2026 Changes Part 1- ID Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Similar equipment Ductless mini?split systems Electric baseboard heaters Wall?mounted room air conditioners Reference:422.12 ex.#1 2. 8 – 2026 Changes Part 11For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.) Assured Grounding Listed Class C SPGFCI protection is permitted instead of GFCI GFCI protection is only suggested now. There are no longer exceptions; it shall be GFCI protected. Reference:210.8 F ex 3 3. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Shall be located but immediately adjacent to the equipment. Shall be marked with the location Can be located elsewhere Can be located downstream Reference:268.91 B 4. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) The disconnection of surge-protection devices A metering center Service disconnects rated under 30 amperes A switchboard Reference:230.71 A 5. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A qualified individual Any engineer A licensed administrator A master electrician Reference:266.4 C 6. 156 – 2026 Changes Part 11 Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? All reconditioned equipment must be listed and marked Explosion Proof regardless of original classification Reconditioned equipment is permitted Reconditioned equipment is prohibited in all hazardous locations unless field evaluated by the AHJ Only equipment located outside the hazardous location requires reconditioning evaluation Reference:501.3 7. 166 – 2026 Changes Part 11 Emergency electrical disconnects for fuel‑dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All associated power All dispensing devices not supplied by intrinsically safe circuits Intrinsically safe electrical equipment All remote pumps serving the dispensing devices Reference:514.11 A 8. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 6 inches 10 inches 12 inches 18 inches Reference:392.18 F 9. 148 – 2026 Changes Part 11 According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating means are required unless the equipment can be deenergized by other methods such as draw out units non load break isolating switches must be interlocked with a series interrupting device or field marked with a warning Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches must always be load?break rated and are required for all equipment regardless of design Reference:495.22 10. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Felexible sealtight and fittings Non-flexible metallic raceways and fittings Reference:250.102 A 11. 167 – 2026 Changes Part 11 Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Other than inside or adjacent to the dispensing device Only adjacent to the dispensing device Only inside the dispensing device Inside Reference:514.13 12. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Wet locations Indoor dry locations only Hazardous (Class I Corrosive locations only Reference:495.4 13. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) Article 266 United Laboratories (UL) Article 250 The National Electrical Safety Code Reference:265.1 14. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? . The nearest doorway The ceiling height The top of the equipment enclosure The floor or working platform Reference:404.10 A 2 15. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 80% of the generator nameplate current rating 125% of the generator nameplate current rating 115% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions Reference:445.13 16. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) Interlocking is optional if the temporary source is supervised by qualified personnel The temporary source may be smaller than the on?site source if load shedding is used The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements Reference:517.30 E 4 17. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 14 AWG Aluminum 16 AWG Copper-Clad Aluminum 18 AWG Copper 16 AWG Copper Reference:310.5 A 18. 157 – 2026 Changes Part 11Section 501.3(B) of the 2026 NEC is ____________. A new requirement for intrinsically safe systems A requirement for wiring methods in Class I Reserved for future use A prohibition on reconditioned equipment in hazardous locations Reference:501.3 B 19. 160 – 2026 Changes Part 11 According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Permitted only when installed in rigid metal conduit Suitable for damp locations only Identified for extra-hard usage Limited to a maximum length of 3 ft Reference:511.10 B 20. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) Only if the common electrode terminates in one of the enclosures As permitted by" the AHJ When installed "in accordance with" the technical NEC requirements As permitted by" a licensed electrical engineer Reference:250.64 D1 21. 191 – 2026 Changes Part 11 Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting ) Egress lighting may be provided by any portable lamp or cord‑and‑plug device Lamp guards are optional if the wiring is GFCI‑protected Bare lamps are permitted if located above 8 ft Lamps for general illumination must be protected by a luminaire or a lamp holder with a guard, and luminaires used for egress lighting must be listed Reference:525.25 A B 22. 115 – 2026 Changes Part 11 Receptacles shall not be installed in a face‑up position in which of the following locations? (The NEC prohibits installing receptacles face‑up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) In a laundry area On walls adjacent to countertops Under raised floors in IT rooms On work surfaces Reference:406.14 G 23. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) Only at the service disconnect At the generator or the first disconnecting means supplied by the generator At the load terminals of the transfer switch At any convenient point in the portable structure Reference:525.31 24. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed Can be installed if the enclosure is indoors Can be installed with AHJ guidance Shall not be installed Reference:250.64 G 25. 149 – 2026 Changes Part 11 Which of the following correctly describes the requirements for grounding switches used in medium‑ and high‑voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches only need to be interlocked with the service disconnect, not with other power sources feeding the equipment Grounding switches are required to be load‑break rated and may be used as the primary disconnecting means Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding, and cannot be closed while the grounding switch is in the grounded position Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Reference:495.26 26. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Inspected annually by a third party Installed by qualified persons Installed in a neat and workman-like manner Inspected by a third party again after installation Reference:393.14 A 27. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. 20 amp grounding type receptacles AFCI receptacles Grounding type receptacles All of these answers are false Reference:406.12 D 1 28. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Shall be located adjacent to the disconnect Must have a black background Must have a red text Letters shall be at least 1/2 inch high Reference:230.70 B2 29. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Single colored stripe other than green Green colored stripe Color painted on Double stripe Reference:200.7 A 30. 174 – 2026 Changes Part 11 Receptacles and fixed equipment in wet‑procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple ) A system supplied from an isolated power source without GFCI protection Individual GFCI devices installed at each receptacle only A system protected only by an equipment grounding conductor A power distribution system in which the entire system is protected by a single GFCI device Reference:517.20 A 3 a b 31. 139 – 2026 Changes Part 11According to the 2026 NEC the terminology for generator remote emergency shutdown has been modernized by replacing an old term emergency stop switch with_______. (This update reflects the evolution of generator control technologies which increasingly rely on digital systems programmable interfaces and network control circuits rather than physical traditional switches ) Emergency disconnect Generator lockout switch Remote trip mechanism Shutdown device Reference:445.19 B 32. 181 – 2026 Changes Part 11 When an EES uses more than one on-site power source, which of the following is REQUIRED when any single on-site source is disabled for service? The temporary connection must be sized to accommodate the largest power source Interlocking is optional if the temporary source is monitored by qualified personnel The temporary source may be connected only after modifying permanent wiring Integration of the temporary source may delay transfer switch timing if supervised Reference:517.30 F 1 33. 130 – 2026 Changes Part 11 A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design A and Design D motors Design B(E) and Design C(E) motors Design S and Design T motors Design F and Design G motors Reference:Recognition throughout article 430 34. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Any aquatic vessels Only bait wells Open aquatic vessels or containers Any metal framed container Reference:210.8 B 35. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Switchgear Panelboards Motor control centers . Switchboards Reference:408,3 B 36. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Straps only Hangers only 2 hole straps only Staples Reference:334.2 37. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Only applies to rigid conduit methods Applies even when you transition and combine raceway types Does not apply to flexible conduits Only applies to each raceway type in the run Reference:300.24 38. 168 – 2026 Changes Part 11 In addition to the off‑site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Only energy storage systems listed for standby use Only generators listed for emergency systems Photovoltaic systems only Power production sources, fuel cell systems, energy storage systems, and healthcare microgrids Reference:517.4 39. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) Only the largest source must be bonded to the structures grounding electrode Bonding is optional if all generators are rated less than 15 kW The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 . Each source must have an isolated equipment grounding conductor Reference:525.12 40. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Green covered conductor Light green insulated conductor Green conductor with a yellow stripe Yellow insulated conductor with a green stripe Reference:250.119 A2 41. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel These are all requirements for a GFCI exception. Equipment design not compatible with GFCI protection Reference:210.8 B ex 2 42. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It eliminates primary?side overcurrent protection for transformers under 1 kVA It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating It permits field?installed overcurrent devices to replace listed transformer protection Reference:450.3 43. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Installed in accordance with Article 410 only Marked suitable for damp locations Installed by a qualified person and approved by the manufacturer Listed for the location and listed for field installation with the luminaire being retrofitted Reference:501.130 C 44. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) Only one is needed if it complies with 225.41 The disconnects shall be installed inside out of the weather Both disconnects shall be installed An emergency disconnecting means is no longer required Reference:225.31 A, 4 1 45. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Cable cleats Blocking Any hangers Jacketing Reference:330.30 A 46. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Coating the raceway Sealing the raceway Using galvanized steel Adding caution tape Reference:342.10 B 47. 135 – 2026 Changes Part 11 According to 2026 NEC the outdoor disconnecting means for a split‑system HVAC unit in other than one‑ and two‑family dwellings must be marked with which of the following? The location of all indoor units it supplies, in accordance with 110.22(A) The manufacturer’s installation instructions for both indoor and outdoor units The location of the branch-circuit overcurrent device supplying the outdoor unit, in accordance with 110.22(A) The minimum circuit ampacity and maximum fuse size for the outdoor unit Reference:440.15 48. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. On?site but permitted to supply only the critical branch Off?site and capable of supplying only the life?safety branch Off?site and sized to supply the entire EES On?site and sized to supply the entire EES Reference:517.30 A 49. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) One- and two-family dwelling units only Commercial and industrial only One- and two-family dwelling and multifamily only All types of Reference:230.70 D 50. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Only generators rated over 15 kW Only equipment installed in permanent studio structures Alternating?current power distribution boxes Only luminaires used for egress lighting Reference:530.2 51. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class B fuses Class A Class A fuses Class C fuses Reference:240.7 52. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 140 degree F 60 degree C 90 degree C 75 degree C Reference:310.16 53. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 inch thick 1 1/2 inch thick 2 inches thick 1 3/4 inch thick Reference:300.6 E 54. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 25 or 21 S Type 2C or 11C Type 11 Type 21C Reference:300.13 E 55. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? shall have a plan review Standard off?the?shelf listed assemblies Field?assembled systems supervised by the installer Site?specific engineered designs by both civil and electrical engineers Reference:426.64 56. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 15 amperes 10 amperes 8 amperes 12 amperes Reference:Table 210.24(2) 57. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 100 feet 50 feet 60 feet 75 feet Reference:225.41 A1 58. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Only grounding and bonding conductors associated with the service Any feeder conductors passing through to adjacent equipment Any control conductors associated with the same building Reference:408.10 2 59. 42 – 2026 Changes Part 11A new code section for overcurrent protection now covers and introduces the new term “transformer secondary conductors,” and they are permitted to be ________. (This change separates feeder tap conductor from the transformer secondary rules.) Tapped without restrictions Considered protected without overcurrent protection at the secondary Always installed without protection regardless of length Considered protected without overcurrent protection Reference:240.21 B3 and 240.21 C 60. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Terminal blocks Wire nuts (splicing connectors) Equipment grounding conductors Internal cable clamps Reference:314.16 B 61. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? . Reconditioned resistors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed Both reconditioned reactors and reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed Reference:470.3 A B 62. 128 – 2026 Changes Part 11 The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Electric baseboard heaters Unit heater fan motors Embedded snow-melting mats Baseboard heater raceways Reference:424.2 63. 51 – 2026 Changes Part 11In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.) All raceways Nonferrous metal enclosures All metallic raceways Ferrous metal cable armor raceways Reference:250.64 E1 64. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) It is recommended that at least 1 conduit A minimum of two conduits A minimum of one conduit Each Reference:250.109 B2 65. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? article 406 Article 210 Article 314 Article 110 Reference:406 66. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 250.8(A)(1) through (A)(6) 110.26(A)(1) through (A)(3) 300.5(A) through (A)(4) 547.44(C)(1) through 547.44(C)(4) Reference:547.44 C 67. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) All feeder and service 1000 volts AC or more only Service In areas with rocks only Reference:300.7 D3 68. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 600 amperes 400 amperes 800 amperes 1000 amperes Reference:230.95 69. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located at least 15 ft from the operator station to prevent accidental operation It must be located inside a locked room accessible only to qualified personnel It must be within sight and within 6 ft of the operator station and readily accessible during operation It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 A 70. 163 – 2026 Changes Part 11 Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Class I Class II Unclassified locations only Class I, Division 2 or Zone 2, as applicable Reference:512.21 71. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To eliminate all requirements for oil?filled equipment below 15 kV To allow reconditioned oil?filled equipment to be installed without listing To expand transformer oil?testing requirements to all electrical equipment To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 72. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Temporary table 501.10 A 1. & Restricted Ordinary Commercial Reference:501.1 73. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery chargers associated with the system nly metallic battery terminals Conductive battery stands Only battery enclosures located outdoors Reference:480.8 74. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Can be reused Must not be refurbished Can be installed if refurbished Are resettable Reference:242.3 75. 134 – 2026 Changes Part 11 If the disconnecting means for air‑conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must be marked with a warning label indicating that energized parts are present It must be locked or require a tool to be opened It must be interlocked with the controller to prevent operation It must automatically de‑energize the equipment when opened Reference:440.11 76. 150 – 2026 Changes Part 11 According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? No special provisions are required if the switchgear is listed for indoor use The combustible floor must be treated with a fire-retardant coating approved by the AHJ The switchgear must be elevated at least 12 inches above the floor Noncombustible protection must be provided under any openings in the bottom of the switchgear Reference:495.36 77. 84 – 2026 Changes Part 11__________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.) Brackets Screws Wraps Staples Reference:320.30 A 78. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) When fished between acess points and concealed In crawl spaces When bundled Directly buried in the earth Reference:334.12 79. 125 – 2026 Changes Part 11 The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A supplemental electric baseboard heater A whole‑house humidifier A ductless mini‑split indoor unit Lighting outlets required by 210.70 C and receptacles required by 210.63 A Reference:422.12 80. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It may be bonded with aluminum conductors if not subject to corrosion It must be bonded with a #12 copper conductor to any nearby metal object It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be connected only to the service neutral Reference:547.44 B 81. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) A messenger Any jacket covering Aluminum conductors A copper-alloy armor Reference:330.10 A 82. 197 – 2026 Changes Part 11 Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) Only outdoor receptacles require GFCI protection GFCI protection must be provided as required in 210.8 GFCI protection is optional if the receptacle is within sight of the panelboard Receptacle outlets must be GFCI protected only when installed in bathrooms Reference:550.13 B 83. 93 – 2026 Changes Part 11There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.) Five times the major diameter dimension can be used. Three times the major diameter dimension is recommended. Three times the minor diameter dimension is allowed. Five times the minor diameter dimension can be used. Reference:338.24 84. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site and sized to supply the entire EES; either on?site or off?site Off?site and sized to supply the entire EES; on?site only Off?site; off?site only On?site but sized only for the life?safety branch; on?site only Reference:517.41 A 85. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. all these answers are true 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 86. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) Listed smoke detection systems Video monitoring systems Type 3 surge-protection devices AVTs (absence of voltage testers) Reference:230.82 87. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of copper or brass Identified bimetallic couplings All listed fittings are Bonding jumpers made of brass Reference:342.14 88. 146 – 2026 Changes Part 11 According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Equipment rated not over 15,000 volts must be listed by January 1, 2029, and equipment rated over 15,000 volts up to 52,000 volts must be listed by January 1, 2032 Only equipment over 52,000 volts must be listed, effective January 1, 2032 Only equipment over 52,000 volts must be listed, effective January 1, 2027 Reference:495.2 AB 89. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) A local utility company The authority having jurisdiction (AHJ) A qualified person The National Electrical Code tables only Reference:268.42 C 90. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade or below grade level Only that have a floor located below grade level Regardless of grade level Only that have a floor located at grade level Reference:210.8 A 91. 153 – 2026 Changes Part 11 According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 μm wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only optical fiber equipment located outside the hazardous location Only laser equipment located inside the hazardous location Only equipment specifically listed for Class I Laser equipment Reference:500.8 G 92. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Meter socket enclosures Electrical mechanical supports All electrical equipment Fittings Reference:312.3 93. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Emergency service facility sleeping quarters like police stations Break and quiet rooms All commercial occupancies All occupancies Reference:215.18 A 94. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are permitted if a warning label is also provided are allowed are not permitted unless with a manual bypass are never allowed Reference:210.70 C3 95. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where ignitable fibers are manufactured Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where combustible dusts are present in suspension Any location containing Class I or Class II materials Reference:500.5 96. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Can not Shall not May Shall Reference:342.29 97. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection shall be installed at the overcurrent protection device AFCI protection shall be marked at the first device The entire circuit shall now be protected AFCI protection can be located at the first switch Reference:210.12 E 98. 138 – 2026 Changes Part 11 According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors are supervised by an AHJ‑approved maintenance program Only if the tap conductors are less than 10 ft in length Only if the tap conductors comply with 240.21(B), and taps are not permitted for portable generators rated 15 kW or less where field wiring terminals are not accessible Only if the tap conductors are installed in rigid metal conduit Reference:445.13 B 99. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Within the same room or area Unless the system is outdoors Unless the system is supervised Unless the system is in an isolated area Reference:265.63 B 100. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 1.0 second 0.05 second 0.1 second 0.01 second Reference:517.42 F Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish