2026 Changes Part 1- ID Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Legally required standby systems Essential electrical systems in healthcare facilities Emergency lighting systems in non?healthcare buildings Optional standby systems Reference:517.26 2. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Listed or field evaluated Listed as suitable for service only Field evaluated only Additionally certified Reference:230.2 B 3. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) Only if the common electrode terminates in one of the enclosures As permitted by" a licensed electrical engineer As permitted by" the AHJ When installed "in accordance with" the technical NEC requirements Reference:250.64 D1 4. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 314 article 406 Article 210 Article 110 Reference:406 5. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 14 AWG Aluminum 18 AWG Copper 16 AWG Copper-Clad Aluminum 14 AWG Copper-Clad Aluminum Reference:340.104 6. 132 – 2026 Changes Part 11Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center? 110.16 Arc?flash hazard warning 408.4 Circuit directory and identification 110.21(B) Field?applied hazard markings 430.102 Disconnecting means for motors Reference:430.98 A 7. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety Section 408.3 Support and arrangement of busbars Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Reference:408.10 F 8. 133 – 2026 Changes Part 11Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit ) None of these answers are correct Purchased from the manufacturer of the HVAC unit being worked on Inspected by the AHJ (Authority having jurisdiction ) Listed as a field installable accessory Reference:440.2 9. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Commercial garages Parks and recreation Health care patient rooms Assembly occupancies Reference:406.26 10. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Green colored stripe Color painted on Single colored stripe other than green Double stripe Reference:200.7 A 11. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. 501.10(A)(1) only 501.3 and 505.3 Article 430 Part IV . 500.8 only Reference:513.3 A 12. 177 – 2026 Changes Part 11A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state? Caution Multiple power sources supplied from separate feeders Hazardous voltage may be present even when equipment is off Disconnect all sources before servicing equipment Warning Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized Reference:517.28 B 13. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) A qualified person The authority having jurisdiction (AHJ) A local utility company The National Electrical Code tables only Reference:268.42 C 14. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is supervised Unless the system is in an isolated area Unless the system is outdoors Within the same room or area Reference:265.63 B 15. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) Video monitoring systems Listed smoke detection systems AVTs (absence of voltage testers) Type 3 surge-protection devices Reference:230.82 16. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only standby battery systems used for emergency power ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only lithium?ion battery systems installed indoors Only battery systems connected to renewable?energy equipment Reference:480.1 17. 11 – 2026 Changes Part 11Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.) 1500 2400 2500 2000 Reference:210.13 A&B 18. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must automatically de?energize the equipment when opened It must be interlocked with the controller to prevent operation It must be locked or require a tool to be opened Reference:440.11 19. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Any conductor Copper-Clad Aluminum Conductors Pneumatic lines Surge protection devices Reference:392.22 B 20. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Reduce Overrides Are in addition to Substitute Reference:225.1 Note 2 21. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) Equipment design not compatible with GFCI protection As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel These are all requirements for a GFCI exception. Reference:210.8 B ex 2 22. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Installed by qualified persons Inspected by a third party again after installation Inspected annually by a third party Installed in a neat and workman-like manner Reference:393.14 A 23. 163 – 2026 Changes Part 11Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Class II Class I Unclassified locations only Reference:512.21 24. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 14 AWG 20 AWG 16 AWG 18 AWG Reference:210.24(1) 25. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The top of the equipment enclosure . The nearest doorway The ceiling height The floor or working platform Reference:404.10 A 2 26. 66 – 2026 Changes Part 11A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.) Conductors not over 1000 Volts AC Conductors to services Class 4 circuits Conductors not over 1500 Volts DC Reference:300.1 27. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A metering center A switchboard Service disconnects rated under 30 amperes The disconnection of surge-protection devices Reference:230.71 A 28. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Only bait wells Any aquatic vessels Any metal framed container Open aquatic vessels or containers Reference:210.8 B 29. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Any fixed cabinet Only fixed cabinets with a work surface Only fixed cabinets with countertops Only fixed cabinets that are not recessed Reference:210.52 A2(1) 30. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The temporary source may be smaller than the on?site source if load shedding is used The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements Interlocking is optional if the temporary source is supervised by qualified personnel Reference:517.30 E 4 31. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Any hangers Blocking Cable cleats Jacketing Reference:330.30 A 32. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2028 1.1.2029 1.1.2027 1.1.2026 Reference:245.2 33. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment may be reused if insulation resistance tests pass The equipment shall be replaced unless the installer certifies it The equipment shall be evaluated and approved by the original manufacturer The equipment must be reinspected by the AHJ only Reference:408.3 A 34. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It permits field?installed overcurrent devices to replace listed transformer protection It eliminates primary?side overcurrent protection for transformers under 1 kVA It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating Reference:450.3 35. 160 – 2026 Changes Part 11According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Limited to a maximum length of 3 ft Suitable for damp locations only Identified for extra?hard usage Permitted only when installed in rigid metal conduit Reference:511.10 B 36. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 8 amperes 15 amperes 12 amperes 10 amperes Reference:Table 210.24(1) 37. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 16 AWG Copper 16 AWG Copper-Clad Aluminum 18 AWG Copper 14 AWG Aluminum Reference:310.5 A 38. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 300.5 550.13 only 406.9 210.52 Reference:550.13 D 39. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) Only at the service disconnect At the load terminals of the transfer switch At the generator or the first disconnecting means supplied by the generator At any convenient point in the portable structure Reference:525.31 40. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 70 amperes or less 60 amperes or less 80 amperes or less 100 amperes or less Reference:210.8 F 41. 122 – 2026 Changes Part 11Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 406.12 Tamper?resistant receptacles section 410.184 A and/or B 210.12 AFCI protection 250.114 Equipment grounding conductor requirements Reference:410.184 42. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are permitted if a warning label is also provided are allowed are never allowed are not permitted unless with a manual bypass Reference:210.70 C3 43. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They cannot be effectively grounded after reconditioning They are no longer manufactured in standard voltage classes Their dielectric materials and protective mechanisms degrade over time They require special labeling that is not recognized by the NEC Reference:460.3 44. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 100 percent 90 percent 110 percent 125 percent Reference:265.20 A 45. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Green covered conductor Light green insulated conductor Yellow insulated conductor with a green stripe Green conductor with a yellow stripe Reference:250.119 A2 46. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 4 2 3 5 Reference:406 47. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? Battery?equipped emergency luminaires Energy storage systems . Battery?equipped emergency luminaires Reference:517.28 A ex. 48. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is installed in a bedroom closet It is mounted on the roof All NEC conditions for location It is installed by the utility Reference:550.51 B 1-7 49. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A plywood-type roof decking only Any wood decking only All types of roof decking A metal-corrugated roof decking only Reference:300.6 E 50. 150 – 2026 Changes Part 11According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? The combustible floor must be treated with a fire?retardant coating approved by the AHJ No special provisions are required if the switchgear is listed for indoor use Noncombustible protection must be provided under any openings in the bottom of the switchgear The switchgear must be elevated at least 12 inches above the floor Reference:495.36 51. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Imaging suites used for diagnostic procedures Patient care areas used for direct preparation and care Category 1 treatment rooms used for invasive procedures Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Reference:517.10 B 52. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) Section 300.11 NEMA GD 1-2019 NECA publication 1-23 EEE Chapter 7 Reference:300.4 C 53. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Emergency service facility sleeping quarters like police stations All commercial occupancies All occupancies Break and quiet rooms Reference:215.18 A 54. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. All of the answers are true Service equipment 3-way "snap" switches Pull out switches Reference:404.1 A 55. 181 – 2026 Changes Part 11When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service? Interlocking is optional if the temporary source is monitored by qualified personnel The temporary connection must be sized to accommodate the largest power source Integration of the temporary source may delay transfer switch timing if supervised The temporary source may be connected only after modifying permanent wiring Reference:517.30 F 1 56. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) Marking labels are recommended The HVAC disconnect shall be marked with a warning label Both the panel circuit breaker and HVAC shall be marked with a warning label The panel circuit breaker shall be marked with a warning label Reference:210.8 F ex 3 57. 115 – 2026 Changes Part 11Receptacles shall not be installed in a face?up position in which of the following locations? (The NEC prohibits installing receptacles face?up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) Under raised floors in IT rooms On work surfaces . On walls adjacent to countertops In a laundry area Reference:406.14 G 58. 109 – 2026 Changes Part 11According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted only in non?dwelling occupancies Reconditioned wiring devices are permitted if listed by a third?party refurbisher Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are not permitted to be used Reference:406.3 59. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Shall Can not Shall not May Reference:342.29 60. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Does not apply to flexible conduits Only applies to each raceway type in the run Only applies to rigid conduit methods Applies even when you transition and combine raceway types Reference:300.24 61. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) All circuits under 100 volts Non-Powered-Limited Signaling circuits Overvoltage protection Power-Limited Remote-Control Circuits Reference:206.1 62. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) In a campus environment Based on temperature rise Provided under engineering supervision Located outdoors Reference:265.19 B 63. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Severe cold Smoke damage Water damage Aged over 50 years Reference:300.4 C 64. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Listed for the location and listed for field installation with the luminaire being retrofitted Installed in accordance with Article 410 only Marked suitable for damp locations Installed by a qualified person and approved by the manufacturer Reference:501.130 C 65. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. All of these answers are false Grounding type receptacles 20 amp grounding type receptacles AFCI receptacles Reference:406.12 D 1 66. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Reference:495.22 67. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Similar equipment Electric baseboard heaters Wall?mounted room air conditioners Ductless mini?split systems Reference:422.12 ex.#1 68. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Shall be located but immediately adjacent to the equipment. Shall be marked with the location Can be located elsewhere Can be located downstream Reference:268.91 B 69. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A whole?house humidifier Lighting outlets required by 210.70 C and receptacles required by 210.63 A . A ductless mini?split indoor unit A supplemental electric baseboard heater Reference:422.12 70. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Any control conductors associated with the same building Any feeder conductors passing through to adjacent equipment Only grounding and bonding conductors associated with the service Reference:408.10 2 71. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located below grade level Only that have a floor located at grade level Only that have a floor located at grade or below grade level Regardless of grade level Reference:210.8 A 72. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Wagos Mounting screws Reduced-Wall-Thickness Boxes Fastening devices Reference:314.2 73. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Equipment grounding conductors Terminal blocks Internal cable clamps Wire nuts (splicing connectors) Reference:314.16 B 74. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 600 amperes 1000 amperes 500 amperes 800 amperes Reference:215.10 B 75. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? Standard off?the?shelf listed assemblies shall have a plan review Field?assembled systems supervised by the installer Site?specific engineered designs by both civil and electrical engineers Reference:426.64 76. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts all these answers are true 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 77. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be a blank faceplate with no openings It shall be listed as a combination faceplate assembly It shall be supplied only by a Class 2 power source only It shall be installed only in dwelling-unit bedrooms Reference:406.16 D 78. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and equipment branch; division occurs at the transfer switches Critical branch and equipment branch; division occurs at the panelboards Life safety branch and critical branch; division occurs at the service disconnect Reference:517.42 A 79. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Any location containing Class I or Class II materials Only locations where ignitable fibers are manufactured Only locations where combustible dusts are present in suspension Reference:500.5 80. 135 – 2026 Changes Part 11According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following? The location of all indoor units it supplies The minimum circuit ampacity and maximum fuse size for the outdoor unit The manufacturers installation instructions for both indoor and outdoor units Reference:440.15 81. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 0.05 second 0.01 second 0.1 second 1.0 second Reference:517.42 F 82. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Only equipment installed in permanent studio structures Only generators rated over 15 kW Alternating?current power distribution boxes Only luminaires used for egress lighting Reference:530.2 83. 156 – 2026 Changes Part 11Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Reconditioned equipment is prohibited in all hazardous locations unless field?evaluated by the AHJ Only equipment located outside the hazardous location requires reconditioning evaluation All reconditioned equipment must be listed and marked Explosion?Proof regardless of original classification Reconditioned equipment is permitted Reference:501.3 84. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded together with a solid copper conductor not smaller than #8 AWG They must be bonded together using a solid copper conductor sized per Table 250.122 D. No bonding is required if each section has its own feeder disconnect They must be bonded with a minimum #12 copper conductor if GFCI protection is provided Reference: 545.20 D 545.26 85. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Sealing the raceway Coating the raceway Adding caution tape Using galvanized steel Reference:342.10 B 86. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Hazardous (Class I Wet locations Corrosive locations only Reference:495.4 87. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Laser equipment Only laser equipment located inside the hazardous location Only equipment specifically listed for Class I Only optical fiber equipment located outside the hazardous location Reference:500.8 G 88. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) Over 500 volts AC For utilities Over 500 volts DC That supply portable or mobile equipment Reference:270.20 C 89. 197 – 2026 Changes Part 11Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) GFCI protection is optional if the receptacle is within sight of the panelboard GFCI protection must be provided as required in 210.8 Only outdoor receptacles require GFCI protection Receptacle outlets must be GFCI?protected only when installed in bathrooms Reference:550.13 B 90. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 1500 square feet 1750 square feet 2000 square feet 2400 square feet Reference:334.1 91. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 1/2 inch thick 2 inches thick 1 3/4 inch thick 1 inch thick Reference:300.6 E 92. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 20 AWG 14 AWG 16 AWG 18 AWG Reference:Table 210.24(2) 93. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class B fuses Class A Class A fuses Class C fuses Reference:240.7 94. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Locknuts Listed bonding bushings with bonding jumpers Threaded couplings made up wrench?tight Tight threadless couplings used with metal raceways Reference:500.30 B 95. 149 – 2026 Changes Part 11Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches only need to be interlocked with the service disconnect Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding Grounding switches are required to be load?break rated and may be used as the primary disconnecting means Reference:495.26 96. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) In areas with rocks only All feeder and service Service 1000 volts AC or more only Reference:300.7 D3 97. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Can be installed if refurbished Must not be refurbished Can be reused Are resettable Reference:242.3 98. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible in commercial applications only Permissible in residential applications only Strictly prohibitted Permissible Reference:240.24 E 99. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Only on?site generators listed for emergency systems Any power source approved by the authority having jurisdiction Photovoltaic systems Reference:517.30 B 100. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 10 ampere 30 ampere 15 ampere 20 ampere Reference:210.22 ex Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish