2026 Changes Part 1- OR Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 14 AWG 16 AWG 18 AWG 20 AWG Reference:210.24(1) 2. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Wire nuts (splicing connectors) Equipment grounding conductors Internal cable clamps Terminal blocks Reference:314.16 B 3. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Regardless of grade level Only that have a floor located at grade level Only that have a floor located below grade level Only that have a floor located at grade or below grade level Reference:210.8 A 4. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The connection may require modification of permanent wiring if approved by the AHJ The connection point must be marked with phase rotation and system bonding requirements The temporary source may be smaller than the on?site source if load shedding is used Interlocking is optional if the temporary source is supervised by qualified personnel Reference:517.30 E 4 5. 63 – 2026 Changes Part 11New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.) A qualified person The National Electrical Code tables only The authority having jurisdiction (AHJ) A local utility company Reference:268.42 C 6. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To expand transformer oil?testing requirements to all electrical equipment To eliminate all requirements for oil?filled equipment below 15 kV To allow reconditioned oil?filled equipment to be installed without listing To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 7. 60 – 2026 Changes Part 11For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.) Unless the system is in an isolated area Unless the system is outdoors Within the same room or area Unless the system is supervised Reference:265.63 B 8. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) The National Electrical Safety Code Article 250 United Laboratories (UL) Article 266 Reference:265.1 9. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Interrupting capacity Switchboards Arc-Flash ratings Locations Reference:230.71 B 10. 71 – 2026 Changes Part 11Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.) All feeder and service In areas with rocks only Service 1000 volts AC or more only Reference:300.7 D3 11. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 16 AWG Copper 14 AWG Aluminum 18 AWG Copper 16 AWG Copper-Clad Aluminum Reference:310.5 A 12. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 100% of the generator nameplate current rating under all conditions 125% of the generator nameplate current rating 80% of the generator nameplate current rating 115% of the generator nameplate current rating Reference:445.13 13. 90 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.) 2 hole straps only Hangers only Straps only Staples Reference:334.2 14. 23 – 2026 Changes Part 11Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.) are not permitted unless with a manual bypass are allowed are never allowed are permitted if a warning label is also provided Reference:210.70 C3 15. 128 – 2026 Changes Part 11 The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Embedded snow-melting mats Electric baseboard heaters Baseboard heater raceways Unit heater fan motors Reference:424.2 16. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) A minimum of one conduit Each It is recommended that at least 1 conduit A minimum of two conduits Reference:250.109 B2 17. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) Type 3 surge-protection devices Video monitoring systems Listed smoke detection systems AVTs (absence of voltage testers) Reference:230.82 18. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Any conductor Surge protection devices Pneumatic lines Copper-Clad Aluminum Conductors Reference:392.22 B 19. 82 – 2026 Changes Part 11Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.) Cable terminations Cable removal Rejuvenation Cable relocation Reference:315.3 20. 161 – 2026 Changes Part 11According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5. Unclassified Class III Class II Class I Reference:511.10 B 2 21. 27 – 2026 Changes Part 11Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.) Both disconnects shall be installed The disconnects shall be installed inside out of the weather An emergency disconnecting means is no longer required Only one is needed if it complies with 225.41 Reference:225.31 A, 4 1 22. 84 – 2026 Changes Part 11__________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.) Wraps Screws Brackets Staples Reference:320.30 A 23. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Only applies to rigid conduit methods Only applies to each raceway type in the run Applies even when you transition and combine raceway types Does not apply to flexible conduits Reference:300.24 24. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 12 amperes 8 amperes 10 amperes 15 amperes Reference:Table 210.24(2) 25. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Alternating?current power distribution boxes Only equipment installed in permanent studio structures Only luminaires used for egress lighting Only generators rated over 15 kW Reference:530.2 26. