Start OR 6901533 Online 2023 NEC Code Update Part 1 Code Credit (8 Hour CC) Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 200 – 2023 NEC Code Updates Part 1 (01-01)1A revision clarified that the sheath on an NM cable (Romex) shall now officially extend not less than ________ beyond any cable clamp or cable entry. 1/4 inch 1/2 inch 1/8 inch 3/8 inch Reference: 334.19 2. 199 – 2023 NEC Code Updates Part 1 (01-01)1An alteration notes that when NM cable (Romex) is protected from physical damage by sleeving it in a conduit, ________. A bushing or an adaptor shall be installed at the entrance The sheath must be stripped off The raceway can be no longer than 5 feet Only type UF can be used Reference: 334.15 B 3. 198 – 2023 NEC Code Updates Part 1 (01-01)1Type NM cable (Romex) shall be permitted to be installed in multifamily dwellings and ________. (See Annexes for Type III, IV, and V construction.) Their detached garages Commercial structures above a dropped ceiling Motion Picture Studios A club house with an occupancy of 115 Reference: 334.10 4. 197 – 2023 NEC Code Updates Part 1 (01-01)1Type Metal Clad Cable (MC) sizes ________ can be used for control and signal applications. (Previously there was some confusion.) AWG 16.00 AWG 22.00 18 AWG only AWG 20.00 Reference: 330.112 A 5. 196 – 2023 NEC Code Updates Part 1 (01-01)1Copper-Clad Aluminum wire is quickly becoming popular and is now allowed in Metal-Clad Cable (MC) with a minimum conductor size of ________. (The terminals of 15 and 20 ampere switches and receptacles are approved for copper-clad aluminum. 14 AWG CCA conductors would have an ampacity of 10 amperes.) AWG 10.00 AWG 8.00 AWG 2.00 AWG 12.00 Reference: 330.104 6. 195 – 2023 NEC Code Updates Part 1 (01-01)1 Type MC cable can now be used in ________ locations if certain conditions are met. (New MCAP All Purpose uses the aluminum sheath as a grounding path and has a smaller diameter. Some fittings are only listed for the traditional MC.) Areas subject to damage Damp locations Corrosive locations Areas subject to physical damage Reference: 330.10 7. 194 – 2023 NEC Code Updates Part 1 (01-01)1In an accessible attic, the term ________ has replaced “joists” when Armored Cable (type AC) is installed. (Attics do not contain floor joists.) Running boards Framing members Vertical surfaces Attic truss Reference: 320.23 A 8. 193 – 2023 NEC Code Updates Part 1 (01-01)1The scope of Article 315 entitled Medium Voltage Conductors and Cables made clarifications as to what voltages are covered and now includes ________. (Article 311 has been deleted with those requirements now relocated here.) 35,000 volts AC 1,000 volts AC 600 volts AC 480 volts AC Reference: 315.1 9. 192 – 2023 NEC Code Updates Part 1 (01-01)1When an electrical junction box is installed underground by exception the location description shall be available to ________. (See local state rules as well. Commonly done at golf courses for some time.) The public, online The public The general contractor on the site Those authorized to maintain it Reference: 314.29 B ex 10. 191 – 2023 NEC Code Updates Part 1 (01-01)1If listed Weight Supporting Attachment Fittings and Ceiling Receptacles are installed to support equipment, the device ________ be included in the box fill calculations. (These new devices will allow for a quick release and re-connection of fixtures.) Can Does not have to Is recommended to Shall Reference: 314.27 E 11. 190 – 2023 NEC Code Updates Part 1 (01-01)1In addition to the previous NEC requirements for supporting a luminaire (light fixture) or ceiling-suspended fan, (paddle fan), the NEC will now allow ________. (This was requested as a requirement for all fixtures in the NEC but it failed.) Non-rated standard duty plastic boxes Any type of plastic pan box Any type of metallic pan box Weight supporting ceiling receptacles and fittings Reference: 314.27 E 12. 189 – 2023 NEC Code Updates Part 1 (01-01)1Generally, all outlet boxes mounted in ceilings of habitable rooms of dwelling units are required to be listed paddle fan support boxes or now ________. (Before, it was if there was a spare wire. Some now use wireless remotes. 90% of fans sold are aftermarket sales.) Have the locations determined by the owner Use taps screws for the connection Installed to allow access to framing without removing the box Be a metallic junction box Reference: 314.27 C 13. 188 – 2023 NEC Code Updates Part 1 (01-01)1 The code section for outlet boxes for ceiling suspended (paddle) fans was revised to require the boxes to be marked on the ________ as suitable for the purpose. (So, it can be seen during the rough in inspection. No more paddle fan accidents please.) Top of the box Exterior of the box Interior of the box Box the unit was shipped in Reference: 314.27 14. 187 – 2023 NEC Code Updates Part 1 (01-01)1A code section was revised to clarify that conduit body enclosures (like an LB or T) must be enclosed ________. (Because conduit bodies can contain splices.) And marked Gasketed By a cover And sealed Reference: 314.25 15. 186 – 2023 NEC Code Updates Part 1 (01-01)1The 2023 NEC has begun to address clearances for junction boxes with devices from side conductor entries. Now the clearance from the box wall to the installed device shall not be less than ________. (A fire investigation and documentation of damage to conductors in these situations were noted.) 1/4 inch 3/8 inch 1/2 inch 5/8 inch Reference: 314.24 C 16. 185 – 2023 NEC Code Updates Part 1 (01-01)1When calculating box fill for conductors smaller than 4 AWG, a terminal block is now counted as ________ conductor volume based on the largest conductor. (Terminal blocks are being used more frequently and were not addressed in previous versions. The term terminal block accessory was chosen so this does not apply to each pole of a multipole block.) 2 1.5 2.5 1 Reference: 314.16 B 6 17. 184 – 2023 NEC Code Updates Part 1 (01-01)1Restrictions have been added that addresses sharp screw that enter outlet, device, pull, and junction box wiring spaces. An exception includes ________. When the installation was done by a journey level electrician When the installation was done by a qualified person If the screw is within 1/2 inch of the enclosure edge If the end of the screw is protected with an approved means Reference: 314.5 ex 18. 183 – 2023 NEC Code Updates Part 1 (01-01)1A new section was added to also address screws and fasteners entering the wire space of junction boxes and conduit bodies giving us seven options and requirements. One option to install a cover plate is ________. (These situations are commonly encountered in the field.) If sheet rock screws are used, to cut the point off To use a machine type screw with a blunt edge Be sure the conductors are at least 1/2 inch from the attachment screws Be sure that the sheet rock screw extends no more than 5/8 inch Reference: 314.5 19. 182 – 2023 NEC Code Updates Part 1 (01-01)1Field installed screws and fasteners shall be permitted to extend into a cabinet or meter enclosure not more than 7/16 inch if it is located within ________ of an enclosure wall. (The possibility of a greater fault in these enclosures due to limited OCP upstream by the serving utility.) 3/8 inch 5/8 inch 3/4 inch 1/2 inch Reference: 312.10 ex 20. 181 – 2023 NEC Code Updates Part 1 (01-01)1 Generally, when a field installed screw or other fastener without a blunt end is used to secure a phenolic label or cover, the screw shall extend no more than ________ into the cabinet without additional protection. (Damage has been an issue for some time. No more shock or fire hazard please.) 1/8 inch 3/8 inch 1/2 inch 1/4 inch Reference: 312.10 21. 180 – 2023 NEC Code Updates Part 1 (01-01)1A new section was added to recognize that additional bending space is needed for conductors ________ and larger in overcurrent device enclosures. (Similar to the junction box rules.) AWG 6.00 AWG 2.00 AWG 4.00 AWG 8.00 Reference: 312.8 A 22. 179 – 2023 NEC Code Updates Part 1 (01-01)1A new Article 305 now covers the wiring methods and the materials used for systems rated over ________. (This new article attempts to organize medium voltage (MV) information into just one location and not scattered throughout the NEC.) 600 volts AC 1,000 volts AC 480 volts AC 800 volts AC Reference: 305.1 23. 178 – 2023 NEC Code Updates Part 1 (01-01)1Non power limited remote control and signaling circuits are no longer considered to be Class 1 circuits and are now governed by ________. (Where did it belong to begin with?) Article 724 Article 300, 300.2 to 300.25 Article 722.24 Article 725 Reference: 300.26 24. 177 – 2023 NEC Code Updates Part 1 (01-01)1A code section prohibits additional electrical wiring in exit enclosures like fire-rated stairwells. Only electrical wiring serving equipment permitted by ________ shall be installed within the exit enclosure. (Don’t poke holes in stairwells, only stuff that must be there should be in there.) A civil engineer The Authority Having Jurisdiction (AHJ) The building official An electrical engineer Reference: 300.25 25. 176 – 2023 NEC Code Updates Part 1 (01-01)1In an exit stairwell (Stair Tower), the exterior egress lighting at the outside exterior door ________ be supplied by the circuit that supplies lighting in the stair tower. (A stair tower is often considered as like a separate building typically sturdy fire resistant to get folks out without smoke.) Shall not Shall Is permitted to May only if engineered Reference: 300.25 26. 175 – 2023 NEC Code Updates Part 1 (01-01)1Generally, where an exit enclosure (like a structure’s stairwell) is required to be separated, as with a 2-hour firewall separation, ________. (Because penetrations did not get fire stopped, many died in a large fire in Las Vegas. The stairwell filled with smoke and acted like a chimney.) Only rigid or IMC conduit can be installed Only feeders can penetrate these fire exits Only wiring serving that exit enclosure is allowed No penetrations or wiring is allowed Reference: 300.25 27. 174 – 2023 NEC Code Updates Part 1 (01-01)1The number and size of conductors and now also ________ in raceways shall be considered and installed so they are not damaged during and after the installation. (Intent before.) Future mules pull strings Sealants Cables Grounding electrode conductors Reference: 300.17 28. 173 – 2023 NEC Code Updates Part 1 (01-01)1At a junction box, with more than 8 inches in any dimension the length of free conductor shall be at least 6 inches to extend out for makeup. That free conductor ________. To address damage from routers and Sawzall. Note that the smaller J boxes are not mentioned yet.) Shall be un-spliced Shall be spliced Is permitted to be spliced Shall be stranded Reference: 300.14 29. 172 – 2023 NEC Code Updates Part 1 (01-01)1The general rule is that a raceway (conduit) can not be used to support a low voltage cable (like with zip ties) unless that cable is associated for control. These low voltage control cables now include ________. (For the same justification that Class 2 cables are allowed.) Class 1 cables Class 1, 2, 3, and 4 cables Class 3 cables Class 4 cables Reference: 300.11 C 30. 171 – 2023 NEC Code Updates Part 1 (01-01)1When corrosion protection is necessary on conduit that is threaded anywhere other than at the factory, the threads shall be coated with a(n) ________ electrically conductive, corrosion resistant compound. Labeled Marked Common Approved Reference: 300.6 A 31. 170 – 2023 NEC Code Updates Part 1 (01-01)1Electrical Metallic Tubing (EMT) has now been added to the Table for minimum underground cover requirements to indicate that it can be installed in underground locations. EMT shall be buried with a minimum of ________ when installed in a trench under concrete that is 2 inches thick. (Although supplementary corrosion protection (a tape) is generally required unless it is stainless. See State codes also.) 18 inches 12 inches 6 inches 16 inches Reference: Table 300.5 32. 169 – 2023 NEC Code Updates Part 1 (01-01)1Where raceways contain 4 AWG or larger insulated conductors and these conductors enter an enclosure, ________ a bushing or listed fitting shall be used to protect the conductors. Prior to the installation After installation During installation After or prior if the bushing is hinged Reference: 300.4 G 33. 168 – 2023 NEC Code Updates Part 1 (01-01)1A raceway installed under a metal corrugated roof decking is not required to be installed 1.5 inches below the decking if the decking is covered by concrete at least ________ thick. (The substantiation noted that metal roof decking fasteners use longer screw to comply with the roof hod down requirements.) 1/2 inch 2 inches 2 1/2 inches 1 inch Reference: 300.4 E ex 34. 167 – 2023 NEC Code Updates Part 1 (01-01)1Wiring methods now found within Chapter 3 now cover up to 1,000 volts AC and ________ nominal or less. (If not limited within other locations of the NEC.) 2,500 volts DC 3,000 volts DC 2,000 volts DC 1,500 volts DC Reference: 300.2 35. 166 – 2023 NEC Code Updates Part 1 (01-01)1If circuit conductors are spliced in a metal junction box, an equipment grounding conductor connection used for no other purpose shall be made between the metal box and the equipment grounding conductors in accordance with ________. (Before it stated associated conductors, so the circuit grounds were separated.) 250.148 250.146 250.142 Table 250.122 Reference: 250.148 C 36. 165 – 2023 NEC Code Updates Part 1 (01-01)1For metal boxes when equipment grounding conductors are spliced within, a connection used for ________ shall be made between the metal box and the grounding conductors. (A pigtail.) Sizing No other purpose Continuity Attachments Reference: 250.148 C 37. 164 – 2023 NEC Code Updates Part 1 (01-01)1Generally, if circuit conductors are spliced in a multi-gang junction box, all the equipment grounding conductors associated with ________ those circuit conductors shall be connected within the box. (Now a blue wire nut may not be large enough to co-mingle all these different circuit grounding conductors together.) Only All and any of Some of None of Reference: 250.148 38. 163 – 2023 NEC Code Updates Part 1 (01-01)1A modified subsection now specifies that ________ equipment grounding conductors (EGCs) spliced or terminated within a box be connected together. (Seems like I have seen this change back and forth in the NEC.) All, even if they are for different circuits It is optional It is optional if there is a redundant path All, unless they are for different circuits Reference: 250.148 A 39. 162 – 2023 NEC Code Updates Part 1 (01-01)1A new revision has provided an alternative to having to replace an existing three wire nonmetallic sheathed cable for a range or clothes dryer when it is updated and should be a four wire. If the existing branch circuit is a type of SE cable ________ when there is only a neutral grounded conductor to a range or dryer. It cannot be used It shall be replaced An equipment grounding conductor can be added The grounded conductor con be used if it is insulated or covered Reference: 250.140 B 40. 161 – 2023 NEC Code Updates Part 1 (01-01)1 When the replacement of an existing snap switch without an equipment grounding terminal occurs with on that does, ________. (Only receptacles were addressed before.) An equipment grounding conductor shall be added This is a code violation The location shall be marked The terminal can be connected to the grounding electrode system Reference: 250.130 41. 160 – 2023 NEC Code Updates Part 1 (01-01)1The section covering types of Equipment Grounding Conductors was reformatted into two subdivisions with permitted and not permitted. ________ shall not be permitted to be used as an Equipment Grounding Conductor. Copper-Clad Aluminum Armor of Type AC cable Cable Trays Grounding Electrode Conductors Reference: 250.118 B 42. 159 – 2023 NEC Code Updates Part 1 (01-01)1Metal enclosures shall be permitted to be used to become part of an effective ground fault path. If metal covers or external extension rings are attached ________. These methods are all allowed The path must be ensured It can be connected by an equipment grounding conductor It can be connected by a bonding jumper Reference: 250.109 43. 158 – 2023 NEC Code Updates Part 1 (01-01)1 An alternative to the requirement for an “Intersystem Bonding Termination Device” to create a location for other systems to bond to the electrical system, is for a busbar. The busbar shall be connected to the grounded electrode system by a conductor sized ________. (The requirement for an accessible point for bonding other systems started for dwelling units in the 1981 NEC. It is considered an important safety measure to prevent possible differences in voltage potentials.) A minimum 6 AWG copper A minimum 10 AWG copper or 8 AWG aluminum A minimum 8 AWG copper To the largest electrode conductor that is connected to the busbar Reference: 250.94 B 44. 157 – 2023 NEC Code Updates Part 1 (01-01)1A clarification notes that an Intersystem Bonding Termination Device is now to be ________. (This device acts as a location for other systems (such as cable TV) to connect their grounding electrodes at a service location externally to that service for easy safe access.) Recommended Securely mounted Optional A 6 AWG conductor Reference: 250.94 A 45. 156 – 2023 NEC Code Updates Part 1 (01-01)1The methods used for grounding and bonding conductor connections to the electrodes have been changed and updated. They now also note that listed ground clamps that are identified for direct burial ________. Can be installed in corrosive environments Are not suitable for concrete encasement Is also suitable for concrete encasement Shall not be used above grade Reference: 250.70 notes 46. 155 – 2023 NEC Code Updates Part 1 (01-01)1A new code section was added to ________ grounding electrode conductors (to ground rods, etc.) being run through equipment ventilation openings. (Such as on the bottom of a transformer.) Require Prohibit Allow Consider Reference: 250.64 G 47. 154 – 2023 NEC Code Updates Part 1 (01-01)1A minimum of ________ is required when PVC conduit is used for protection for a Copper-Clad Aluminum grounding electrode conductor from physical damage. (What if it is not subject to physical damage and it is only being done because it looks prettier?) Schedule 20 Schedule 40 Copper-Clad is not allowed here Schedule 80 Reference: 250.64 B 2 48. 153 – 2023 NEC Code Updates Part 1 (01-01)1When it comes to a grounding electrode system, the term “reinforcing steel or rods” has been replaced with ________. (To make it easier to understand in the field and the construction industry.) Ground ring Building steel Bonding mesh Rebar Reference: 250.52 A 3 49. 152 – 2023 NEC Code Updates Part 1 (01-01)1An Impedance Grounded System where one phase is grounded shall be permitted for three phase AC systems of ________. (The conductor that connects the neutral point through impedance is no longer referred to as a grounded conductor or neutral conductor. This strange and dangerous animal must be supervised and maintained by qualified persons usually in an industrial facility.) 480 volts 208 volts 277 volts 360 volts Reference: 250.36 50. 151 – 2023 NEC Code Updates Part 1 (01-01)1When ungrounded service entrance conductors (hots) are connected in parallel (multiple) runs of two or more raceways, the grounded conductors (neutrals) ________. (The word “connected” has also replaced “installed”.) Must be sized at 125 percent Can be sized based on that single run Shall be connected and installed in parallel Can be just a single run Reference: 250.24 D 51. 150 – 2023 NEC Code Updates Part 1 (01-01)1 Alternating Current (AC) Systems shall be grounded as per Article 250, ________. (There are different types of systems out there.) Except for some equipment in hospitals Unless prohibited elsewhere in the NEC Unless there is a step-up transformer At all times Reference: 250.20 52. 149 – 2023 NEC Code Updates Part 1 (01-01)1A change in Article 250 provides remedies to objectional currents resulting from ________. Poor workmanship Ground faults Multiple bonding connections Arc faults Reference: 250.6 B 53. 148 – 2023 NEC Code Updates Part 1 (01-01)1The requirements for overcurrent protection of circuits rated greater than 1,000 volts AC or 1,500 volts DC are found in new Article ________. (Medium voltage requirements are now for the most part found in their own articles. It consists of language previously found in 240 and 490.) 245 212 239 215 Reference: 245.1 54. 147 – 2023 NEC Code Updates Part 1 (01-01)1The duty cycle rating of a surge arrester is now required to be not less than ________ of the maximum system voltage available. 100 percent 80 percent 125 percent 115 percent Reference: 242.42 55. 146 – 2023 NEC Code Updates Part 1 (01-01)1There is a new requirement that surge protective devices (SPDs) provide an indication that they are ________. (So, they can be replaced when they reach the end of their life.) Energized Failing Tripped Functioning properly Reference: 242.9 56. 145 – 2023 NEC Code Updates Part 1 (01-01)1When Surge Protective Devices (SPDs) and surge arrestors reach the end of their usable life span they can ________. (The NEC addressing overvoltage now.) Be remanufactured Not be reconditioned Be reconditioned Be refurbished Reference: 242.2 57. 144 – 2023 NEC Code Updates Part 1 (01-01)1The prohibition against locating branch circuit overcurrent devices in some bathrooms has been expanded to include ________. (Addresses the difficulty with access when occupied.) Dormitory units School nursing areas Assisted living units Locker rooms with showers Reference: 240.24 E 58. 143 – 2023 NEC Code Updates Part 1 (01-01)1Generally, switches containing fuses and circuit breakers shall be readily accessible. An exception would be ________. (This was a problem for certain locations.) For busways in industrial environments For any commercial location The use of a tool for an enclosure to protect against environmental conditions For a one- or two-family dwelling unit Reference: 240.24 A ex 59. 142 – 2023 NEC Code Updates Part 1 (01-01)1Circuit breakers shall be readily accessible and not need a tool to access it. Exceptions were clarified to now include ________. (An example would be a Type 4x steel panel with bolts around the perimeter.) All enclosures when installed lower than 6 feet 7 inches Enclosures in commercial locations Enclosures designed for hazardous locations All enclosures when installed in an electrical equipment room Reference: 240.24 A ex 60. 141 – 2023 NEC Code Updates Part 1 (01-01)1The minimum interrupting rating of a branch circuit overcurrent protective device like a circuit breaker is _________. (Existing circuit breakers that are not marked should be considered as 5,000 amperes.) 5,000 amperes 12,000 amperes 10,000 amperes 20,000 amperes Reference: 240.16 61. 140 – 2023 NEC Code Updates Part 1 (01-01)1If one feeder overcurrent protective device (breaker) is required to be selectively coordinated with the service overcurrent device, ________ feeder device(s) supplied by the service shall be selectively coordinated as well. (An overcurrent condition on one of the other feeders can and often does open and trip the service device.) Some One No other All Reference: 240.11 62. 139 – 2023 NEC Code Updates Part 1 (01-01)1A new section has clarified that branch circuit overcurrent protective devices, relays and circuit breakers that provide ground fault protection must be ________. (No more counterfeit devices please.) Field evaluated Noted Identified Listed Reference: 240.7 63. 