2026 Changes Part 1- WA Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 93 – 2026 Changes Part 11There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.) Five times the minor diameter dimension can be used. Five times the major diameter dimension can be used. Three times the major diameter dimension is recommended. Three times the minor diameter dimension is allowed. Reference:338.24 2. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2028 1.1.2027 1.1.2029 1.1.2026 Reference:245.2 3. 126 – 2026 Changes Part 11Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that ) Classification was removed As cold water heaters Continuous load Continuous load only for branch circuit conductors Reference:422.13 4. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? Standard off?the?shelf listed assemblies shall have a plan review Field?assembled systems supervised by the installer Site?specific engineered designs by both civil and electrical engineers Reference:426.64 5. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A whole?house humidifier . A ductless mini?split indoor unit Lighting outlets required by 210.70 C and receptacles required by 210.63 A A supplemental electric baseboard heater Reference:422.12 6. 8 – 2026 Changes Part 11For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.) Listed Class C SPGFCI protection is permitted instead of GFCI GFCI protection is only suggested now. Assured Grounding There are no longer exceptions; it shall be GFCI protected. Reference:210.8 F ex 3 7. 133 – 2026 Changes Part 11Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit ) None of these answers are correct Purchased from the manufacturer of the HVAC unit being worked on Listed as a field installable accessory Inspected by the AHJ (Authority having jurisdiction ) Reference:440.2 8. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Electric baseboard heaters Wall?mounted room air conditioners Ductless mini?split systems Similar equipment Reference:422.12 ex.#1 9. 128 – 2026 Changes Part 11The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Unit heater fan motors Electric baseboard heaters Baseboard heater raceways Embedded snow?melting mats Reference:424.2 10. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) As permitted by" the AHJ As permitted by" a licensed electrical engineer When installed "in accordance with" the technical NEC requirements Only if the common electrode terminates in one of the enclosures Reference:250.64 D1 11. 78 – 2026 Changes Part 11In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.) 140 degree F 60 degree C 90 degree C 75 degree C Reference:310.16 12. 135 – 2026 Changes Part 11According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following? The minimum circuit ampacity and maximum fuse size for the outdoor unit The manufacturers installation instructions for both indoor and outdoor units The location of all indoor units it supplies Reference:440.15 13. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) It is recommended that at least 1 conduit A minimum of two conduits A minimum of one conduit Each Reference:250.109 B2 14. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Marking requirement Conduit length Entry height Reference:300.9 A 15. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Only embedded concrete heating mats . Only roof?mounted heating cables Only factory?assembled heating systems Conductive pavement heating systems Reference:Article 424, 425, 426 and 427 16. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) In areas with rocks only 1000 volts AC or more only Service All feeder and service Reference:300.7 D3 17. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Any hangers Jacketing Blocking Cable cleats Reference:330.30 A 18. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Utility disconnect Service switch Service disconnect Electrical disconnect Reference:230.70 B 19. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 70 amperes or less 60 amperes or less 100 amperes or less 80 amperes or less Reference:210.8 F 20. 85 – 2026 Changes Part 11New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.) The brackets The cable only The fittings only Staples and/or straps Reference:330.2 21. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. Off?site and sized to supply the entire EES; on?site only On?site and sized to supply the entire EES; either on?site or off?site Off?site; off?site only On?site but sized only for the life?safety branch; on?site only Reference:517.41 A 22. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Electrical mechanical supports All electrical equipment Meter socket enclosures Fittings Reference:312.3 23. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) Interlocking is optional if the temporary source is supervised by qualified personnel The connection may require modification of permanent wiring if approved by the AHJ The temporary source may be smaller than the on?site source if load shedding is used The connection point must be marked with phase rotation and system bonding requirements Reference:517.30 E 4 24. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) The disconnects shall be installed inside out of the weather Only one is needed if it complies with 225.41 An emergency disconnecting means is no longer required Both disconnects shall be installed Reference:225.31 A, 4 1 25. 112 – 2026 Changes Part 11A nongrounding?type receptacle with no grounding conductor present may be replaced with which of the following? all of these anwsers are true only a non-grounding receptacle A grounding?type receptacle supplied through a GFCI device Any grounding?type receptacle as long as it is labeled No Equipment Ground Reference:406.12 D 1 26. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) Section 300.11 EEE Chapter 7 NEMA GD 1-2019 NECA publication 1-23 Reference:300.4 C 27. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) They cannot be effectively grounded after reconditioning They require special labeling that is not recognized by the NEC They are no longer manufactured in standard voltage classes Their dielectric materials and protective mechanisms degrade over time Reference:460.3 28. 73 – 2026 Changes Part 11When raceways are installed in a wet location above grade level they now shall _______. (Moisture accumulation can be an issue in environments such as food processing plants, car washes, and swimming pools.) Use listed fittings that prevent condensation Have drip loops Be designed to drain Be nonmetallic Reference:300.11 B 29. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Coating the raceway Using galvanized steel Sealing the raceway Adding caution tape Reference:342.10 B 30. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Section 408.3 Support and arrangement of busbars Reference:408.10 F 31. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The reconditioning contractors documented quality?control program The motor nameplate data and conductor ampacity tables The manufacturers instructions The installers field evaluation or local AHJ preference Reference:430.3 32. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel These are all requirements for a GFCI exception. Equipment design not compatible with GFCI protection Reference:210.8 B ex 2 33. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 18 AWG Copper 16 AWG Copper 16 AWG Copper-Clad Aluminum 14 AWG Aluminum Reference:310.5 A 34. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment may be reused if insulation resistance tests pass The equipment must be reinspected by the AHJ only The equipment shall be replaced unless the installer certifies it The equipment shall be evaluated and approved by the original manufacturer Reference:408.3 A 35. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) Any engineer A licensed administrator A master electrician A qualified individual Reference:266.4 C 36. 83 – 2026 Changes Part 11Armored Cable is now required to be supported with approved and listed _________. (Non listed devices can degrade with time under heat.) Hangers only Staples Straps only 2 hole straps only Reference:320.2 37. 64 – 2026 Changes Part 11For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.) Can be located elsewhere Can be located downstream Shall be marked with the location Shall be located but immediately adjacent to the equipment. Reference:268.91 B 38. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 7 ft 0 in 5 ft 6 in 6 ft 7 in 6 ft 0 in Reference:404.10 A 2 39. 34 – 2026 Changes Part 11There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.) Must have a red text Must have a black background Shall be located adjacent to the disconnect Letters shall be at least 1/2 inch high Reference:230.70 B2 40. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where combustible dusts are present in suspension Only locations where ignitable fibers are manufactured Any location containing Class I or Class II materials Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Reference:500.5 41. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 600 amperes 1000 amperes 400 amperes 800 amperes Reference:230.95 42. 20 – 2026 Changes Part 11As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.) 12 inches 24 inches 6 inches 18 inches Reference:210.52 C4 43. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only Category 3 and Category 4 spaces Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only the category assigned by the authority having jurisdiction Only Category 1 and Category 2 spaces Reference:517.7 & Informational note 44. 108 – 2026 Changes Part 11In the electrical trade, the term wiring devices commonly refers to which of the following? Only luminaires Only switches switches and receptacles Only circuit breakers Reference:Article 406 and Definitions 45. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Color painted on Double stripe Single colored stripe other than green Green colored stripe Reference:200.7 A 46. 139 – 2026 Changes Part 11According to the 2026 NEC the terminology for generator remote emergency shutdown has been modernized by replacing an old term emergency stop switch with_______. (This update reflects the evolution of generator control technologies which increasingly rely on digital systems programmable interfaces and network control circuits rather than physical traditional switches ) Emergency disconnect Shutdown device Generator lockout switch Remote trip mechanism Reference:445.19 B 47. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only battery systems connected to renewable?energy equipment Only lithium?ion battery systems installed indoors ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only standby battery systems used for emergency power Reference:480.1 48. 100 – 2026 Changes Part 11Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.) Inspected by a third party again after installation Inspected annually by a third party Installed by qualified persons Installed in a neat and workman-like manner Reference:393.14 A 49. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It shall not be mounted in or on the mobile home and must be within sight of the home it serves It must be located at least 50 ft from the mobile home It may be mounted on the exterior wall of the mobile home if weatherproof It cannot serve as the emergency disconnect Reference:550.51 50. 16 – 2026 Changes Part 11There is now a new size limitation to permit a ______ minimum size Copper-Clad Aluminum Conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (A Copper-Clad conductor has copper on the outside and aluminum in the center. Be sure to use wirenuts rated for copper and aluminum AL/CU.) 16 AWG 20 AWG 14 AWG 18 AWG Reference:Table 210.24(2) 51. 130 – 2026 Changes Part 11A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) Design S and Design T motors Design B(E) and Design C(E) motors . Design F and Design G motors Design A and Design D motors Reference:Recognition throughout article 430 52. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Any control conductors associated with the same building Only grounding and bonding conductors associated with the service Any feeder conductors passing through to adjacent equipment Reference:408.10 2 53. 177 – 2026 Changes Part 11A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state? Caution Multiple power sources supplied from separate feeders Warning Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized Disconnect all sources before servicing equipment Hazardous voltage may be present even when equipment is off Reference:517.28 B 54. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. Service equipment Pull out switches All of the answers are true 3-way "snap" switches Reference:404.1 A 55. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is in an isolated area Unless the system is outdoors Within the same room or area Unless the system is supervised Reference:265.63 B 56. 97 – 2026 Changes Part 11A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.) Can not Shall not Shall May Reference:342.29 57. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located inside a locked room accessible only to qualified personnel It must be located at least 15 ft from the operator station to prevent accidental operation It must be within sight and within 6 ft of the operator station and readily accessible during operation It may expose uninsulated live parts when opened without any additional restrictions Reference:525.21 A 58. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) shall be marked at the switch must be located outside of the laundry area shall be located inside the laundry area adjacent to the door can now be located outside of the laundry area Reference:210.70 A ex 3 59. 148 – 2026 Changes Part 11According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? . Isolating means are required unless the equipment can be de?energized by other methods such as draw?out units; nonload?break isolating switches must be interlocked with a series interrupting device or field?marked with a warning Isolating switches must always be load?break rated and are required for all equipment regardless of design Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Reference:495.22 60. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Any conductor Copper-Clad Aluminum Conductors Surge protection devices Pneumatic lines Reference:392.22 B 61. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Inside Other than inside or adjacent to the dispensing device . Only inside the dispensing device Only adjacent to the dispensing device Reference:514.13 62. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be bonded with a #12 copper conductor to any nearby metal object It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion Reference:547.44 B 63. 47 – 2026 Changes Part 11The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.) Used for dissipation of surges Used for dissipation of lightning Considered a ground-fault path Used for a voltage reference Reference:250.4 A5 64. 166 – 2026 Changes Part 11Emergency electrical disconnects for fuel?dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All remote pumps serving the dispensing devices Intrinsically safe electrical equipment All associated power . All dispensing devices not supplied by intrinsically safe circuits Reference:514.11 A 65. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable removal Rejuvenation Cable relocation Cable terminations Reference:315.3 66. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 12 inches 24 inches 18 inches 6 inches Reference:210.52 A5 67. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) All listed fittings are Bonding jumpers made of copper or brass Identified bimetallic couplings Bonding jumpers made of brass Reference:342.14 68. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Type MI fittings Straps and hangers Type MI Cable Reference:332.2 69. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Yellow insulated conductor with a green stripe Light green insulated conductor Green covered conductor Green conductor with a yellow stripe Reference:250.119 A2 70. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade or below grade level Only that have a floor located below grade level Regardless of grade level Only that have a floor located at grade level Reference:210.8 A 71. 80 – 2026 Changes Part 11Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.) Mounting screws Wagos Fastening devices Reduced-Wall-Thickness Boxes Reference:314.2 72. 69 – 2026 Changes Part 11Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.) A metal-corrugated roof decking only All types of roof decking Any wood decking only A plywood-type roof decking only Reference:300.6 E 73. 140 – 2026 Changes Part 11A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision? It permits field?installed overcurrent devices to replace listed transformer protection It requires all transformers to be listed as energy?efficient regardless of rating It eliminates primary?side overcurrent protection for transformers under 1 kVA It reorganizes and modernizes the overcurrent protection tables and rules for clearer application Reference:450.3 74. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 50 feet 75 feet 100 feet 60 feet Reference:225.41 A1 75. 175 – 2026 Changes Part 11According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 ) Legally required standby systems Essential electrical systems in healthcare facilities Optional standby systems Emergency lighting systems in non?healthcare buildings Reference:517.26 76. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Reduce Are in addition to Substitute Overrides Reference:225.1 Note 2 77. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 4 2 3 5 Reference:406 78. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Imaging suites used for diagnostic procedures Patient care areas used for direct preparation and care Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Category 1 treatment rooms used for invasive procedures Reference:517.10 B 79. 116 – 2026 Changes Part 11Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet? It shall be installed only in dwelling-unit bedrooms It shall be listed as a combination faceplate assembly It shall be supplied only by a Class 2 power source only It shall be a blank faceplate with no openings Reference:406.16 D 80. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. all these answers are true 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 81. 2 – 2026 Changes Part 11New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.) Non-Powered-Limited Signaling circuits Power-Limited Remote-Control Circuits Overvoltage protection All circuits under 100 volts Reference:206.1 82. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) Hangers only Staples Straps only 2 hole straps only Reference:334.2 83. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 11 Type 21C Type 2C or 11C Type 25 or 21 S Reference:300.13 E 84. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 125 percent 100 percent 90 percent 110 percent Reference:265.20 A 85. 150 – 2026 Changes Part 11According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? The combustible floor must be treated with a fire?retardant coating approved by the AHJ Noncombustible protection must be provided under any openings in the bottom of the switchgear The switchgear must be elevated at least 12 inches above the floor No special provisions are required if the switchgear is listed for indoor use Reference:495.36 86. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must be interlocked with the controller to prevent operation It must be locked or require a tool to be opened It must automatically de?energize the equipment when opened Reference:440.11 87. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 406.9 300.5 210.52 550.13 only Reference:550.13 D 88. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 2 inches thick 1 1/2 inch thick 1 3/4 inch thick 1 inch thick Reference:300.6 E 89. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. 20 amp grounding type receptacles Grounding type receptacles AFCI receptacles All of these answers are false Reference:406.12 D 1 90. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 16 AWG Copper-Clad Aluminum 18 AWG Copper 14 AWG Copper-Clad Aluminum 14 AWG Aluminum Reference:340.104 91. 163 – 2026 Changes Part 11Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Unclassified locations only Class I Class II Reference:512.21 92. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) A qualified person The National Electrical Code tables only A local utility company The authority having jurisdiction (AHJ) Reference:268.42 C 93. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Unclassified Class I Class II Reference:513.8 94. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 12 inches 6 inches 18 inches 10 inches Reference:392.18 F 95. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible in residential applications only Permissible Permissible in commercial applications only Strictly prohibitted Reference:240.24 E 96. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 8 amperes 12 amperes 10 amperes 15 amperes Reference:Table 210.24(1) 97. 42 – 2026 Changes Part 11A new code section for overcurrent protection now covers and introduces the new term “transformer secondary conductors,” and they are permitted to be ________. (This change separates feeder tap conductor from the transformer secondary rules.) Considered protected without overcurrent protection at the secondary Considered protected without overcurrent protection Always installed without protection regardless of length Tapped without restrictions Reference:240.21 B3 and 240.21 C 98. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Terminal blocks Internal cable clamps Wire nuts (splicing connectors) Equipment grounding conductors Reference:314.16 B 99. 153 – 2026 Changes Part 11According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only optical fiber equipment located outside the hazardous location Only equipment specifically listed for Class I Only laser equipment located inside the hazardous location Laser equipment Reference:500.8 G 100. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Straps and hangers Staples Straps Hangers Reference:332.3 Back Save Progress Retry Finish