Marked suitable for damp locations Installed by a qualified person and approved by the manufacturer Installed in accordance with Article 410 only Reference:501.130 C 45. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? Battery?equipped emergency luminaires Energy storage systems . Battery?equipped emergency luminaires Reference:517.28 A ex. 46. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 10 inches 6 inches 18 inches 12 inches Reference:392.18 F 47. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Jacketing Any hangers Blocking Cable cleats Reference:330.30 A 48. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It shall not be mounted in or on the mobile home and must be within sight of the home it serves It may be mounted on the exterior wall of the mobile home if weatherproof It cannot serve as the emergency disconnect It must be located at least 50 ft from the mobile home Reference:550.51 49. 47 – 2026 Changes Part 11The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.) Used for a voltage reference Considered a ground-fault path Used for dissipation of surges Used for dissipation of lightning Reference:250.4 A5 50. 103 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? General?use snap switches GFCI?type switching devices Dimmer switches Knife switches Reference:404.3 51. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Unclassified Class II Class I Reference:513.8 52. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 547.44(C)(1) through 547.44(C)(4) 110.26(A)(1) through (A)(3) 300.5(A) through (A)(4) 250.8(A)(1) through (A)(6) Reference:547.44 C 53. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Any fixed cabinet Only fixed cabinets with a work surface Only fixed cabinets with countertops Only fixed cabinets that are not recessed Reference:210.52 A2(1) 54. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) Directly buried in the earth When fished between acess points and concealed When bundled In crawl spaces Reference:334.12 55. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 60 degree C 140 degree F 75 degree C 90 degree C Reference:310.16 56. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Hangers Straps and hangers Staples Straps Reference:332.3 57. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Listed as suitable for service only Listed or field evaluated Additionally certified Field evaluated only Reference:230.2 B 58. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. Service equipment Pull out switches All of the answers are true 3-way "snap" switches Reference:404.1 A 59. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside branch circuits and feeders Outside services All branch circuits and feeders Indoor branch circuits and feeders Reference:267.1 60. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Coating the raceway Adding caution tape Sealing the raceway Using galvanized steel Reference:342.10 B 61. 31 – 2026 Changes Part 11Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.) SVC SLS SUS SSS Reference:230.46 note 62. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located at least 15 ft from the operator station to prevent accidental operation It must be located inside a locked room accessible only to qualified personnel It must be within sight and within 6 ft of the operator station and readily accessible during operation It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 A 63. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 1500 square feet 2000 square feet 1750 square feet 2400 square feet Reference:334.1 64. 145 – 2026 Changes Part 11According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A secondary disconnecting means located within sight of the battery room A timer?based charging system that limits charging to off?peak hours Overcharge control provisions to prevent the batteries from becoming overcharged A cooling fan that operates whenever the battery is charging Reference:480.14 65. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 24 inches 18 inches 12 inches 6 inches Reference:210.52 A5 66. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 18 AWG Copper 14 AWG Copper-Clad Aluminum 14 AWG Aluminum 16 AWG Copper-Clad Aluminum Reference:340.104 67. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Electrical disconnect Service switch Service disconnect Utility disconnect Reference:230.70 B 68. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) All types of One- and two-family dwelling and multifamily only Commercial and industrial only One- and two-family dwelling units only Reference:230.70 D 69. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Open aquatic vessels or containers Any metal framed container Any aquatic vessels Only bait wells Reference:210.8 B 70. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 18 AWG 16 AWG 14 AWG 20 AWG Reference:210.24(1) 71. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It eliminates primary?side overcurrent protection for transformers under 1 kVA It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating It permits field?installed overcurrent devices to replace listed transformer protection Reference:450.3 72. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Fittings Electrical mechanical supports Meter socket enclosures All electrical equipment Reference:312.3 73. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Installed in a neat and workman-like manner Installed by qualified persons Inspected annually by a third party Inspected by a third party again after installation Reference:393.14 A 74. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site but sized only for the life?safety branch; on?site only On?site and sized to supply the entire EES; either on?site or off?site Off?site and sized to supply the entire EES; on?site only Off?site; off?site only Reference:517.41 A 75. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 550.13 only 406.9 210.52 300.5 Reference:550.13 D 76. 85 – 2026 Changes Part 11New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.) The fittings only The brackets Staples and/or straps The cable only Reference:330.2 77. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 15 amperes 12 amperes 8 amperes 10 amperes Reference:Table 210.24(2) 78. 73 – 2026 Changes Part 11When raceways are installed in a wet location above grade level they now shall _______. (Moisture accumulation can be an issue in environments such as food processing plants, car washes, and swimming pools.) Be designed to drain Have drip loops Use listed fittings that prevent condensation Be nonmetallic Reference:300.11 B 79. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Industrial manufacturing plants Commercial amusement parks with permanent rides Carnivals Permanent theatrical stages only Reference:525.1 80. 150 – 2026 Changes Part 11According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? The combustible floor must be treated with a fire?retardant coating approved by the AHJ Noncombustible protection must be provided under any openings in the bottom of the switchgear The switchgear must be elevated at least 12 inches above the floor No special provisions are required if the switchgear is listed for indoor use Reference:495.36 81. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Counted unless under engineering supervision Not considered as current carrying Considered as current carrying and shall be counted Considered as current carrying but does not need to be counted Reference:310.15 E 82. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Life safety branch and critical branch; division occurs at the service disconnect Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and equipment branch; division occurs at the transfer switches Critical branch and equipment branch; division occurs at the panelboards Reference:517.42 A 83. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) Supervision and only qualified personnel As Assured Equipment Grounding Conductor Program (AEGCP) Equipment design not compatible with GFCI protection These are all requirements for a GFCI exception. Reference:210.8 B ex 2 84. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Felexible sealtight and fittings Flexible metallic raceways and fittings Non-flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Reference:250.102 A 85. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All associated power All remote pumps serving the dispensing devices . All dispensing devices not supplied by intrinsically safe circuits Intrinsically safe electrical equipment Reference:514.11 A 86. 109 – 2026 Changes Part 11According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are permitted only in non?dwelling occupancies Reconditioned wiring devices are not permitted to be used Reconditioned wiring devices are permitted if listed by a third?party refurbisher Reference:406.3 87. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded together using a solid copper conductor sized per Table 250.122 D. No bonding is required if each section has its own feeder disconnect They must be bonded together with a solid copper conductor not smaller than #8 AWG They must be bonded with a minimum #12 copper conductor if GFCI protection is provided Reference: 545.20 D 545.26 88. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is supervised Unless the system is outdoors Unless the system is in an isolated area Within the same room or area Reference:265.63 B 89. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Commercial Temporary Ordinary table 501.10 A 1. & Restricted Reference:501.1 90. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They require special labeling that is not recognized by the NEC They are no longer manufactured in standard voltage classes They cannot be effectively grounded after reconditioning Their dielectric materials and protective mechanisms degrade over time Reference:460.3 91. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Emergency lighting systems in non?healthcare buildings Essential electrical systems in healthcare facilities Legally required standby systems Optional standby systems Reference:517.26 92. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class A fuses Class B fuses Class C fuses Class A Reference:240.7 93. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) The entire circuit shall now be protected AFCI protection can be located at the first switch AFCI protection shall be installed at the overcurrent protection device AFCI protection shall be marked at the first device Reference:210.12 E 94. 102 – 2026 Changes Part 11A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switchessuch as snap switches, dimmers, and electronic controlswere moved to Article 406 as part of a structural reorganization.) The relocation of most device?type switches The expansion of Article 404 to include all wiring devices such as receptacles and GFCIs The elimination of Article 404 and redistribution of its content into Chapter 2 The increase of allowable switch voltage ratings to 2000 volts Reference:404.1 B 95. 4 – 2026 Changes Part 11Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.) Indoor damp and/or wet locations Outdoor wet and damp locations only Outdoor wet locations only Indoor wet locations (damp locations were removed) Reference:210.8 A 96. 137 – 2026 Changes Part 11If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges ) 125 percent 100 percent None of these answers are correct except this one 115 percent Reference:445.13 97. 93 – 2026 Changes Part 11There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.) Three times the minor diameter dimension is allowed. Three times the major diameter dimension is recommended. Five times the major diameter dimension can be used. Five times the minor diameter dimension can be used. Reference:338.24 98. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Straps only Staples 2 hole straps only Hangers only Reference:334.2 99. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) Over 500 volts AC That supply portable or mobile equipment For utilities Over 500 volts DC Reference:270.20 C 100. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 120 volts to ground 300 volts to ground 150 volts to ground 50 volts to ground Reference:410.184 A B Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish