2026 Changes Part 1- AK Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Overvoltage protection Power-Limited Remote-Control Circuits Non-Powered-Limited Signaling circuits All circuits under 100 volts Reference:206.1 2. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 8 amperes 10 amperes 12 amperes 15 amperes Reference:Table 210.24(2) 3. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 14 AWG Aluminum 16 AWG Copper-Clad Aluminum 14 AWG Copper-Clad Aluminum 18 AWG Copper Reference:340.104 4. 160 – 2026 Changes Part 11According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Permitted only when installed in rigid metal conduit Identified for extra?hard usage Suitable for damp locations only Limited to a maximum length of 3 ft Reference:511.10 B 5. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 90 degree C 60 degree C 75 degree C 140 degree F Reference:310.16 6. 197 – 2026 Changes Part 11Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) Only outdoor receptacles require GFCI protection Receptacle outlets must be GFCI?protected only when installed in bathrooms GFCI protection is optional if the receptacle is within sight of the panelboard GFCI protection must be provided as required in 210.8 Reference:550.13 B 7. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Hangers only Straps only 2 hole straps only Staples Reference:334.2 8. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2026 1.1.2027 1.1.2028 1.1.2029 Reference:245.2 9. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection shall be marked at the first device The entire circuit shall now be protected AFCI protection shall be installed at the overcurrent protection device AFCI protection can be located at the first switch Reference:210.12 E 10. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Photovoltaic systems Any power source approved by the authority having jurisdiction Only on?site generators listed for emergency systems Reference:517.30 B 11. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) Any wood decking only A metal-corrugated roof decking only A plywood-type roof decking only All types of roof decking Reference:300.6 E 12. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) The disconnection of surge-protection devices Service disconnects rated under 30 amperes A metering center A switchboard Reference:230.71 A 13. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Sealing the raceway Using galvanized steel Coating the raceway Adding caution tape Reference:342.10 B 14. 21 – 2026 Changes Part 11The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________. to address both dwelling and non-dwelling units to now only require for dwelling units the verbiage to mandate it not be located on the load side (this requirement has been deleted) so the receptacle shall be located within another room Reference:210.63 B 15. 84 – 2026 Changes Part 11__________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.) Brackets Wraps Screws Staples Reference:320.30 A 16. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) Intrinsically safe electrical equipment All remote pumps serving the dispensing devices All associated power . All dispensing devices not supplied by intrinsically safe circuits Reference:514.11 A 17. 132 – 2026 Changes Part 11Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center? 110.21(B) Field?applied hazard markings 110.16 Arc?flash hazard warning 430.102 Disconnecting means for motors 408.4 Circuit directory and identification Reference:430.98 A 18. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Blocking Cable cleats Jacketing Any hangers Reference:330.30 A 19. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where combustible dusts are present in suspension Any location containing Class I or Class II materials Only locations where ignitable fibers are manufactured Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Reference:500.5 20. 190 – 2026 Changes Part 11Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does ) It must be securely installed . It may be run on the ground if marked with caution tape It may be loosely supported if used only during daylight hours It must be installed only on the exterior of the tent or concession Reference:525.22 21. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Motor control centers . Switchboards Switchgear Panelboards Reference:408,3 B 22. 157 – 2026 Changes Part 11Section 501.3(B) of the 2026 NEC is ____________. A requirement for wiring methods in Class I A new requirement for intrinsically safe systems A prohibition on reconditioned equipment in hazardous locations Reserved for future use Reference:501.3 B 23. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) When bundled In crawl spaces Directly buried in the earth When fished between acess points and concealed Reference:334.12 24. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Terminal blocks Internal cable clamps Wire nuts (splicing connectors) Equipment grounding conductors Reference:314.16 B 25. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) Both the panel circuit breaker and HVAC shall be marked with a warning label Marking labels are recommended The panel circuit breaker shall be marked with a warning label The HVAC disconnect shall be marked with a warning label Reference:210.8 F ex 3 26. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible Permissible in commercial applications only Strictly prohibitted Permissible in residential applications only Reference:240.24 E 27. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is installed by the utility All NEC conditions for location It is installed in a bedroom closet It is mounted on the roof Reference:550.51 B 1-7 28. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Type MI fittings Type MI Cable Straps and hangers Reference:332.2 29. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? . A ductless mini?split indoor unit A supplemental electric baseboard heater Lighting outlets required by 210.70 C and receptacles required by 210.63 A A whole?house humidifier Reference:422.12 30. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Industrial manufacturing plants Permanent theatrical stages only Carnivals Commercial amusement parks with permanent rides Reference:525.1 31. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Shall be marked with the location Shall be located but immediately adjacent to the equipment. Can be located elsewhere Can be located downstream Reference:268.91 B 32. 181 – 2026 Changes Part 11When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service? The temporary connection must be sized to accommodate the largest power source The temporary source may be connected only after modifying permanent wiring Integration of the temporary source may delay transfer switch timing if supervised Interlocking is optional if the temporary source is monitored by qualified personnel Reference:517.30 F 1 33. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery enclosures located outdoors Only battery chargers associated with the system Conductive battery stands nly metallic battery terminals Reference:480.8 34. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. On?site and sized to supply the entire EES Off?site and sized to supply the entire EES Off?site and capable of supplying only the life?safety branch On?site but permitted to supply only the critical branch Reference:517.30 A 35. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) All feeder and service Service In areas with rocks only 1000 volts AC or more only Reference:300.7 D3 36. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of copper or brass Identified bimetallic couplings All listed fittings are Bonding jumpers made of brass Reference:342.14 37. 150 – 2026 Changes Part 11According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? Noncombustible protection must be provided under any openings in the bottom of the switchgear No special provisions are required if the switchgear is listed for indoor use The switchgear must be elevated at least 12 inches above the floor The combustible floor must be treated with a fire?retardant coating approved by the AHJ Reference:495.36 38. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Comply with at least 2 subparts Comply with all 3 subparts Be installed according to 1 subpart Combine any 2 subparts to comply Reference:242.14 39. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Legally required standby systems Essential electrical systems in healthcare facilities Emergency lighting systems in non?healthcare buildings Optional standby systems Reference:517.26 40. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 75 feet 50 feet 60 feet 100 feet Reference:225.41 A1 41. 31 – 2026 Changes Part 11Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.) SVC SSS SUS SLS Reference:230.46 note 42. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Section 408.3 Support and arrangement of busbars Reference:408.10 F 43. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded with a minimum #12 copper conductor if GFCI protection is provided They must be bonded together using a solid copper conductor sized per Table 250.122 They must be bonded together with a solid copper conductor not smaller than #8 AWG D. No bonding is required if each section has its own feeder disconnect Reference: 545.20 D 545.26 44. 104 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General?use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) molded-case switches (Breaker type switches) Transfer switches Automatic transfer switches Manual bypass/isolation switches Reference:404.3 B 45. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 5 ft 6 in 6 ft 0 in 7 ft 0 in 6 ft 7 in Reference:404.10 A 2 46. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) The National Electrical Safety Code Article 250 United Laboratories (UL) Article 266 Reference:265.1 47. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Double stripe Green colored stripe Color painted on Single colored stripe other than green Reference:200.7 A 48. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) These are all requirements for a GFCI exception. Equipment design not compatible with GFCI protection Supervision and only qualified personnel Reference:210.8 B ex 2 49. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 80% of the generator nameplate current rating 125% of the generator nameplate current rating 115% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions Reference:445.13 50. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) A minimum of two conduits A minimum of one conduit Each It is recommended that at least 1 conduit Reference:250.109 B2 51. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade or below grade level Only that have a floor located at grade level Regardless of grade level Only that have a floor located below grade level Reference:210.8 A 52. 130 – 2026 Changes Part 11A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design S and Design T motors . Design F and Design G motors Design A and Design D motors Design B(E) and Design C(E) motors Reference:Recognition throughout article 430 53. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Only equipment over 52 Equipment rated not over 15 All equipment over 1 Reference:495.2 AB 54. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Entry height Conduit length Marking requirement Reference:300.9 A 55. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Similar equipment Ductless mini?split systems Wall?mounted room air conditioners Electric baseboard heaters Reference:422.12 ex.#1 56. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside branch circuits and feeders Outside services Indoor branch circuits and feeders All branch circuits and feeders Reference:267.1 57. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Electrical mechanical supports Fittings Meter socket enclosures All electrical equipment Reference:312.3 58. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 10 amperes 12 amperes 8 amperes 15 amperes Reference:Table 210.24(1) 59. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. Article 430 Part IV 501.3 and 505.3 501.10(A)(1) only . 500.8 only Reference:513.3 A 60. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. . Only inside the dispensing device Inside Other than inside or adjacent to the dispensing device Only adjacent to the dispensing device Reference:514.13 61. 85 – 2026 Changes Part 11New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.) The fittings only The brackets The cable only Staples and/or straps Reference:330.2 62. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At the load terminals of the transfer switch At any convenient point in the portable structure At the generator or the first disconnecting means supplied by the generator Only at the service disconnect Reference:525.31 63. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Must not be refurbished Can be reused Are resettable Can be installed if refurbished Reference:242.3 64. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 18 AWG Copper 14 AWG Aluminum 16 AWG Copper 16 AWG Copper-Clad Aluminum Reference:310.5 A 65. 66 – 2026 Changes Part 11A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.) Class 4 circuits Conductors not over 1500 Volts DC Conductors to services Conductors not over 1000 Volts AC Reference:300.1 66. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To eliminate all requirements for oil?filled equipment below 15 kV To allow reconditioned oil?filled equipment to be installed without listing To expand transformer oil?testing requirements to all electrical equipment To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 67. 4 – 2026 Changes Part 11Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.) Indoor wet locations (damp locations were removed) Indoor damp and/or wet locations Outdoor wet and damp locations only Outdoor wet locations only Reference:210.8 A 68. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) Any engineer A qualified individual A master electrician A licensed administrator Reference:266.4 C 69. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Tight threadless couplings used with metal raceways Locknuts Threaded couplings made up wrench?tight Listed bonding bushings with bonding jumpers Reference:500.30 B 70. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 90 percent 100 percent 125 percent 110 percent Reference:265.20 A 71. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) A listed mechanical grounding connector Any split-bolt lug All set-screw style connectors Connectors that do not comply with ANSI/UL 467 standards Reference:250.64 C 72. 185 – 2026 Changes Part 11Diagnostic imaging and treatment equipment shall be installed in accordance with which portion of the NEC?(The 2026 NEC revision clarifies and expands the scope of part five vertical 517 by stating that it applies to all diagnostic imaging and treatment equipment not just x-ray systems ) Article 645 Article 517 Article 700 Article 760 Reference:517.7 73. 138 – 2026 Changes Part 11According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors are installed in rigid metal conduit Only if the tap conductors comply with 240.21(B) Only if the tap conductors are less than 10 ft in length Only if the tap conductors are supervised by an AHJ?approved maintenance program Reference:445.13 B 74. 168 – 2026 Changes Part 11In addition to the off?site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Power production sources Only generators listed for emergency systems Photovoltaic systems only Only energy storage systems listed for standby use Reference:517.4 75. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 12 inches 18 inches 24 inches 6 inches Reference:210.52 A5 76. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Parks and recreation Commercial garages Health care patient rooms Assembly occupancies Reference:406.26 77. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only laser equipment located inside the hazardous location Laser equipment Only equipment specifically listed for Class I Only optical fiber equipment located outside the hazardous location Reference:500.8 G 78. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 12 inches 18 inches 10 inches 6 inches Reference:392.18 F 79. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Reduced-Wall-Thickness Boxes Fastening devices Mounting screws Wagos Reference:314.2 80. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) Any jacket covering A messenger Aluminum conductors A copper-alloy armor Reference:330.10 A 81. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable removal Rejuvenation Cable relocation Cable terminations Reference:315.3 82. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) The National Electrical Code tables only A local utility company A qualified person The authority having jurisdiction (AHJ) Reference:268.42 C 83. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed with AHJ guidance Shall not be installed Can be installed if the enclosure is indoors Can be installed Reference:250.64 G 84. 36 – 2026 Changes Part 11The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.) Qualifiers Does not qualify Can qualify if listed Can qualify if listed SVC Reference:230.70 F 85. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) Provided under engineering supervision Located outdoors Based on temperature rise In a campus environment Reference:265.19 B 86. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be installed only in dwelling-unit bedrooms It shall be supplied only by a Class 2 power source only It shall be a blank faceplate with no openings It shall be listed as a combination faceplate assembly Reference:406.16 D 87. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) A non-metallic enclosure A minimum 6 AWG copper grounding electrode conductor A satellite electrode Any location inside Reference:250.94 A 88. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 300 volts to ground 120 volts to ground 50 volts to ground 150 volts to ground Reference:410.184 A B 89. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 15 ampere 20 ampere 30 ampere 10 ampere Reference:210.22 ex 90. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Branch circuits with AFCI protection Multiwire branch circuits Individual branch circuits Branch circuits supplied from emergency sources Reference:517.15 91. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Only equipment installed in permanent studio structures Alternating?current power distribution boxes Only generators rated over 15 kW Only luminaires used for egress lighting Reference:530.2 92. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It permits field?installed overcurrent devices to replace listed transformer protection It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating It eliminates primary?side overcurrent protection for transformers under 1 kVA Reference:450.3 93. 128 – 2026 Changes Part 11The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Electric baseboard heaters Embedded snow?melting mats Baseboard heater raceways Unit heater fan motors Reference:424.2 94. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is outdoors Unless the system is in an isolated area Within the same room or area Unless the system is supervised Reference:265.63 B 95. 29 – 2026 Changes Part 11The NEC requirement to list service equipment as suitable as service has been consolidated into a list format and now includes _________. (An increasing emphasis on listing ensuring product safety through third party certification. AVTs are used to verify that circuits are de-energized.) Utility power company owned transfer switches All meter sockets Permanently mounted absence of voltage testers (AVTs) Power distribution blocks only Reference:230.2 A 96. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only Category 1 and Category 2 spaces Only Category 3 and Category 4 spaces Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only the category assigned by the authority having jurisdiction Reference:517.7 & Informational note 97. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Straps and hangers Straps Staples Hangers Reference:332.3 98. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only grounding and bonding conductors associated with the service Only conductors intended for termination within that section Any feeder conductors passing through to adjacent equipment Any control conductors associated with the same building Reference:408.10 2 99. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 500 amperes 1000 amperes 800 amperes 600 amperes Reference:215.10 B 100. 174 – 2026 Changes Part 11Receptacles and fixed equipment in wet?procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple ) A system supplied from an isolated power source without GFCI protection Individual GFCI devices installed at each receptacle only A system protected only by an equipment grounding conductor A power distribution system in which the entire system is protected by a single GFCI device Reference:517.20 A 3 a b Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish