2026 Changes Part 2 – WA Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 34 – 2026 code change part 2

    1
    Who must conduct the performance testing of the GFPE system serving marinas and piers?
    555.35 F
  2. 2. 78 – 2026 code change part 2

    1
    Which of the following three‑phase circuits does NOT require Class A GFCI protection
    680.5 B
  3. 3. 58 – 2026 code change part 2

    1
    Which installation condition allows the supply circuit rating for EV charging equipment to be less than the full load?
    625.42
  4. 4. 141 – 2026 code change part 2

    1
    Which of the following is an example of a device that combines control signals with Class 4 emergency power?
    700.28 A B Informational note
  5. 5. 119 – 2026 code change part 2

    1
    Fuel cell system DC circuits installed in one‑ and two‑family dwellings must comply with a maximum voltage limit of __________ volts.(By setting clear voltage limits the National Electric Code aims to enhance the safety and reliability of fuel cell systems)
    692.7
  6. 6. 197 – 2026 code change part 2

    1
    Metal raceways containing entrance wire or cable for limited‑energy systems must be connected to a grounding electrode using ____
    750.42
  7. 7. 182 – 2026 code change part 2

    1
    Part ______ In article 722 covers limited energy cables and wiring methods.
    722.12
  8. 8. 43 – 2026 code change part 2

    1
    Which of the following is not permitted to share the elevator car lighting branch circuit?
    620.22
  9. 9. 137 – 2026 code change part 2

    1
    A Directly Controlled Luminaire (DCL) provides emergency illumination when:
    700.24 B
  10. 10. 61 – 2026 code change part 2

    1
    When one or more pieces of equipment include an integral load‑management control, the system must be:
    625.42 A
  11. 11. 124 – 2026 code change part 2

    1

    Fire pump supply conductors may be installed as part of which type of listed cable system?

    695.7 A 2 3
  12. 12. 40 – 2026 code change part 2

    1
    The field‑applied marking on an elevator control panel must meet the requirements for:
    620.16
  13. 13. 88 – 2026 code change part 2

    1
    The vertical bonding zone for perimeter surfaces now extends
    680.26 B 2
  14. 14. 29 – 2026 code change part 2

    1
    Which of the following conductors may be installed without GFPE protection when supplying marina or pier equipment?
    555.35 A
  15. 15. 166 – 2026 code change part 2

    1
    Reconditioned energy storage systems (ESS) are ______ to be installed.
    706.4
  16. 16. 36 – 2026 code change part 2

    1
    Which of the following is permitted under 590.6(I) for temporary installations?
    590.6 I Exception
  17. 17. 193 – 2026 code change part 2

    1
    Because Class 2 and Class 3 circuits are power‑limited, alternate requirements are provided for ____
    725.1 info note
  18. 18. 149 – 2026 code change part 2

    1
    Legally required standby system switchgear, switchboards, and panelboards shall have an SPD (Surge protection device ) installed integral to or immediately adjacent to ________.
    701.9
  19. 19. 132 – 2026 code change part 2

    1
    If the permanent emergency power source is part of a separately derived system with a grounded conductor, the switching means for the temporary source must:
    700.4 F
  20. 20. 83 – 2026 code change part 2

    1
    In an indoor pool area, certain equipment may be installed at a minimum height of 7 ft 6 in above the maximum water level if:
    680.22 B 2
  21. 21. 199 – 2026 code change part 2

    1
    Inner system bonding for limited‑energy systems must be connected in accordance with the rules that apply to ____
    750.94
  22. 22. 79 – 2026 code change part 2

    1
    A maintenance electrician is replacing a 277‑volt single‑phase lighting circuit that supplies luminaires located directly above an indoor commercial pool. The branch circuit operates at 277 volt to ground and 480 volt phase‑to‑phase. What type of ground‑fault protection is required?
    680.5 C
  23. 23. 118 – 2026 code change part 2

    1
    Fuel cell system DC circuits shall not exceed __________ volts when installed on or in buildings.
    692.7
  24. 24. 46 – 2026 code change part 2

    1
    Under the 2026 NEC, where must the surge protective device (SPD) be installed for an elevator system?
    620.51 E
  25. 25. 135 – 2026 code change part 2

    1
    Interconnected power production sources that are not designated stored‑energy emergency power sources:
    700.12 F
  26. 26. 165 – 2026 code change part 2

    1
    Circulating neutral currents from added power sources can affect ground‑fault protection operation. A common corrective measure is alternative placement of ________.
    705.32 & Informational note
  27. 27. 174 – 2026 code change part 2

    1
    A written or ______ record shall be kept of COPS tests and servicing. (This revision modernizing documentation standards by recognizing digital records as equivalent to written records by adopting” record keeping” instead of “written records” the NEC ensures it stays relevant in a digital first operating environments )
    708.6 D
  28. 28. 131 – 2026 code change part 2

    1
    A permanent field‑applied label at the emergency system temporary generator connection point must identify:
    700.4 F
  29. 29. 68 – 2026 code change part 2

    1
    Cord‑and‑plug‑connected EVSE(electrical vehicle supply equipment )Electric vehicle supply equipment and WPTE(Wireless power transfer equipment ) equipment may use the plug as the disconnecting means when:
    625.43 A B C
  30. 30. 117 – 2026 code change part 2

    1
    The maximum voltage of a fuel cell system DC circuit is the highest voltage between __________ conductors of a circuit or any conductor and ground.
    692.7
  31. 31. 105 – 2026 code change part 2

    1
    Which of the following may serve as a rapid‑shutdown initiating device?
    690.12 C 1
  32. 32. 146 – 2026 code change part 2

    1

    Selective coordination shall be reevaluated if replacement OCPDs supplying emergency loads are not replaced with the same manufacturer and ________.

    700.32 A B C
  33. 33. 69 – 2026 code change part 2

    1
    Electric vehicle supply equipment and wireless power transfer equipment connected to premises wiring must be installed using:
    625.44
  34. 34. 159 – 2026 code change part 2

    1
    Identification of DC power source output conductors shall use color coding, marking tape, tagging, or other approved means in accordance with ________.
    705.25 B
  35. 35. 19 – 2026 code change part 2

    1
    Which statement best describes the purpose of the equipotential plane bonding requirements at marinas and similar waterfront facilities?
    555.14
  36. 36. 64 – 2026 code change part 2

    1
    Electric vehicle supply equipment and wireless power transfer equipment must be provided with: (The 2026 revision significantly reorganized and expands the requirements for disconnecting means related to electrical vehicle supply equipment and wireless power transfer equipment. the update addresses modern installation conditions previously a disconnect was only required for equipment rate at 60 amps or more and with more than 150 volts to ground however it is now necessary for all EVSE equipment )
    625.43
  37. 37. 63 – 2026 code change part 2

    1
    For electric vehicle charging equipment that is not self‑adjusting, the current adjustment setting must be:
    625.42 B
  38. 38. 176 – 2026 code change part 2

    1
    Table 720.4(A) lists the ______ covered by the general requirements of Article 720. (By explicitly referencing this table 720 .4 A this revision enhances code usability consistency and enforceability for systems that operate at lower power levels section 720.4 A introduces cross reference table that aligns general limited energy system requirements with specific articles governing these various technologies this centralized referencing system is a great addition )
    Table 720.4 A
  39. 39. 81 – 2026 code change part 2

    1
    A 240‑volt electric pool water heater has a nameplate load of 44 A. What is the minimum ampacity of the branch‑circuit conductors?
    680.10 A 2
  40. 40. 98 – 2026 code change part 2

    1
    PV system DC circuits on or attached to buildings may not exceed:
    690.7
  41. 41. 164 – 2026 code change part 2

    1
    Current‑carrying neutral conductors from power sources connected on the load side of ground‑fault protection can cause ________ of the ground‑fault protection due to circulating neutral currents.
    705.32 & Informational note
  42. 42. 200 – 2026 code change part 2

    1
    Inner system bonding requirements apply to both limited‑energy systems and ____
    750.94
  43. 43. 35 – 2026 code change part 2

    1
    What documentation must be provided to the AHJ after GFPE system testing?
    555.35 F
  44. 44. 99 – 2026 code change part 2

    1
    The maximum current of a Solar Photovoltaic system ( PV) source circuit may be calculated using which of the following?
    690.8 A
  45. 45. 172 – 2026 code change part 2

    1
    The authority having jurisdiction (AHJ) shall ______ a test of the completed COPS (Critical operations power systems ) system upon installation.
    708.6 A
  46. 46. 17 – 2026 code change part 2

    1
    A marina installs a new pier distribution system operating at 208/120V single‑phase. What documentation may the AHJ accept?
    555.9 Exception
  47. 47. 5 – 2026 code change part 2

    1
    Which of the following is an example of an ESV under Article 624?
    100 definitions
  48. 48. 7 – 2026 code change part 2

    1
    Which definition applies to vehicles such as boats, aircraft, and farm equipment when electrically powered?
    100 definitions
  49. 49. 129 – 2026 code change part 2

    1

    The connection point for the temporary alternate source of power for the emergency system must be marked with:

    700.4 F
  50. 50. 16 – 2026 code change part 2

    1
    When required by the authority having jurisdiction, what must be provided for a pier distribution system?
    555.9
  51. 51. 143 – 2026 code change part 2

    1
    Emergency system overcurrent protective devices shall be selectively coordinated with all ________ overcurrent protective devices.
    700.32 A B C
  52. 52. 156 – 2026 code change part 2

    1
    Placards for one‑ and two‑family dwellings shall indicate the location of each permanently installed ________ optional standby power source disconnect.
    702.7 A 1&2
  53. 53. 33 – 2026 code change part 2

    1
    What is the purpose of the new coordination and performance testing requirement for marina GFPE systems?
    555.35 F
  54. 54. 11 – 2026 code change part 2

    1
    Recreational vehicle site supply equipment must include receptacles that meet which of the following requirements? ( must be installed at each RV site
    → The configurations in Figure 551.46(C)(1) (TT‑30, 14‑50, 5‑20, etc.)
    551.71
  55. 55. 62 – 2026 code change part 2

    1

    Electric vehicle charging equipment with an adjustable current setting is permitted only when:

    625.42 B
  56. 56. 190 – 2026 code change part 2

    1
    Class 1 power‑limited circuits must be protected according to wiring method rules because their classification requires compliance with ____
    724.1 info note
  57. 57. 123 – 2026 code change part 2

    1
    One permitted method of protecting fire pump supply conductors is encasement in concrete at least:
    695.7 A2 d1
  58. 58. 56 – 2026 code change part 2

    1
    Without the use of load‑management controls, the supply circuit for EV charging equipment must be sized to:
    625.42
  59. 59. 31 – 2026 code change part 2

    1
    What type of ground‑fault requirement applies to fire pump circuits serving marina electrical systems?
    555.35 B
  60. 60. 91 – 2026 code change part 2

    1
    A storable pool is installed with a permanent deck that encloses part of the pool’s perimeter and provides access to the pool. Under the 2026 NEC, what additional requirement now applies?
    680.30 B
  61. 61. 144 – 2026 code change part 2

    1
    Selective coordination shall be selected by a licensed professional engineer or other ________ persons engaged primarily in the design, installation, or servicing of electrical systems.
    700.32 A B C
  62. 62. 60 – 2026 code change part 2

    1
    A power control system used for EV load management may be:
    625.42 A
  63. 63. 162 – 2026 code change part 2

    1
    A circuit breaker that is not marked line and load shall be considered ________ for backfeeding.
    705.30 D
  64. 64. 161 – 2026 code change part 2

    1
    Fused disconnects, unless otherwise marked, shall be considered ________ for backfeed.
    705.30 D
  65. 65. 188 – 2026 code change part 2

    1

    Although Class 1 circuits are power‑limited, they are not treated as limited‑energy systems because they require ____

    724.1 info note
  66. 66. 103 – 2026 code change part 2

    1
    The purpose of the rapid shutdown requirement for PV systems is
    690.12
  67. 67. 150 – 2026 code change part 2

    1
    The SPD required for legally required standby systems must be installed integral to or immediately adjacent to all legally required standby system ________.
    701.9
  68. 68. 45 – 2026 code change part 2

    1
    There’s been a revision selective coordination for elevator systems must be reevaluated under which of the following conditions? (Requirements were added to reevaluate selective coordination whenever over current protection is replaced even if deletions are made to the existing elevator system)
    620.62
  69. 69. 49 – 2026 code change part 2

    1
    The requirement in article 625 applies to EV connections used for:
    625.4
  70. 70. 89 – 2026 code change part 2

    1
    For non‑conductive pool shells, how many bonding attachment points are required under the 2026 NEC?
    680.26 B 2
  71. 71. 125 – 2026 code change part 2

    1
    Emergency system record keeping requires that written or digital records of tests and maintenance be:
    700.4 D
  72. 72. 18 – 2026 code change part 2

    1
    Which of the following pier distribution systems requires full engineered documentation, with no option for simplified documentation?
    555.9 Exception
  73. 73. 134 – 2026 code change part 2

    1
    Interconnection equipment for a microgrid‑connected emergency source must be listed to:
    700.12 F
  74. 74. 55 – 2026 code change part 2

    1
    The rating of the electrical supply to EV charging equipment may be reduced only when:
    625.42
  75. 75. 86 – 2026 code change part 2

    1
    Under the 2026 NEC, the perimeter bonding zone around a pool now extends how far horizontally from the inside pool wall?
    680.26 B 2
  76. 76. 57 – 2026 code change part 2

    1

    Which statement best reflects the requirement for supplying EV charging equipment?

    625.42
  77. 77. 95 – 2026 code change part 2

    1
    Which condition alone triggers the need for an equipotential plane at a aeration pond ?
    682.33
  78. 78. 106 – 2026 code change part 2

    1
    A rapid‑shutdown initiating devices must be:
    690.12 C 1
  79. 79. 127 – 2026 code change part 2

    1
    When the emergency system relies on a single alternate source that will be disabled for servicing, the emergency system must include:
    700.4 F
  80. 80. 38 – 2026 code change part 2

    1
    What information must be field‑marked on an elevator control panel regarding fault current?
    620.16
  81. 81. 65 – 2026 code change part 2

    1
    In a multifamily dwelling where multiple Electric vehicle supply equipment or wireless power transfer equipment units each have individual disconnects, each unit must have:
    625.43 A B C
  82. 82. 177 – 2026 code change part 2

    1
    Limited energy system grounding is covered in Article ______.
    Table 720.4 A
  83. 83. 66 – 2026 code change part 2

    1
    When the disconnecting means for permanently connected EVSE and WPTE equipment is installed remote from the equipment, the equipment must have:
    625.43 A B C
  84. 84. 198 – 2026 code change part 2

    1
    Selecting a grounding location that provides the shortest practical bonding conductor or grounding electrode conductor helps reduce ____
    750.48 info note
  85. 85. 185 – 2026 code change part 2

    1
    Raceways used for limited‑energy systems must be supported and secured according to ____
    723.22 A 2
  86. 86. 107 – 2026 code change part 2

    1

    A photovoltaic system (PV system) disconnecting means must be installed so that it:

    690.13
  87. 87. 178 – 2026 code change part 2

    1
    Article 721 covers ______ requirements for limited energy systems. (Power sources for limited energy systems establishes the power source requirements for limited energy system circuits it ensures that power sources are properly selected and protected to maintain reliability and safety they also have to align with the specific characteristics at operational limits of low energy systems )
    721.1
  88. 88. 32 – 2026 code change part 2

    1
    Which of the following must be true of the fire pump ground‑fault alarm?
    555.35 B
  89. 89. 171 – 2026 code change part 2

    1
    Commissioning of ESS( Energy storage systems) is required upon installation except in ______.
    706.7 B
  90. 90. 42 – 2026 code change part 2

    1

    What is now required for supplying lighting in each elevator car? (A long standing ambiguous requirement regarding how car lighting in elevators must be wired specifically the update language mandate separate branch circuit for the car lights In each individual elevator car the revised language now clearly requires one branch circuit per elevator car for the car lighting system)

    620.22
  91. 91. 70 – 2026 code change part 2

    1
    Cord‑and‑plug‑connected Wireless power transfer equipment and electric vehicle supply equipment when used must be provided with an attachment plug rated at least:
    625.44
  92. 92. 147 – 2026 code change part 2

    1
    Selective coordination shall be reevaluated if replacement OCPDs are not replaced with the same manufacturer and type and with the same ________ or setting.
    700.32 A B C
  93. 93. 22 – 2026 code change part 2

    1
    Which statement best reflects the intent of the updated equipotential bonding requirements for marinas?
    555.14
  94. 94. 100 – 2026 code change part 2

    1
    The maximum current of a PV source circuit is:
    690.8 A 1 a 1
  95. 95. 27 – 2026 code change part 2

    1
    What is the primary purpose of adding “piers” to the marina ground‑fault protection language?
    555.35
  96. 96. 47 – 2026 code change part 2

    1
    The scope of Article 624 covers power transfer systems capable of which type(s) of current flow?
    624.1
  97. 97. 140 – 2026 code change part 2

    1
    Devices that combine control signals with Class 4 emergency power on a single circuit must be:
    700.28 A
  98. 98. 153 – 2026 code change part 2

    1
    If a shutdown occurs due to an overloaded condition, reconnection of the supply shall only be performed ________.
    702.4 A 3 Informational note #1 and #2
  99. 99. 154 – 2026 code change part 2

    1
    PCS functionality is typically used to control loads at the ________, feeder, distribution level, or a combination of both.
    702.4 A 3 Informational note #1 and #2
  100. 100. 52 – 2026 code change part 2

    1
    The SCCR of EVSE may be established using:
    625.5 2