2026 Changes Part 1- WA Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 149 – 2026 Changes Part 11 Which of the following correctly describes the requirements for grounding switches used in medium‑ and high‑voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding, and cannot be closed while the grounding switch is in the grounded position Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches only need to be interlocked with the service disconnect, not with other power sources feeding the equipment Grounding switches are required to be load‑break rated and may be used as the primary disconnecting means Reference:495.26 2. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Category 1 treatment rooms used for invasive procedures Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Imaging suites used for diagnostic procedures Patient care areas used for direct preparation and care Reference:517.10 B 3. 138 – 2026 Changes Part 11 According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors are less than 10 ft in length Only if the tap conductors are installed in rigid metal conduit Only if the tap conductors comply with 240.21(B), and taps are not permitted for portable generators rated 15 kW or less where field wiring terminals are not accessible Only if the tap conductors are supervised by an AHJ‑approved maintenance program Reference:445.13 B 4. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 60 amperes or less 100 amperes or less 80 amperes or less 70 amperes or less Reference:210.8 F 5. 12 – 2026 Changes Part 11___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.) Commercial break rooms Industrial and commercial break rooms Holding tanks Dormitories (16 individuals or more) Reference:210.17 6. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside services All branch circuits and feeders Outside branch circuits and feeders Indoor branch circuits and feeders Reference:267.1 7. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Threaded couplings made up wrench?tight Locknuts Listed bonding bushings with bonding jumpers Tight threadless couplings used with metal raceways Reference:500.30 B 8. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) Directly buried in the earth When bundled In crawl spaces When fished between acess points and concealed Reference:334.12 9. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) All types of Commercial and industrial only One- and two-family dwelling and multifamily only One- and two-family dwelling units only Reference:230.70 D 10. 73 – 2026 Changes Part 11When raceways are installed in a wet location above grade level they now shall _______. (Moisture accumulation can be an issue in environments such as food processing plants, car washes, and swimming pools.) Use listed fittings that prevent condensation Be nonmetallic Be designed to drain Have drip loops Reference:300.11 B 11. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Shall not be installed Can be installed if the enclosure is indoors Can be installed with AHJ guidance Can be installed Reference:250.64 G 12. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) shall be located inside the laundry area adjacent to the door must be located outside of the laundry area shall be marked at the switch can now be located outside of the laundry area Reference:210.70 A ex 3 13. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) All feeder and service 1000 volts AC or more only Service In areas with rocks only Reference:300.7 D3 14. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Combine any 2 subparts to comply Comply with all 3 subparts Comply with at least 2 subparts Be installed according to 1 subpart Reference:242.14 15. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 140 degree F 60 degree C 90 degree C 75 degree C Reference:310.16 16. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It permits field?installed overcurrent devices to replace listed transformer protection It eliminates primary?side overcurrent protection for transformers under 1 kVA It reorganizes and modernizes the overcurrent protection tables and rules for clearer application It requires all transformers to be listed as energy?efficient regardless of rating Reference:450.3 17. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Shall Can not Shall not May Reference:342.29 18. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Carnivals Commercial amusement parks with permanent rides Permanent theatrical stages only Industrial manufacturing plants Reference:525.1 19. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Power-Limited Remote-Control Circuits All circuits under 100 volts Non-Powered-Limited Signaling circuits Overvoltage protection Reference:206.1 20. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Any control conductors associated with the same building Only grounding and bonding conductors associated with the service Any feeder conductors passing through to adjacent equipment Only conductors intended for termination within that section Reference:408.10 2 21. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of brass Identified bimetallic couplings All listed fittings are Bonding jumpers made of copper or brass Reference:342.14 22. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Alternating?current power distribution boxes Only equipment installed in permanent studio structures Only generators rated over 15 kW Only luminaires used for egress lighting Reference:530.2 23. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 18 inches 6 inches 10 inches 12 inches Reference:392.18 F 24. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Prudent demand factors and historic data The nameplate rating of the largest single piece of equipment only Connected loads Feeder calculations Reference:517.4 B 25. 175 – 2026 Changes Part 11 According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Essential electrical systems in healthcare facilities Legally required standby systems Emergency lighting systems in non-healthcare buildings Optional standby systems Reference:517.26 26. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The motor nameplate data and conductor ampacity tables The reconditioning contractors documented quality?control program The installers field evaluation or local AHJ preference The manufacturers instructions Reference:430.3 27. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To allow reconditioned oil?filled equipment to be installed without listing To expand transformer oil?testing requirements to all electrical equipment To eliminate all requirements for oil?filled equipment below 15 kV To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 28. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) It is recommended that at least 1 conduit A minimum of one conduit A minimum of two conduits Each Reference:250.109 B2 29. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) As permitted by" a licensed electrical engineer When installed "in accordance with" the technical NEC requirements As permitted by" the AHJ Only if the common electrode terminates in one of the enclosures Reference:250.64 D1 30. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Utility disconnect Electrical disconnect Service switch Service disconnect Reference:230.70 B 31. 156 – 2026 Changes Part 11 Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Reconditioned equipment is prohibited in all hazardous locations unless field evaluated by the AHJ All reconditioned equipment must be listed and marked Explosion Proof regardless of original classification Only equipment located outside the hazardous location requires reconditioning evaluation Reconditioned equipment is permitted Reference:501.3 32. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Ordinary Temporary Commercial table 501.10 A 1. & Restricted Reference:501.1 33. 161 – 2026 Changes Part 11According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5. Class III Class II Unclassified Class I Reference:511.10 B 2 34. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) Bonding is optional if all generators are rated less than 15 kW Only the largest source must be bonded to the structures grounding electrode The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 . Each source must have an isolated equipment grounding conductor Reference:525.12 35. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Not considered as current carrying Counted unless under engineering supervision Considered as current carrying and shall be counted Considered as current carrying but does not need to be counted Reference:310.15 E 36. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 210 article 406 Article 314 Article 110 Reference:406 37. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) A non-metallic enclosure A satellite electrode Any location inside A minimum 6 AWG copper grounding electrode conductor Reference:250.94 A 38. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) Their dielectric materials and protective mechanisms degrade over time They are no longer manufactured in standard voltage classes They cannot be effectively grounded after reconditioning They require special labeling that is not recognized by the NEC Reference:460.3 39. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Can be reused Can be installed if refurbished Must not be refurbished Are resettable Reference:242.3 40. 148 – 2026 Changes Part 11 According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design Isolating means are required unless the equipment can be deenergized by other methods such as draw out units non load break isolating switches must be interlocked with a series interrupting device or field marked with a warning Reference:495.22 41. 135 – 2026 Changes Part 11 According to 2026 NEC the outdoor disconnecting means for a split‑system HVAC unit in other than one‑ and two‑family dwellings must be marked with which of the following? The manufacturer’s installation instructions for both indoor and outdoor units The location of the branch-circuit overcurrent device supplying the outdoor unit, in accordance with 110.22(A) The minimum circuit ampacity and maximum fuse size for the outdoor unit The location of all indoor units it supplies, in accordance with 110.22(A) Reference:440.15 42. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) United Laboratories (UL) Article 266 Article 250 The National Electrical Safety Code Reference:265.1 43. 145 – 2026 Changes Part 11 According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A cooling fan that operates whenever the battery is charging A timer‑based charging system that limits charging to off‑peak hours A secondary disconnecting means located within sight of the battery room Overcharge control provisions to prevent the batteries from becoming overcharged Reference:480.14 44. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Shall be marked with the location Shall be located but immediately adjacent to the equipment. Can be located downstream Can be located elsewhere Reference:268.91 B 45. 115 – 2026 Changes Part 11 Receptacles shall not be installed in a face‑up position in which of the following locations? (The NEC prohibits installing receptacles face‑up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) In a laundry area On walls adjacent to countertops Under raised floors in IT rooms On work surfaces Reference:406.14 G 46. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 125% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions 115% of the generator nameplate current rating 80% of the generator nameplate current rating Reference:445.13 47. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Fastening devices Mounting screws Reduced-Wall-Thickness Boxes Wagos Reference:314.2 48. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 550.13 only 210.52 300.5 406.9 Reference:550.13 D 49. 48 – 2026 Changes Part 11The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.) Is allowed at all times Is no longer allowed Is allowed only with express consent from the AHJ Is allowed if a rock bottom is encountered when a rod is driven at a 45 degree angle Reference:250.53 A4 50. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class C fuses Class A Class B fuses Class A fuses Reference:240.7 51. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Conduit length Marking requirement Listed fittings Entry height Reference:300.9 A 52. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 14 AWG 20 AWG 18 AWG 16 AWG Reference:Table 210.24(2) 53. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? All NEC conditions for location It is installed by the utility It is mounted on the roof It is installed in a bedroom closet Reference:550.51 B 1-7 54. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? . Battery?equipped emergency luminaires Energy storage systems Battery?equipped emergency luminaires Reference:517.28 A ex. 55. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements The temporary source may be smaller than the on?site source if load shedding is used Interlocking is optional if the temporary source is supervised by qualified personnel Reference:517.30 E 4 56. 197 – 2026 Changes Part 11 Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) Only outdoor receptacles require GFCI protection GFCI protection is optional if the receptacle is within sight of the panelboard GFCI protection must be provided as required in 210.8 Receptacle outlets must be GFCI protected only when installed in bathrooms Reference:550.13 B 57. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) A local utility company The authority having jurisdiction (AHJ) A qualified person The National Electrical Code tables only Reference:268.42 C 58. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) Both disconnects shall be installed The disconnects shall be installed inside out of the weather An emergency disconnecting means is no longer required Only one is needed if it complies with 225.41 Reference:225.31 A, 4 1 59. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Substitute Are in addition to Overrides Reduce Reference:225.1 Note 2 60. 114 – 2026 Changes Part 11 On work surfaces, receptacles shall not be installed in a face‑up position unless which condition is met? It's in an area below a sink The receptacle is located more than 12 inches from a sink and AFCI, GFCI's are used It's in a work Surface The receptacle is part of a listed assembly specifically designed for face‑up installation Reference:406.14 G 61. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Severe cold Water damage Aged over 50 years Smoke damage Reference:300.4 C 62. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 30 ampere 20 ampere 15 ampere 10 ampere Reference:210.22 ex 63. 125 – 2026 Changes Part 11 The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? Lighting outlets required by 210.70 C and receptacles required by 210.63 A A supplemental electric baseboard heater A ductless mini‑split indoor unit A whole‑house humidifier Reference:422.12 64. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be listed as a combination faceplate assembly It shall be supplied only by a Class 2 power source only It shall be installed only in dwelling-unit bedrooms It shall be a blank faceplate with no openings Reference:406.16 D 65. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 14 AWG 18 AWG 20 AWG 16 AWG Reference:210.24(1) 66. 181 – 2026 Changes Part 11 When an EES uses more than one on-site power source, which of the following is REQUIRED when any single on-site source is disabled for service? The temporary connection must be sized to accommodate the largest power source Interlocking is optional if the temporary source is monitored by qualified personnel The temporary source may be connected only after modifying permanent wiring Integration of the temporary source may delay transfer switch timing if supervised Reference:517.30 F 1 67. 11 – 2026 Changes Part 11Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.) 2500 1500 2400 2000 Reference:210.13 A&B 68. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) Over 500 volts DC That supply portable or mobile equipment For utilities Over 500 volts AC Reference:270.20 C 69. 130 – 2026 Changes Part 11 A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design S and Design T motors Design A and Design D motors Design B(E) and Design C(E) motors Design F and Design G motors Reference:Recognition throughout article 430 70. 93 – 2026 Changes Part 11There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.) Three times the major diameter dimension is recommended. Five times the minor diameter dimension can be used. Three times the minor diameter dimension is allowed. Five times the major diameter dimension can be used. Reference:338.24 71. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Letters shall be at least 1/2 inch high Must have a red text Shall be located adjacent to the disconnect Must have a black background Reference:230.70 B2 72. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A licensed administrator Any engineer A qualified individual A master electrician Reference:266.4 C 73. 167 – 2026 Changes Part 11 Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Inside Only inside the dispensing device Only adjacent to the dispensing device Other than inside or adjacent to the dispensing device Reference:514.13 74. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Type MI fittings Type MI Cable Straps and hangers Reference:332.2 75. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Only on?site generators listed for emergency systems Photovoltaic systems Any power source approved by the authority having jurisdiction Reference:517.30 B 76. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 14 AWG Aluminum 18 AWG Copper 14 AWG Copper-Clad Aluminum 16 AWG Copper-Clad Aluminum Reference:340.104 77. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Pneumatic lines Copper-Clad Aluminum Conductors Any conductor Surge protection devices Reference:392.22 B 78. 36 – 2026 Changes Part 11The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.) Can qualify if listed SVC Qualifiers Can qualify if listed Does not qualify Reference:230.70 F 79. 8 – 2026 Changes Part 11For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.) There are no longer exceptions; it shall be GFCI protected. Listed Class C SPGFCI protection is permitted instead of GFCI GFCI protection is only suggested now. Assured Grounding Reference:210.8 F ex 3 80. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Inspected annually by a third party Inspected by a third party again after installation Installed by qualified persons Installed in a neat and workman-like manner Reference:393.14 A 81. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Emergency service facility sleeping quarters like police stations Break and quiet rooms All occupancies All commercial occupancies Reference:215.18 A 82. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 250.8(A)(1) through (A)(6) 300.5(A) through (A)(4) 110.26(A)(1) through (A)(3) 547.44(C)(1) through 547.44(C)(4) Reference:547.44 C 83. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located below grade level Regardless of grade level Only that have a floor located at grade or below grade level Only that have a floor located at grade level Reference:210.8 A 84. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 0.05 second 0.1 second 0.01 second 1.0 second Reference:517.42 F 85. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Conductive battery stands Only battery enclosures located outdoors nly metallic battery terminals Only battery chargers associated with the system Reference:480.8 86. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Motor control centers Panelboards . Switchboards Switchgear Reference:408,3 B 87. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Any fixed cabinet Only fixed cabinets with countertops Only fixed cabinets that are not recessed Only fixed cabinets with a work surface Reference:210.52 A2(1) 88. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 3/4 inch thick 1 inch thick 1 1/2 inch thick 2 inches thick Reference:300.6 E 89. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards A listed mechanical grounding connector Any split-bolt lug All set-screw style connectors Reference:250.64 C 90. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Color painted on Single colored stripe other than green Double stripe Green colored stripe Reference:200.7 A 91. 162 – 2026 Changes Part 11Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies? Mercantile occupancies only Assembly Business occupancies only Industrial or storage occupancies only Reference:512.6 92. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. All of these answers are false 20 amp grounding type receptacles AFCI receptacles Grounding type receptacles Reference:406.12 D 1 93. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 6 ft 7 in 7 ft 0 in 6 ft 0 in 5 ft 6 in Reference:404.10 A 2 94. 163 – 2026 Changes Part 11 Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Class I Class II Class I, Division 2 or Zone 2, as applicable Unclassified locations only Reference:512.21 95. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It cannot serve as the emergency disconnect It shall not be mounted in or on the mobile home and must be within sight of the home it serves It must be located at least 50 ft from the mobile home It may be mounted on the exterior wall of the mobile home if weatherproof Reference:550.51 96. 104 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General‑use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) Molded-case switches (Breaker type switches) Transfer switches Automatic transfer switches Manual bypass/isolation switches Reference:404.3 B 97. 109 – 2026 Changes Part 11 According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted only in non‑dwelling occupancies Reconditioned wiring devices are permitted if listed by a third‑party refurbisher Reconditioned wiring devices are not permitted to be used Reconditioned wiring devices are permitted if tested by a qualified person Reference:406.3 98. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety 110.21 B Identification of disconnecting means Section 250.8 Equipment grounding conductor identification Section 408.3 Support and arrangement of busbars Reference:408.10 F 99. 139 – 2026 Changes Part 11According to the 2026 NEC the terminology for generator remote emergency shutdown has been modernized by replacing an old term emergency stop switch with_______. (This update reflects the evolution of generator control technologies which increasingly rely on digital systems programmable interfaces and network control circuits rather than physical traditional switches ) Shutdown device Generator lockout switch Remote trip mechanism Emergency disconnect Reference:445.19 B 100. 150 – 2026 Changes Part 11 According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? No special provisions are required if the switchgear is listed for indoor use Noncombustible protection must be provided under any openings in the bottom of the switchgear The switchgear must be elevated at least 12 inches above the floor The combustible floor must be treated with a fire-retardant coating approved by the AHJ Reference:495.36 Back Save Progress Retry Finish