2026 Changes Part 1- WA Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Listed as suitable for service only Field evaluated only Additionally certified Listed or field evaluated Reference:230.2 B 2. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The temporary source may be smaller than the on?site source if load shedding is used Interlocking is optional if the temporary source is supervised by qualified personnel The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements Reference:517.30 E 4 3. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) A messenger A copper-alloy armor Aluminum conductors Any jacket covering Reference:330.10 A 4. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded together with a solid copper conductor not smaller than #8 AWG D. No bonding is required if each section has its own feeder disconnect They must be bonded together using a solid copper conductor sized per Table 250.122 They must be bonded with a minimum #12 copper conductor if GFCI protection is provided Reference: 545.20 D 545.26 5. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) A minimum of one conduit Each It is recommended that at least 1 conduit A minimum of two conduits Reference:250.109 B2 6. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) AVTs (absence of voltage testers) Listed smoke detection systems Video monitoring systems Type 3 surge-protection devices Reference:230.82 7. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Counted unless under engineering supervision Considered as current carrying and shall be counted Not considered as current carrying Considered as current carrying but does not need to be counted Reference:310.15 E 8. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? . The nearest doorway The ceiling height The top of the equipment enclosure The floor or working platform Reference:404.10 A 2 9. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Laser equipment Only laser equipment located inside the hazardous location Only equipment specifically listed for Class I Only optical fiber equipment located outside the hazardous location Reference:500.8 G 10. 171 – 2026 Changes Part 11Part II of Article 517 applies to which of the following? Patient care spaces of all healthcare facilities Only Category 1 and Category 2 treatment rooms Only facilities with essential electrical systems Only hospitals and ambulatory surgical centers Reference:517.10 A 11. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Must have a black background Shall be located adjacent to the disconnect Must have a red text Letters shall be at least 1/2 inch high Reference:230.70 B2 12. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? Standard off?the?shelf listed assemblies Site?specific engineered designs by both civil and electrical engineers Field?assembled systems supervised by the installer shall have a plan review Reference:426.64 13. 12 – 2026 Changes Part 11___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.) Holding tanks Dormitories (16 individuals or more) Commercial break rooms Industrial and commercial break rooms Reference:210.17 14. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are not permitted unless with a manual bypass are allowed are permitted if a warning label is also provided are never allowed Reference:210.70 C3 15. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Marked suitable for damp locations Installed in accordance with Article 410 only Listed for the location and listed for field installation with the luminaire being retrofitted Installed by a qualified person and approved by the manufacturer Reference:501.130 C 16. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Only adjacent to the dispensing device . Only inside the dispensing device Inside Other than inside or adjacent to the dispensing device Reference:514.13 17. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 800 amperes 1000 amperes 600 amperes 500 amperes Reference:215.10 B 18. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 600 amperes 1000 amperes 400 amperes 800 amperes Reference:230.95 19. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 547.44(C)(1) through 547.44(C)(4) 250.8(A)(1) through (A)(6) 300.5(A) through (A)(4) 110.26(A)(1) through (A)(3) Reference:547.44 C 20. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Hangers Staples Straps Straps and hangers Reference:332.3 21. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 15 ampere 10 ampere 20 ampere 30 ampere Reference:210.22 ex 22. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Ductless mini?split systems Electric baseboard heaters Similar equipment Wall?mounted room air conditioners Reference:422.12 ex.#1 23. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 16 AWG Copper-Clad Aluminum 18 AWG Copper 14 AWG Aluminum 16 AWG Copper Reference:310.5 A 24. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Using galvanized steel Adding caution tape Sealing the raceway Coating the raceway Reference:342.10 B 25. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must automatically de?energize the equipment when opened It must be interlocked with the controller to prevent operation It must be locked or require a tool to be opened Reference:440.11 26. 174 – 2026 Changes Part 11Receptacles and fixed equipment in wet?procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple ) A power distribution system in which the entire system is protected by a single GFCI device A system protected only by an equipment grounding conductor Individual GFCI devices installed at each receptacle only A system supplied from an isolated power source without GFCI protection Reference:517.20 A 3 a b 27. 144 – 2026 Changes Part 11According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded) Only battery enclosures located outdoors Conductive battery stands nly metallic battery terminals Only battery chargers associated with the system Reference:480.8 28. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Any fixed cabinet Only fixed cabinets with countertops Only fixed cabinets with a work surface Only fixed cabinets that are not recessed Reference:210.52 A2(1) 29. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Equipment grounding conductors Terminal blocks Wire nuts (splicing connectors) Internal cable clamps Reference:314.16 B 30. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) The panel circuit breaker shall be marked with a warning label The HVAC disconnect shall be marked with a warning label Marking labels are recommended Both the panel circuit breaker and HVAC shall be marked with a warning label Reference:210.8 F ex 3 31. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Applies even when you transition and combine raceway types Does not apply to flexible conduits Only applies to rigid conduit methods Only applies to each raceway type in the run Reference:300.24 32. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? . Battery?equipped emergency luminaires Energy storage systems Battery?equipped emergency luminaires Reference:517.28 A ex. 33. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 12 inches 18 inches 24 inches 6 inches Reference:210.52 A5 34. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Any mechanical connection Bonding is not required if the system voltage is under 50 volts Only wire?type equipment grounding conductors installed in every raceway Threaded couplings/hubs made up wrench?tight Reference:500.3 35. 168 – 2026 Changes Part 11In addition to the off?site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Only generators listed for emergency systems Photovoltaic systems only Only energy storage systems listed for standby use Power production sources Reference:517.4 36. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) One- and two-family dwelling and multifamily only Commercial and industrial only All types of One- and two-family dwelling units only Reference:230.70 D 37. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A metering center Service disconnects rated under 30 amperes The disconnection of surge-protection devices A switchboard Reference:230.71 A 38. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It may be mounted on the exterior wall of the mobile home if weatherproof It must be located at least 50 ft from the mobile home It cannot serve as the emergency disconnect It shall not be mounted in or on the mobile home and must be within sight of the home it serves Reference:550.51 39. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Fastening devices Mounting screws Reduced-Wall-Thickness Boxes Wagos Reference:314.2 40. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade or below grade level Only that have a floor located below grade level Only that have a floor located at grade level Regardless of grade level Reference:210.8 A 41. 156 – 2026 Changes Part 11Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Reconditioned equipment is permitted Reconditioned equipment is prohibited in all hazardous locations unless field?evaluated by the AHJ All reconditioned equipment must be listed and marked Explosion?Proof regardless of original classification Only equipment located outside the hazardous location requires reconditioning evaluation Reference:501.3 42. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site but sized only for the life?safety branch; on?site only Off?site; off?site only Off?site and sized to supply the entire EES; on?site only On?site and sized to supply the entire EES; either on?site or off?site Reference:517.41 A 43. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 10 amperes 15 amperes 12 amperes 8 amperes Reference:Table 210.24(2) 44. 197 – 2026 Changes Part 11Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) Receptacle outlets must be GFCI?protected only when installed in bathrooms GFCI protection must be provided as required in 210.8 Only outdoor receptacles require GFCI protection GFCI protection is optional if the receptacle is within sight of the panelboard Reference:550.13 B 45. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) All commercial occupancies Break and quiet rooms Emergency service facility sleeping quarters like police stations All occupancies Reference:215.18 A 46. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable removal Cable relocation Rejuvenation Cable terminations Reference:315.3 47. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Only embedded concrete heating mats Only factory?assembled heating systems . Only roof?mounted heating cables Conductive pavement heating systems Reference:Article 424, 425, 426 and 427 48. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Unclassified Class I Class II Reference:513.8 49. 181 – 2026 Changes Part 11When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service? The temporary source may be connected only after modifying permanent wiring Interlocking is optional if the temporary source is monitored by qualified personnel The temporary connection must be sized to accommodate the largest power source Integration of the temporary source may delay transfer switch timing if supervised Reference:517.30 F 1 50. 122 – 2026 Changes Part 11Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 210.12 AFCI protection section 410.184 A and/or B 406.12 Tamper?resistant receptacles 250.114 Equipment grounding conductor requirements Reference:410.184 51. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection shall be marked at the first device AFCI protection can be located at the first switch AFCI protection shall be installed at the overcurrent protection device The entire circuit shall now be protected Reference:210.12 E 52. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? . A ductless mini?split indoor unit A supplemental electric baseboard heater Lighting outlets required by 210.70 C and receptacles required by 210.63 A A whole?house humidifier Reference:422.12 53. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only battery systems connected to renewable?energy equipment Only standby battery systems used for emergency power ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only lithium?ion battery systems installed indoors Reference:480.1 54. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) Provided under engineering supervision In a campus environment Located outdoors Based on temperature rise Reference:265.19 B 55. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) As permitted by" a licensed electrical engineer As permitted by" the AHJ Only if the common electrode terminates in one of the enclosures When installed "in accordance with" the technical NEC requirements Reference:250.64 D1 56. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. 20 amp grounding type receptacles Grounding type receptacles AFCI receptacles All of these answers are false Reference:406.12 D 1 57. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Ordinary table 501.10 A 1. & Restricted Temporary Commercial Reference:501.1 58. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To expand transformer oil?testing requirements to all electrical equipment To allow reconditioned oil?filled equipment to be installed without listing To eliminate all requirements for oil?filled equipment below 15 kV To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 59. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure At the generator or the first disconnecting means supplied by the generator Only at the service disconnect At the load terminals of the transfer switch Reference:525.31 60. 102 – 2026 Changes Part 11A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switchessuch as snap switches, dimmers, and electronic controlswere moved to Article 406 as part of a structural reorganization.) The elimination of Article 404 and redistribution of its content into Chapter 2 The expansion of Article 404 to include all wiring devices such as receptacles and GFCIs The increase of allowable switch voltage ratings to 2000 volts The relocation of most device?type switches Reference:404.1 B 61. 104 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General?use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices ) molded-case switches (Breaker type switches) Manual bypass/isolation switches Automatic transfer switches Transfer switches Reference:404.3 B 62. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Non-flexible metallic raceways and fittings Felexible sealtight and fittings Reference:250.102 A 63. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Life safety branch and equipment branch; division occurs at the transfer switches Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and critical branch; division occurs at the service disconnect Critical branch and equipment branch; division occurs at the panelboards Reference:517.42 A 64. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 15 amperes 10 amperes 8 amperes 12 amperes Reference:Table 210.24(1) 65. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Single colored stripe other than green Double stripe Green colored stripe Color painted on Reference:200.7 A 66. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 16 AWG 20 AWG 14 AWG 18 AWG Reference:210.24(1) 67. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Commercial amusement parks with permanent rides Carnivals Industrial manufacturing plants Permanent theatrical stages only Reference:525.1 68. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. On?site but permitted to supply only the critical branch Off?site and capable of supplying only the life?safety branch On?site and sized to supply the entire EES Off?site and sized to supply the entire EES Reference:517.30 A 69. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 115% of the generator nameplate current rating 125% of the generator nameplate current rating 80% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions Reference:445.13 70. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Conduit length Entry height Marking requirement Listed fittings Reference:300.9 A 71. 150 – 2026 Changes Part 11According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? Noncombustible protection must be provided under any openings in the bottom of the switchgear No special provisions are required if the switchgear is listed for indoor use The switchgear must be elevated at least 12 inches above the floor The combustible floor must be treated with a fire?retardant coating approved by the AHJ Reference:495.36 72. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class A Class A fuses Class B fuses Class C fuses Reference:240.7 73. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 100 percent 125 percent 90 percent 110 percent Reference:265.20 A 74. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Green covered conductor Yellow insulated conductor with a green stripe Green conductor with a yellow stripe Light green insulated conductor Reference:250.119 A2 75. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Branch circuits supplied from emergency sources Branch circuits with AFCI protection Individual branch circuits Multiwire branch circuits Reference:517.15 76. 177 – 2026 Changes Part 11A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state? Hazardous voltage may be present even when equipment is off Disconnect all sources before servicing equipment Caution Multiple power sources supplied from separate feeders Warning Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized Reference:517.28 B 77. 48 – 2026 Changes Part 11The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.) Is allowed at all times Is allowed if a rock bottom is encountered when a rod is driven at a 45 degree angle Is allowed only with express consent from the AHJ Is no longer allowed Reference:250.53 A4 78. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It eliminates primary?side overcurrent protection for transformers under 1 kVA It permits field?installed overcurrent devices to replace listed transformer protection It requires all transformers to be listed as energy?efficient regardless of rating It reorganizes and modernizes the overcurrent protection tables and rules for clearer application Reference:450.3 79. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Any location containing Class I or Class II materials Only locations where combustible dusts are present in suspension Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where ignitable fibers are manufactured Reference:500.5 80. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Service disconnect Utility disconnect Electrical disconnect Service switch Reference:230.70 B 81. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? Reconditioned reactors are permitted to be installed Both reconditioned reactors and reconditioned resistors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed . Reconditioned resistors are permitted to be installed Reference:470.3 A B 82. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Hazardous (Class I Wet locations Corrosive locations only Reference:495.4 83. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible in residential applications only Strictly prohibitted Permissible in commercial applications only Permissible Reference:240.24 E 84. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located inside a locked room accessible only to qualified personnel It may expose uninsulated live parts when opened without any additional restrictions It must be located at least 15 ft from the operator station to prevent accidental operation It must be within sight and within 6 ft of the operator station and readily accessible during operation Reference:525.21 A 85. 189 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a non?moving attraction or portable structure such as a tent, concession, inflatable, or slide? It must be located exactly 6 ft inside the structure It must be located at the service equipment supplying the carnival It may expose uninsulated live parts when opened without any additional restrictions It must be located inside or outside the structure within 6 ft Reference:525.21 B 86. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Any control conductors associated with the same building Any feeder conductors passing through to adjacent equipment Only conductors intended for termination within that section Only grounding and bonding conductors associated with the service Reference:408.10 2 87. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 210 article 406 Article 314 Article 110 Reference:406 88. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Health care patient rooms Parks and recreation Commercial garages Assembly occupancies Reference:406.26 89. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A metal-corrugated roof decking only A plywood-type roof decking only All types of roof decking Any wood decking only Reference:300.6 E 90. 20 – 2026 Changes Part 11As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.) 24 inches 6 inches 12 inches 18 inches Reference:210.52 C4 91. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Overvoltage protection Power-Limited Remote-Control Circuits All circuits under 100 volts Non-Powered-Limited Signaling circuits Reference:206.1 92. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of copper or brass All listed fittings are Identified bimetallic couplings Bonding jumpers made of brass Reference:342.14 93. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside services Indoor branch circuits and feeders All branch circuits and feeders Outside branch circuits and feeders Reference:267.1 94. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion It must be bonded with a #12 copper conductor to any nearby metal object It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG Reference:547.44 B 95. 162 – 2026 Changes Part 11Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies? Industrial or storage occupancies only Business occupancies only Assembly Mercantile occupancies only Reference:512.6 96. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Can be located elsewhere Can be located downstream Shall be marked with the location Shall be located but immediately adjacent to the equipment. Reference:268.91 B 97. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be installed only in dwelling-unit bedrooms It shall be a blank faceplate with no openings It shall be listed as a combination faceplate assembly It shall be supplied only by a Class 2 power source only Reference:406.16 D 98. 109 – 2026 Changes Part 11According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are permitted only in non?dwelling occupancies Reconditioned wiring devices are permitted if listed by a third?party refurbisher Reconditioned wiring devices are not permitted to be used Reference:406.3 99. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Only equipment over 52 All equipment over 1 Equipment rated not over 15 Reference:495.2 AB 100. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards Any split-bolt lug A listed mechanical grounding connector All set-screw style connectors Reference:250.64 C Back Save Progress Retry Finish