2026 Changes Part 1- WA Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is installed in a bedroom closet It is installed by the utility All NEC conditions for location It is mounted on the roof Reference:550.51 B 1-7 2. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) Any location inside A minimum 6 AWG copper grounding electrode conductor A satellite electrode A non-metallic enclosure Reference:250.94 A 3. 161 – 2026 Changes Part 11According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5. Class II Unclassified Class I Class III Reference:511.10 B 2 4. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. 3-way "snap" switches Pull out switches All of the answers are true Service equipment Reference:404.1 A 5. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 50 feet 100 feet 75 feet 60 feet Reference:225.41 A1 6. 174 – 2026 Changes Part 11Receptacles and fixed equipment in wet?procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple ) A system protected only by an equipment grounding conductor A system supplied from an isolated power source without GFCI protection A power distribution system in which the entire system is protected by a single GFCI device Individual GFCI devices installed at each receptacle only Reference:517.20 A 3 a b 7. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) The National Electrical Code tables only A qualified person The authority having jurisdiction (AHJ) A local utility company Reference:268.42 C 8. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Legally required standby systems Essential electrical systems in healthcare facilities Emergency lighting systems in non?healthcare buildings Optional standby systems Reference:517.26 9. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Field evaluated only Listed as suitable for service only Additionally certified Listed or field evaluated Reference:230.2 B 10. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The manufacturers instructions The reconditioning contractors documented quality?control program The motor nameplate data and conductor ampacity tables The installers field evaluation or local AHJ preference Reference:430.3 11. 145 – 2026 Changes Part 11According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A cooling fan that operates whenever the battery is charging Overcharge control provisions to prevent the batteries from becoming overcharged A secondary disconnecting means located within sight of the battery room A timer?based charging system that limits charging to off?peak hours Reference:480.14 12. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only Category 1 and Category 2 spaces Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only Category 3 and Category 4 spaces Only the category assigned by the authority having jurisdiction Reference:517.7 & Informational note 13. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 30 ampere 20 ampere 15 ampere 10 ampere Reference:210.22 ex 14. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only equipment specifically listed for Class I Only laser equipment located inside the hazardous location Only optical fiber equipment located outside the hazardous location Laser equipment Reference:500.8 G 15. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 25 or 21 S Type 11 Type 2C or 11C Type 21C Reference:300.13 E 16. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 60 degree C 90 degree C 140 degree F 75 degree C Reference:310.16 17. 67 – 2026 Changes Part 11A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.) Smoke damage Aged over 50 years Water damage Severe cold Reference:300.4 C 18. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 300 volts to ground 50 volts to ground 150 volts to ground 120 volts to ground Reference:410.184 A B 19. 85 – 2026 Changes Part 11New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.) The fittings only The cable only The brackets Staples and/or straps Reference:330.2 20. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) table 501.10 A 1. & Restricted Temporary Ordinary Commercial Reference:501.1 21. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Shall Shall not May Can not Reference:342.29 22. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? Battery?equipped emergency luminaires . Battery?equipped emergency luminaires Energy storage systems Reference:517.28 A ex. 23. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) Equipment design not compatible with GFCI protection These are all requirements for a GFCI exception. As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel Reference:210.8 B ex 2 24. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must be locked or require a tool to be opened It must be interlocked with the controller to prevent operation It must automatically de?energize the equipment when opened Reference:440.11 25. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Panelboards Motor control centers Switchgear . Switchboards Reference:408,3 B 26. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Hazardous (Class I Corrosive locations only Wet locations Reference:495.4 27. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside services All branch circuits and feeders Indoor branch circuits and feeders Outside branch circuits and feeders Reference:267.1 28. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade or below grade level Only that have a floor located below grade level Regardless of grade level Only that have a floor located at grade level Reference:210.8 A 29. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 12 inches 6 inches 24 inches 18 inches Reference:210.52 A5 30. 130 – 2026 Changes Part 11A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design A and Design D motors Design S and Design T motors Design B(E) and Design C(E) motors . Design F and Design G motors Reference:Recognition throughout article 430 31. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A switchboard Service disconnects rated under 30 amperes A metering center The disconnection of surge-protection devices Reference:230.71 A 32. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Adding caution tape Coating the raceway Sealing the raceway Using galvanized steel Reference:342.10 B 33. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Reference:495.22 34. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 250.8 Equipment grounding conductor identification Section 90.7 Examination of equipment for safety 110.21 B Identification of disconnecting means Section 408.3 Support and arrangement of busbars Reference:408.10 F 35. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 0.1 second 0.01 second 0.05 second 1.0 second Reference:517.42 F 36. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. On?site and sized to supply the entire EES Off?site and sized to supply the entire EES Off?site and capable of supplying only the life?safety branch On?site but permitted to supply only the critical branch Reference:517.30 A 37. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Feeder calculations Connected loads Prudent demand factors and historic data The nameplate rating of the largest single piece of equipment only Reference:517.4 B 38. 42 – 2026 Changes Part 11A new code section for overcurrent protection now covers and introduces the new term “transformer secondary conductors,” and they are permitted to be ________. (This change separates feeder tap conductor from the transformer secondary rules.) Tapped without restrictions Always installed without protection regardless of length Considered protected without overcurrent protection at the secondary Considered protected without overcurrent protection Reference:240.21 B3 and 240.21 C 39. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) 1000 volts AC or more only In areas with rocks only Service All feeder and service Reference:300.7 D3 40. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Light green insulated conductor Green conductor with a yellow stripe Green covered conductor Yellow insulated conductor with a green stripe Reference:250.119 A2 41. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Straps and hangers Type MI fittings Type MI Cable Reference:332.2 42. 12 – 2026 Changes Part 11___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.) Industrial and commercial break rooms Commercial break rooms Dormitories (16 individuals or more) Holding tanks Reference:210.17 43. 45 – 2026 Changes Part 11When installing a Type 2 Surge Protection Device (SPD), the NEC provides 3 situations with separate subpart requirements. The installer shall ___________. (The previous interpretation was considered impractical and sometimes technically incompatible.) Comply with at least 2 subparts Combine any 2 subparts to comply Comply with all 3 subparts Be installed according to 1 subpart Reference:242.14 44. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Tight threadless couplings used with metal raceways Locknuts Threaded couplings made up wrench?tight Listed bonding bushings with bonding jumpers Reference:500.30 B 45. 137 – 2026 Changes Part 11If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges ) 115 percent None of these answers are correct except this one 100 percent 125 percent Reference:445.13 46. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Any aquatic vessels Any metal framed container Only bait wells Open aquatic vessels or containers Reference:210.8 B 47. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Staples Straps only 2 hole straps only Hangers only Reference:334.2 48. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Reduced-Wall-Thickness Boxes Wagos Mounting screws Fastening devices Reference:314.2 49. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. Off?site; off?site only On?site but sized only for the life?safety branch; on?site only On?site and sized to supply the entire EES; either on?site or off?site Off?site and sized to supply the entire EES; on?site only Reference:517.41 A 50. 117 – 2026 Changes Part 11Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units? Assembly occupancies Health care patient rooms Commercial garages Parks and recreation Reference:406.26 51. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? Both reconditioned reactors and reconditioned resistors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed . Reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed Reference:470.3 A B 52. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 16 AWG Copper-Clad Aluminum 14 AWG Copper-Clad Aluminum 14 AWG Aluminum 18 AWG Copper Reference:340.104 53. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where ignitable fibers are manufactured Any location containing Class I or Class II materials Only locations where combustible dusts are present in suspension Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Reference:500.5 54. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Any feeder conductors passing through to adjacent equipment Only grounding and bonding conductors associated with the service Only conductors intended for termination within that section Any control conductors associated with the same building Reference:408.10 2 55. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only battery systems connected to renewable?energy equipment Only lithium?ion battery systems installed indoors Only standby battery systems used for emergency power ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Reference:480.1 56. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. AFCI receptacles Grounding type receptacles 20 amp grounding type receptacles All of these answers are false Reference:406.12 D 1 57. 109 – 2026 Changes Part 11According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are not permitted to be used Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are permitted if listed by a third?party refurbisher Reconditioned wiring devices are permitted only in non?dwelling occupancies Reference:406.3 58. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Power-Limited Remote-Control Circuits Non-Powered-Limited Signaling circuits All circuits under 100 volts Overvoltage protection Reference:206.1 59. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 10 amperes 15 amperes 8 amperes 12 amperes Reference:Table 210.24(2) 60. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 210 Article 314 Article 110 article 406 Reference:406 61. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Service disconnect Electrical disconnect Service switch Utility disconnect Reference:230.70 B 62. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) As permitted by" the AHJ When installed "in accordance with" the technical NEC requirements As permitted by" a licensed electrical engineer Only if the common electrode terminates in one of the enclosures Reference:250.64 D1 63. 181 – 2026 Changes Part 11When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service? The temporary source may be connected only after modifying permanent wiring The temporary connection must be sized to accommodate the largest power source Integration of the temporary source may delay transfer switch timing if supervised Interlocking is optional if the temporary source is monitored by qualified personnel Reference:517.30 F 1 64. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Only applies to rigid conduit methods Applies even when you transition and combine raceway types Does not apply to flexible conduits Only applies to each raceway type in the run Reference:300.24 65. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Substitute Overrides Are in addition to Reduce Reference:225.1 Note 2 66. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Non-flexible metallic raceways and fittings Felexible sealtight and fittings Flexible metallic raceways and fittings Rigid Metal Conduit (RMC) only Reference:250.102 A 67. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) For utilities That supply portable or mobile equipment Over 500 volts DC Over 500 volts AC Reference:270.20 C 68. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 16 AWG 18 AWG 20 AWG 14 AWG Reference:Table 210.24(2) 69. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They require special labeling that is not recognized by the NEC They cannot be effectively grounded after reconditioning They are no longer manufactured in standard voltage classes Their dielectric materials and protective mechanisms degrade over time Reference:460.3 70. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A supplemental electric baseboard heater Lighting outlets required by 210.70 C and receptacles required by 210.63 A A whole?house humidifier . A ductless mini?split indoor unit Reference:422.12 71. 163 – 2026 Changes Part 11Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Unclassified locations only Class I Class II Reference:512.21 72. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Photovoltaic systems Only on?site generators listed for emergency systems Any power source approved by the authority having jurisdiction Reference:517.30 B 73. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Life safety branch and equipment branch; division occurs at the transfer switches Critical branch and equipment branch; division occurs at the panelboards Life safety branch and critical branch; division occurs at the service disconnect Critical branch and delayed?automatic branch; division occurs at the generator terminals Reference:517.42 A 74. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 115% of the generator nameplate current rating 80% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions 125% of the generator nameplate current rating Reference:445.13 75. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) Only one is needed if it complies with 225.41 The disconnects shall be installed inside out of the weather An emergency disconnecting means is no longer required Both disconnects shall be installed Reference:225.31 A, 4 1 76. 149 – 2026 Changes Part 11Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences ) Grounding switches only need to be interlocked with the service disconnect Grounding switches are required to be load?break rated and may be used as the primary disconnecting means Grounding switches may be operated at any time as long as the operator is wearing appropriate PPE Grounding switches must be interlocked with all disconnecting means so the disconnects are open before grounding Reference:495.26 77. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) United Laboratories (UL) The National Electrical Safety Code Article 266 Article 250 Reference:265.1 78. 160 – 2026 Changes Part 11According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Limited to a maximum length of 3 ft Permitted only when installed in rigid metal conduit Suitable for damp locations only Identified for extra?hard usage Reference:511.10 B 79. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Conduit length Listed fittings Entry height Marking requirement Reference:300.9 A 80. 190 – 2026 Changes Part 11Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does ) It may be loosely supported if used only during daylight hours It must be installed only on the exterior of the tent or concession It must be securely installed . It may be run on the ground if marked with caution tape Reference:525.22 81. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A metal-corrugated roof decking only Any wood decking only A plywood-type roof decking only All types of roof decking Reference:300.6 E 82. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) All occupancies Break and quiet rooms Emergency service facility sleeping quarters like police stations All commercial occupancies Reference:215.18 A 83. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 800 amperes 600 amperes 1000 amperes 400 amperes Reference:230.95 84. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) One- and two-family dwelling and multifamily only One- and two-family dwelling units only Commercial and industrial only All types of Reference:230.70 D 85. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2027 1.1.2029 1.1.2028 1.1.2026 Reference:245.2 86. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Bonding is not required if the system voltage is under 50 volts Any mechanical connection Threaded couplings/hubs made up wrench?tight Only wire?type equipment grounding conductors installed in every raceway Reference:500.3 87. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Cable cleats Any hangers Jacketing Blocking Reference:330.30 A 88. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located inside a locked room accessible only to qualified personnel It must be located at least 15 ft from the operator station to prevent accidental operation It must be within sight and within 6 ft of the operator station and readily accessible during operation It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 A 89. 177 – 2026 Changes Part 11A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state? Hazardous voltage may be present even when equipment is off Caution Multiple power sources supplied from separate feeders Warning Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized Disconnect all sources before servicing equipment Reference:517.28 B 90. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Fittings All electrical equipment Electrical mechanical supports Meter socket enclosures Reference:312.3 91. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure At the generator or the first disconnecting means supplied by the generator Only at the service disconnect At the load terminals of the transfer switch Reference:525.31 92. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) Interlocking is optional if the temporary source is supervised by qualified personnel The connection point must be marked with phase rotation and system bonding requirements The connection may require modification of permanent wiring if approved by the AHJ The temporary source may be smaller than the on?site source if load shedding is used Reference:517.30 E 4 93. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 3/4 inch thick 1 inch thick 1 1/2 inch thick 2 inches thick Reference:300.6 E 94. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion It must be bonded with a #12 copper conductor to any nearby metal object Reference:547.44 B 95. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 12 amperes 10 amperes 15 amperes 8 amperes Reference:Table 210.24(1) 96. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Must not be refurbished Are resettable Can be reused Can be installed if refurbished Reference:242.3 97. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All remote pumps serving the dispensing devices . All dispensing devices not supplied by intrinsically safe circuits All associated power Intrinsically safe electrical equipment Reference:514.11 A 98. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 300.5 406.9 550.13 only 210.52 Reference:550.13 D 99. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. all these answers are true 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 100. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed with AHJ guidance Can be installed if the enclosure is indoors Shall not be installed Can be installed Reference:250.64 G Complete Quiz Restart Quiz Save Progress Back Save Progress Retry Finish