138 – 2023 NEC Code Updates Part 1 (01-01)1Provisions were added by CMP-10 to ________ remote access to adjustable trip circuit breakers through the internet. (Adjustments made from your office. Provisions were also added to address cybersecurity.) Allowed by electrical engineers only Allow Deny Allowed by qualified personnel only Reference: 240.6 D 64. 137 – 2023 NEC Code Updates Part 1 (01-01)1Standard ampere ratings for fuses and circuit breakers have changed but do not include a ________ device. (These fuses and circuit breakers are available in the field.) 601 amp 225 amp 55 amp 10 amp Reference: 240.6 A 65. 136 – 2023 NEC Code Updates Part 1 (01-01)1The maximum continuous load on a 14 AWG Copper-Clad Aluminum conductor shall not exceed ________. (Any circuit breakers must also be listed and marked for use with these conductors.) 8 amperes 12 amperes 10 amperes 15 amperes Reference: 240.4 D 3 66. 135 – 2023 NEC Code Updates Part 1 (01-01)1An overcurrent device rated 800 amperes or less with an adjustable trip is permitted to be used if the setting does not exceed ________ the conductor capacity. (The means to adjust the setting of the trip must have restricted access.) The next standard rating size above 125 percent of 115 percent of The next standard rating size below only applies Reference: 240.4 B 67. 134 – 2023 NEC Code Updates Part 1 (01-01)1A new section identifies Overcurrent Protective Devices (OCPDs) that are permitted to be reconditioned. ________ are permitted to be reconditioned. (When many devices reach the end of their usable life span, they need to be replaced.) Low voltage fuse holders Ground fault circuit breakers Low voltage power circuit breakers Molded case circuit breakers Reference: 240.2 68. 133 – 2023 NEC Code Updates Part 1 (01-01)1The requirement for surge protection of services has been expanded to include ________. (Also now includes nursing homes.) Office buildings Data centers Guest rooms of hotels All structures Reference: 230.67 69. 132 – 2023 NEC Code Updates Part 1 (01-01)1A new ________ has become the placeholder for medium voltage branch circuits, feeders, and services over 1,000 volts AC and 1,500 volts DC. (This information was located throughout the NEC before.) Article 255 Article 245 Article 290 Article 235 Reference: 235.1 70. 131 – 2023 NEC Code Updates Part 1 (01-01)1The label marking required on an emergency disconnecting means for a one- and two-family dwelling unit service shall ________. (Also requested by first responders. See also some specific State rules.) Have letters at least 1/2 inch high Be red colored letters text 6 by 6 inch minimum Be yellow in background Reference: 230.85 E 2 71. 130 – 2023 NEC Code Updates Part 1 (01-01)1Where equipment for isolation of other energy source systems (such as solar) is not located adjacent to the emergency disconnect for one- and two-family dwelling services, a plaque identifying the location shall be located ________ the disconnecting means. (Comes up a lot more often now.) Adjacent to Inside Within sight of Above Reference: 230.85 D 72. 129 – 2023 NEC Code Updates Part 1 (01-01)1When only a service ________ is replaced for a one- and two-family dwelling unit, the outside emergency disconnect requirements shall not apply. (To aid in emergency service damage relief.) Meter socket Disconnect Enclosure Panelboard Reference: 230.85 C 73. 128 – 2023 NEC Code Updates Part 1 (01-01)1If the required emergency disconnecting means for dwelling units is a meter disconnect, it must be ________ the meter mounting equipment. (This undefined term is often mistakenly thought to be a simple disconnect switch on the supply side of the meter enclosure which is not the intention.) Integral to Adjacent to Near Remote from Reference: 230.85 B 74. 127 – 2023 NEC Code Updates Part 1 (01-01)1For a one- and two-family dwelling unit service, an emergency disconnecting means shall be installed in a readily accessible and ________. Outdoor location on or within sight On the home only Indoor location Indoor or outdoor location Reference: 230.85 A ex 75. 126 – 2023 NEC Code Updates Part 1 (01-01)1The required Emergency Disconnect for a one- and two-family dwelling shall have a short circuit rating ________. (Maybe Fire Fighter Disconnect is a better name? Can smart meters contact utility and have power turned off remotely by fire fighters now? Non-fused disconnects are only rated at 10k.) A minimum of 20k A minimum of 30k A minimum of 10k Equal or greater than the available fault current Reference: 230.85 A 76. 125 – 2023 NEC Code Updates Part 1 (01-01)1 The requirements for a one- and two-family dwelling unit demand that an emergency disconnect now specify that it can be installed ________. (Many locations were already requiring this. Also, to provide safety to first responders, pulling the meter under load with an arc was not a good option.) Inside within 10 feet Inside near the garage entry door Outside within 100 feet Outdoors within sight Reference: 230.85 77. 124 – 2023 NEC Code Updates Part 1 (01-01)1________ are now permitted to be connected to the supply side of the service disconnecting means. Communications Power Supplies Control power circuits for protective relays Maintenance power receptacles Egress lighting Reference: 230.82 78. 123 – 2023 NEC Code Updates Part 1 (01-01)1An exception was added to permit the installation of up to 6 additional service disconnecting means in a single enclosure in ________. (Installed in compliance with editions of the code prior to the 2020 edition.) Refineries Industrial locations Existing equipment Commercial applications Reference: 230.71 B ex 79. 122 – 2023 NEC Code Updates Part 1 (01-01)1Up to 6 disconnects in a service metering center (like for a multifamily apartment structure) is allowed if ________. (Many meter centers do not have individual sections.) The meter pack is located outside of the building only The fault current is below 65k only It has a service main disconnect Each disconnect is labeled Reference: 230.71 B 80. 121 – 2023 NEC Code Updates Part 1 (01-01)1________ were added by CMP-10 to the list of the two to six service disconnects permitted for each service location. (To clarify that they must be listed for service when used as service equipment. Will existing legacy systems be required to be updated when altered?) Sub panels Snap switches Transfer switches Double throw switches Reference: 230.71 B 81. 120 – 2023 NEC Code Updates Part 1 (01-01)1All services supplying _________ are now required to be provided with Surge Protection Devices (SPD) inside or immediately adjacent to the service equipment. (The code is concerned about the safety of people and property. This rule helps protect property that is Life Safety such as AFCI’s and smoke detectors.) Motel guest rooms Any load Industrial installations Commercial installations Reference: 230.67 A 82. 119 – 2023 NEC Code Updates Part 1 (01-01)1An exception to the code section requirement for barriers to be placed in service equipment so that no uninsulated, ungrounded busbar or service terminal is exposed to inadvertent contact includes ________. (This touch safe rule allows small holes for testing. Some say these barriers do not last very long in cold weather.) There are no exceptions. When the service is rated 1,000 amperes or more When maintenance is performed by qualified personnel When there is more than one main disconnect in a single enclosure Reference: 230.62 C 83. 118 – 2023 NEC Code Updates Part 1 (01-01)1Barriers are now required in service equipment in such a way that ungrounded busbars in panels are not exposed to inadvertent contact while being serviced ________. (An amendment has been added to this code section because they forgot the word “energized”.) For panelboards only When the service main disconnect is in the closed-on position When the service main disconnect is in the open position In commercial energized locations only Reference: 230.62 C 84. 117 – 2023 NEC Code Updates Part 1 (01-01)1________ for splices and taps installed on service entrance conductors shall be listed and marked (suitable for use on the line side of the service equipment.) (Some are only recognized components now. These connections are considered free floated, not connected to an enclosure, with no overcurrent protection device ahead of it.) Starting January 1, 2025, devices Split bolts only Pressure connectors and devices Lugs only Reference: 230.46 85. 116 – 2023 NEC Code Updates Part 1 (01-01)1________ cable is now allowed as an approved wiring method in the NEC for service entrance 1,000 volts or less. (Many states have additional restrictions.) Any type UF NMB TC ER Reference: 230.43 86. 115 – 2023 NEC Code Updates Part 1 (01-01)1The wiring method for service entrance conductors at 1,000 volts or less is limited, ________ are permitted. (See also new Article 371.) Any of these methods are permitted Flexible bus systems Type TC-ER cable when identified Type MC cable Reference: 230.43 87. 114 – 2023 NEC Code Updates Part 1 (01-01)1Generally, there should only be one service location on a structure. An exception is a building with two-hour fire walls with more than one occupancy. When there are more than six service disconnect locations, ________. This is no longer allowed Special permission must be obtained Each location shall have a plaque describing the locations This is only permitted for multifamily applications Reference: 230.40 ex 1 88. 113 – 2023 NEC Code Updates Part 1 (01-01)1 The minimum clearance of service conductors above roofs has been increased to ________. (It did not make sense for service conductors to have a lower clearance requirement than feeders.) 8 feet 9 feet 7 feet 8 feet 6 inches Reference: 230.24 A 89. 112 – 2023 NEC Code Updates Part 1 (01-01)1Circuit conductors other than service conductors shall not be installed in the same ________ as the service conductors. (There have been some issues with generator conductors mixed in with service conductors.) Switchboard Panelboard Switch gear Raceway Reference: 230.7 90. 111 – 2023 NEC Code Updates Part 1 (01-01)1Where a feeder supplies a ________, a surge protective device (SPD) shall now be installed. (Similar to the requirements for services.) Fire stations Ranger stations Dormitory units Police stations Reference: 225.42 91. 110 – 2023 NEC Code Updates Part 1 (01-01)1If more than one emergency disconnecting means is allowed for a dwelling unit supplied by a feeder, they shall be ________. Grouped Separated Within 20 feet of each other Withing 25 feet of each other Reference: 225.41 A 92. 109 – 2023 NEC Code Updates Part 1 (01-01)1When a one- and two-family dwelling unit is supplied be a feeder, an emergency main disconnect ________. (Similar to the requirements for dwellings that are supplied by a service.) Shall be located on the structure Is now required Shall not be located on the structure Is not required Reference: 225.41 93. 108 – 2023 NEC Code Updates Part 1 (01-01)1Generally, when a building is supplied and served by a feeder, only one is allowed. A new special condition exception to this one main disconnect rule is for ________. (Other feeder supply rules mirror the service rules.) Educational Institutions Industrial facilities Hospitals Electrical Vehicle (EVs) charging systems Reference: 225.30 A 94. 107 – 2023 NEC Code Updates Part 1 (01-01)1When determining a load calculation exception on an existing feeder or service that has any renewable energy system connected to it (like Solar Photovoltaic), the calculation ______. Shall be multiplied by 115 percent Method shall not be permitted Shall be multiplied by 125 percent Must use the standard method Reference: 220.87 95. 106 – 2023 NEC Code Updates Part 1 (01-01)1A new section in Article 220 will ________ an Energy Management System (EMS) to be considered and used to reduce the loads on services or feeder calculations. (Malfunction of the system must result in the disconnection of loads.) Permit only with engineering Permit Permit only with permission Not allow Reference: 220.70 96. 105 – 2023 NEC Code Updates Part 1 (01-01)1When the load for Electric Vehicle Supply Equipment (EVSE) is calculated, it shall be either ________ or the equipment nameplate rating, whichever is larger. (There was a need for the NEC to give guidance here with all the electrical vehicles being added. It is based on a 30 ampere, 240-volt size.) 7,200 watts 5,600 watts 6,400 watts 8,000 watts Reference: 220.57 97. 104 – 2023 NEC Code Updates Part 1 (01-01)1For dwelling unit load calculations, the NEC permits a reduction of the demand factor of 75 percent to be applied to the nameplate of 4 or more appliances fastened in place. Electric vehicle supply equipment (EVSE) has been added to the list of equipment that is ________ to use the demand factor. Permitted with special permission Permitted Permitted if the list contains 6 or more Not permitted Reference: 220.53 98. 103 – 2023 NEC Code Updates Part 1 (01-01)1Calculations Table 220.42a received revisions for non-dwelling occupancies. When using this Table, the 125% multiplier for continuous loads ________. (Most of these revisions are load reductions and this change should save money. These discrepancies were a waste of resources.) Is already included Shall be used Is reduced to 80 percent Must be considered Reference: Table 220.42 A 99. 102 – 2023 NEC Code Updates Part 1 (01-01)1For a load calculation on a dwelling unit, the calculated square foot floor area ________ include open porches, or unused space not adaptable for future use. (Even dirt can be adaptable to a future use. A change for garages.) May not Shall Shall be permitted to Shall not Reference: 220.5 C 100. 101 – 2023 NEC Code Updates Part 1 (01-01)1For the purposes of load calculations, the square footage of a dwelling unit does not include ________. A garage space is now included. With home price increases more people are turning garages into dens, kitchens, and bedrooms. A second-floor area An unfinished basement Areas not adaptable as future occupiable space An entryway Reference: 220.5 C Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish