2026 Changes Part 1- OR Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 14 – 2026 Changes Part 1

    1
    In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard)
    Reference:210.24(1)
  2. 2. 81 – 2026 Changes Part 1

    1
    Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.)
    Reference:314.16 B
  3. 3. 3 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards.
    Reference:210.8 A
  4. 4. 180 – 2026 Changes Part 1

    1
    An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance )
    Reference:517.30 E 4
  5. 5. 63 – 2026 Changes Part 1

    1
    New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.)
    Reference:268.42 C
  6. 6. 151 – 2026 Changes Part 1

    1
    What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment )
    Reference:article495 parts VI andVII
  7. 7. 60 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.)
    Reference:265.63 B
  8. 8. 57 – 2026 Changes Part 1

    1
    New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.)
    Reference:265.1
  9. 9. 38 – 2026 Changes Part 1

    1
    The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.)
    Reference:230.71 B
  10. 10. 71 – 2026 Changes Part 1

    1
    Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.)
    Reference:300.7 D3
  11. 11. 76 – 2026 Changes Part 1

    1
    A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.)
    Reference:310.5 A
  12. 12. 136 – 2026 Changes Part 1

    1
    According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following?
    Reference:445.13
  13. 13. 90 – 2026 Changes Part 1

    1
    Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.)
    Reference:334.2
  14. 14. 23 – 2026 Changes Part 1

    1
    Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.)
    Reference:210.70 C3
  15. 15. 128 – 2026 Changes Part 1

    1

    The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following?

    Reference:424.2
  16. 16. 55 – 2026 Changes Part 1

    1
    A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.)
    Reference:250.109 B2
  17. 17. 39 – 2026 Changes Part 1

    1
    The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.)
    Reference:230.82
  18. 18. 99 – 2026 Changes Part 1

    1
    Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.)
    Reference:392.22 B
  19. 19. 82 – 2026 Changes Part 1

    1
    Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.)
    Reference:315.3
  20. 20. 161 – 2026 Changes Part 1

    1
    According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5.
    Reference:511.10 B 2
  21. 21. 27 – 2026 Changes Part 1

    1
    Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.)
    Reference:225.31 A, 4 1
  22. 22. 84 – 2026 Changes Part 1

    1
    __________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.)
    Reference:320.30 A
  23. 23. 75 – 2026 Changes Part 1

    1
    A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.)
    Reference:300.24
  24. 24. 17 – 2026 Changes Part 1

    1
    If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.)
    Reference:Table 210.24(2)
  25. 25. 193 – 2026 Changes Part 1

    1
    Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.)
    Reference:530.2
  26. 26. 50 – 2026 Changes Part 1

    1
    A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.)
    Reference:250.64 D1
  27. 27. 26 – 2026 Changes Part 1

    1
    NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.)
    Reference:225.1 Note 2
  28. 28. 162 – 2026 Changes Part 1

    1
    Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies?
    Reference:512.6
  29. 29. 19 – 2026 Changes Part 1

    1
    The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.)
    Reference:210.52 A5
  30. 30. 111 – 2026 Changes Part 1

    1
    In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish:

    – **Wiring?device–type switches**
    – **Receptacles and cord connectors**
    – **Attachment plugs (caps)** )

    Reference:406
  31. 31. 88 – 2026 Changes Part 1

    1
    For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.)
    Reference:332.2
  32. 32. 94 – 2026 Changes Part 1

    1
    An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.)
    Reference:340.104
  33. 33. 170 – 2026 Changes Part 1

    1
    All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care )
    Reference:517.7 & Informational note
  34. 34. 28 – 2026 Changes Part 1

    1
    The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.)
    Reference:225.41 A1
  35. 35. 95 – 2026 Changes Part 1

    1
    Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.)
    Reference:342.10 B
  36. 36. 20 – 2026 Changes Part 1

    1
    As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.)
    Reference:210.52 C4
  37. 37. 124 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment?
    Reference:422.12 ex.#1
  38. 38. 119 – 2026 Changes Part 1

    1
    According to the NEC, which of the following types of equipment is not permitted to be reconditioned?
    Reference:408,3 B
  39. 39. 178 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________.
    Reference:517.30 A
  40. 40. 122 – 2026 Changes Part 1

    1

    Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following?

    Reference:410.184
  41. 41. 74 – 2026 Changes Part 1

    1
    When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.)
    Reference:300.13 E
  42. 42. 141 – 2026 Changes Part 1

    1
    According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”)
    Reference:460.3
  43. 43. 106 – 2026 Changes Part 1

    1
    When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following?
    Reference:404.10 A 2
  44. 44. 47 – 2026 Changes Part 1

    1
    The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.)
    Reference:250.4 A5
  45. 45. 53 – 2026 Changes Part 1

    1
    The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.)
    Reference:250.94 A
  46. 46. 120 – 2026 Changes Part 1

    1
    As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section?
    Reference:408.10 2
  47. 47. 46 – 2026 Changes Part 1

    1
    Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.)
    Reference:245.2
  48. 48. 143 – 2026 Changes Part 1

    1

    Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations )

    Reference:480.1
  49. 49. 25 – 2026 Changes Part 1

    1
    Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.)
    Reference:215.18 A
  50. 50. 98 – 2026 Changes Part 1

    1
    A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.)
    Reference:392.18 F
  51. 51. 12 – 2026 Changes Part 1

    1
    ___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.)
    Reference:210.17
  52. 52. 126 – 2026 Changes Part 1

    1
    Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that )
    Reference:422.13
  53. 53. 176 – 2026 Changes Part 1

    1
    A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement?
    Reference:517.28 A ex.
  54. 54. 200 – 2026 Changes Part 1

    1
    Service equipment is permitted to be installed in or on a manufactured home only if which condition is met?
    Reference:550.51 B 1-7
  55. 55. 56 – 2026 Changes Part 1

    1
    Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.)
    Reference:250.119 A2
  56. 56. 147 – 2026 Changes Part 1

    1
    According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily)
    Reference:495.4
  57. 57. 191 – 2026 Changes Part 1

    1

    Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting )

    Reference:525.25 A B
  58. 58. 187 – 2026 Changes Part 1

    1
    Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code )
    Reference:525.12
  59. 59. 15 – 2026 Changes Part 1

    1
    If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.)
    Reference:Table 210.24(1)
  60. 60. 164 – 2026 Changes Part 1

    1
    According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________.
    Reference:513.3 A
  61. 61. 181 – 2026 Changes Part 1

    1

    When an EES uses more than one on-site power source, which of the following is REQUIRED when any single on-site source is disabled for service?

    Reference:517.30 F 1
  62. 62. 152 – 2026 Changes Part 1

    1
    According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments )
    Reference:500.5
  63. 63. 89 – 2026 Changes Part 1

    1
    The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.)
    Reference:332.3
  64. 64. 40 – 2026 Changes Part 1

    1
    Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.)
    Reference:230.95
  65. 65. 70 – 2026 Changes Part 1

    1
    The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.)
    Reference:300.6 E
  66. 66. 1 – 2026 Changes Part 1

    1
    A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.)
    Reference:200.7 A
  67. 67. 198 – 2026 Changes Part 1

    1
    Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes )
    Reference:550.13 D
  68. 68. 186 – 2026 Changes Part 1

    1
    Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential)
    Reference:525.1
  69. 69. 68 – 2026 Changes Part 1

    1
    The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.)
    Reference:300.4 C
  70. 70. 195 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments )
    Reference:547.44 B
  71. 71. 137 – 2026 Changes Part 1

    1
    If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges )
    Reference:445.13
  72. 72. 129 – 2026 Changes Part 1

    1
    Fixed outdoor electric deicing and snow?melting equipment includes which of the following?
    Reference:Article 424, 425, 426 and 427
  73. 73. 127 – 2026 Changes Part 1

    1
    Conductive pavement heating systems shall be designed as which of the following?
    Reference:426.64
  74. 74. 72 – 2026 Changes Part 1

    1
    A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.)
    Reference:300.9 A
  75. 75. 123 – 2026 Changes Part 1

    1
    The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold?
    Reference:410.184 A B
  76. 76. 41 – 2026 Changes Part 1

    1
    A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.)
    Reference:240.7
  77. 77. 44 – 2026 Changes Part 1

    1
    Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.)
    Reference:242.3
  78. 78. 32 – 2026 Changes Part 1

    1
    A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.)
    Reference:230.62 C
  79. 79. 154 – 2026 Changes Part 1

    1
    The 2026 NEC requires which of the following bonding methods for normally non–current?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations?
    Reference:500.3
  80. 80. 51 – 2026 Changes Part 1

    1
    In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.)
    Reference:250.64 E1
  81. 81. 177 – 2026 Changes Part 1

    1

    A warning sign is required where removal of a grounding or bonding connection in power source equipment would interrupt the grounding- electrode-conductor or grounded conductor connection to another energized source. What must the sign state?

    Reference:517.28 B
  82. 82. 91 – 2026 Changes Part 1

    1
    A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering.
    Reference:334.1
  83. 83. 105 – 2026 Changes Part 1

    1
    Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position?
    Reference:404.10 A 2
  84. 84. 43 – 2026 Changes Part 1

    1
    New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.)
    Reference:240.24 E
  85. 85. 112 – 2026 Changes Part 1

    1
    A non–grounding?type receptacle with no grounding conductor present may be replaced with which of the following?
    Reference:406.12 D 1
  86. 86. 6 – 2026 Changes Part 1

    1
    An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.)
    Reference:210.8 B ex 2
  87. 87. 48 – 2026 Changes Part 1

    1
    The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.)
    Reference:250.53 A4
  88. 88. 62 – 2026 Changes Part 1

    1
    The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.)
    Reference:267.1
  89. 89. 166 – 2026 Changes Part 1

    1

    Emergency electrical disconnects for fuel‑dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency )

    Reference:514.11 A
  90. 90. 96 – 2026 Changes Part 1

    1
    For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.)
    Reference:342.14
  91. 91. 153 – 2026 Changes Part 1

    1

    According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 μm wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay )

    Reference:500.8 G
  92. 92. 52 – 2026 Changes Part 1

    1
    A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.)
    Reference:250.64 G
  93. 93. 172 – 2026 Changes Part 1

    1
    Part II of Article 517 does NOT apply to which of the following spaces?
    Reference:517.10 B
  94. 94. 49 – 2026 Changes Part 1

    1
    Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation…does that include burial?)
    Reference:250.64 C
  95. 95. 188 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525?
    Reference:525.21 A
  96. 96. 21 – 2026 Changes Part 1

    1
    The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________.
    Reference:210.63 B
  97. 97. 5 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.)
    Reference:210.8 B
  98. 98. 30 – 2026 Changes Part 1

    1
    Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.)
    Reference:230.2 B
  99. 99. 59 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.)
    Reference:265.20 A
  100. 100. 58 – 2026 Changes Part 1

    1
    The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.)
    Reference:265.19 B
Back