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) As permitted by" the AHJ When installed "in accordance with" the technical NEC requirements As permitted by" a licensed electrical engineer Only if the common electrode terminates in one of the enclosures Reference:250.64 D1 27. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Reduce Are in addition to Substitute Overrides Reference:225.1 Note 2 28. 162 – 2026 Changes Part 11Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies? Mercantile occupancies only Industrial or storage occupancies only Assembly Business occupancies only Reference:512.6 29. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 18 inches 12 inches 24 inches 6 inches Reference:210.52 A5 30. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 2 3 5 4 Reference:406 31. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Type MI fittings Type MI Cable Straps and hangers Reference:332.2 32. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 16 AWG Copper-Clad Aluminum 14 AWG Aluminum 14 AWG Copper-Clad Aluminum 18 AWG Copper Reference:340.104 33. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only Category 3 and Category 4 spaces Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only the category assigned by the authority having jurisdiction Only Category 1 and Category 2 spaces Reference:517.7 & Informational note 34. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 60 feet 100 feet 50 feet 75 feet Reference:225.41 A1 35. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Using galvanized steel Coating the raceway Adding caution tape Sealing the raceway Reference:342.10 B 36. 20 – 2026 Changes Part 11As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.) 12 inches 6 inches 18 inches 24 inches Reference:210.52 C4 37. 124 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment? Similar equipment Ductless mini?split systems Electric baseboard heaters Wall?mounted room air conditioners Reference:422.12 ex.#1 38. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? Motor control centers Switchgear . Switchboards Panelboards Reference:408,3 B 39. 178 – 2026 Changes Part 11Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________. Off?site and capable of supplying only the life?safety branch On?site and sized to supply the entire EES On?site but permitted to supply only the critical branch Off?site and sized to supply the entire EES Reference:517.30 A 40. 122 – 2026 Changes Part 11 Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 210.12 — AFCI protection 250.114 — Equipment grounding conductor requirements 406.12 — Tamper‑resistant receptacles section 410.184 A and/or B Reference:410.184 41. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 21C Type 25 or 21 S Type 11 Type 2C or 11C Reference:300.13 E 42. 141 – 2026 Changes Part 11According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”) Their dielectric materials and protective mechanisms degrade over time They are no longer manufactured in standard voltage classes They cannot be effectively grounded after reconditioning They require special labeling that is not recognized by the NEC Reference:460.3 43. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The floor or working platform The top of the equipment enclosure The ceiling height . The nearest doorway Reference:404.10 A 2 44. 47 – 2026 Changes Part 11The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.) Considered a ground-fault path Used for dissipation of surges Used for dissipation of lightning Used for a voltage reference Reference:250.4 A5 45. 53 – 2026 Changes Part 11The NEC requirement to provide an Intersystem Bonding Termination (IBT) device at the service equipment and separate structure now additionally able to be secured and connect directly to ___________. (ITBs are used as a common grounding point for other systems like telephone, cable, and broadband. These are frequently grounded improperly if at all.) A non-metallic enclosure A satellite electrode A minimum 6 AWG copper grounding electrode conductor Any location inside Reference:250.94 A 46. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Any control conductors associated with the same building Any feeder conductors passing through to adjacent equipment Only grounding and bonding conductors associated with the service Reference:408.10 2 47. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2028 1.1.2026 1.1.2027 1.1.2029 Reference:245.2 48. 143 – 2026 Changes Part 11 Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only lithium?ion battery systems installed indoors Only standby battery systems used for emergency power Only battery systems connected to renewable-energy equipment ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Reference:480.1 49. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Break and quiet rooms All occupancies Emergency service facility sleeping quarters like police stations All commercial occupancies Reference:215.18 A 50. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 18 inches 12 inches 6 inches 10 inches Reference:392.18 F 51. 12 – 2026 Changes Part 11___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.) Holding tanks Industrial and commercial break rooms Dormitories (16 individuals or more) Commercial break rooms Reference:210.17 52. 126 – 2026 Changes Part 11Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that ) Continuous load only for branch circuit conductors As cold water heaters Continuous load Classification was removed Reference:422.13 53. 176 – 2026 Changes Part 11A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement? . Battery?equipped emergency luminaires Battery?equipped emergency luminaires Energy storage systems Reference:517.28 A ex. 54. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? It is mounted on the roof It is installed in a bedroom closet It is installed by the utility All NEC conditions for location Reference:550.51 B 1-7 55. 56 – 2026 Changes Part 11Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.) Yellow insulated conductor with a green stripe Light green insulated conductor Green conductor with a yellow stripe Green covered conductor Reference:250.119 A2 56. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Corrosive locations only Indoor dry locations only Wet locations Hazardous (Class I Reference:495.4 57. 191 – 2026 Changes Part 11 Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting ) Lamp guards are optional if the wiring is GFCI‑protected Bare lamps are permitted if located above 8 ft Lamps for general illumination must be protected by a luminaire or a lamp holder with a guard, and luminaires used for egress lighting must be listed Egress lighting may be provided by any portable lamp or cord‑and‑plug device Reference:525.25 A B 58. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 Only the largest source must be bonded to the structures grounding electrode Bonding is optional if all generators are rated less than 15 kW . Each source must have an isolated equipment grounding conductor Reference:525.12 59. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 8 amperes 12 amperes 15 amperes 10 amperes Reference:Table 210.24(1) 60. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. 501.3 and 505.3 501.10(A)(1) only Article 430 Part IV . 500.8 only Reference:513.3 A 61. 181 – 2026 Changes Part 11 When an EES uses more than one on-site power source, which of the following is REQUIRED when any single on-site source is disabled for service? The temporary connection must be sized to accommodate the largest power source Interlocking is optional if the temporary source is monitored by qualified personnel Integration of the temporary source may delay transfer switch timing if supervised The temporary source may be connected only after modifying permanent wiring Reference:517.30 F 1 62. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where combustible dusts are present in suspension Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where ignitable fibers are manufactured Any location containing Class I or Class II materials Reference:500.5 63. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Straps and hangers Straps Hangers Staples Reference:332.3 64. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 800 amperes 1000 amperes 400 amperes 600 amperes Reference:230.95 65. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 inch thick 1 3/4 inch thick 1 1/2 inch thick 2 inches thick Reference:300.6 E 66. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Green colored stripe Color painted on Single colored stripe other than green Double stripe Reference:200.7 A 67. 198 – 2026 Changes Part 11Outdoor receptacle outlets installed on mobile or manufactured homes must now comply with which NEC section?(Again this section is now in alignment with the requirements for stick built homes ) 406.9 550.13 only 210.52 300.5 Reference:550.13 D 68. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Industrial manufacturing plants Permanent theatrical stages only Commercial amusement parks with permanent rides Carnivals Reference:525.1 69. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) NEMA GD 1-2019 EEE Chapter 7 Section 300.11 NECA publication 1-23 Reference:300.4 C 70. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be bonded with a #12 copper conductor to any nearby metal object Reference:547.44 B 71. 137 – 2026 Changes Part 11If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges ) None of these answers are correct except this one 115 percent 125 percent 100 percent Reference:445.13 72. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Only embedded concrete heating mats Conductive pavement heating systems Only factory?assembled heating systems . Only roof?mounted heating cables Reference:Article 424, 425, 426 and 427 73. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? Site?specific engineered designs by both civil and electrical engineers Standard off?the?shelf listed assemblies shall have a plan review Field?assembled systems supervised by the installer Reference:426.64 74. 72 – 2026 Changes Part 11A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.) Listed fittings Marking requirement Conduit length Entry height Reference:300.9 A 75. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 120 volts to ground 300 volts to ground 50 volts to ground 150 volts to ground Reference:410.184 A B 76. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class C fuses Class A Class A fuses Class B fuses Reference:240.7 77. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Are resettable Must not be refurbished Can be installed if refurbished Can be reused Reference:242.3 78. 32 – 2026 Changes Part 11A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.) Identified (listed or labeled) Orange in color Verified by testing in the field Improvised in the field Reference:230.62 C 79. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Only wire?type equipment grounding conductors installed in every raceway Any mechanical connection Threaded couplings/hubs made up wrench?tight Bonding is not required if the system voltage is under 50 volts Reference:500.3 80. 51 – 2026 Changes Part 11In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.) All raceways Ferrous metal cable armor raceways All metallic raceways Nonferrous metal enclosures Reference:250.64 E1 81. 177 – 2026 Changes Part 11 A warning sign is required where removal of a grounding or bonding connection in power source equipment would interrupt the grounding- electrode-conductor or grounded conductor connection to another energized source. What must the sign state? “Disconnect all sources before servicing equipment” “Warning — Shock hazard exists if grounding electrode conductor or bonding jumper connection in this equipment is removed while another source is energized” “Caution — Multiple power sources supplied from separate feeders” “Hazardous voltage may be present even when equipment is off” Reference:517.28 B 82. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 2400 square feet 2000 square feet 1750 square feet 1500 square feet Reference:334.1 83. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 6 ft 0 in 5 ft 6 in 6 ft 7 in 7 ft 0 in Reference:404.10 A 2 84. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible in residential applications only Permissible Permissible in commercial applications only Strictly prohibitted Reference:240.24 E 85. 112 – 2026 Changes Part 11A nongrounding?type receptacle with no grounding conductor present may be replaced with which of the following? only a non-grounding receptacle all of these anwsers are true A grounding?type receptacle supplied through a GFCI device Any grounding?type receptacle as long as it is labeled No Equipment Ground Reference:406.12 D 1 86. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) Equipment design not compatible with GFCI protection As Assured Equipment Grounding Conductor Program (AEGCP) Supervision and only qualified personnel These are all requirements for a GFCI exception. Reference:210.8 B ex 2 87. 48 – 2026 Changes Part 11The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.) Is allowed at all times Is allowed if a rock bottom is encountered when a rod is driven at a 45 degree angle Is no longer allowed Is allowed only with express consent from the AHJ Reference:250.53 A4 88. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) All branch circuits and feeders Outside services Outside branch circuits and feeders Indoor branch circuits and feeders Reference:267.1 89. 166 – 2026 Changes Part 11 Emergency electrical disconnects for fuel‑dispensing systems shall be installed in approved locations not less than 20 ft and not more than 100 ft from the dispensing devices they serve. Activation of the emergency shutoff device or electrical disconnect shall disconnect power to all of the following EXCEPT __________.(Just change Clarifies receptacles over or adjacent to motor fuel and dispensing devices and hazardous classified locations must be disconnected during an emergency ) All associated power All remote pumps serving the dispensing devices All dispensing devices not supplied by intrinsically safe circuits Intrinsically safe electrical equipment Reference:514.11 A 90. 96 – 2026 Changes Part 11For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.) Bonding jumpers made of brass All listed fittings are Identified bimetallic couplings Bonding jumpers made of copper or brass Reference:342.14 91. 153 – 2026 Changes Part 11 According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 μm wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay ) Only optical fiber equipment located outside the hazardous location Only laser equipment located inside the hazardous location Only equipment specifically listed for Class I Laser equipment Reference:500.8 G 92. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed if the enclosure is indoors Shall not be installed Can be installed with AHJ guidance Can be installed Reference:250.64 G 93. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Imaging suites used for diagnostic procedures Patient care areas used for direct preparation and care Category 1 treatment rooms used for invasive procedures Reference:517.10 B 94. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards All set-screw style connectors Any split-bolt lug A listed mechanical grounding connector Reference:250.64 C 95. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It must be located at least 15 ft from the operator station to prevent accidental operation It may expose uninsulated live parts when opened without any additional restrictions It must be within sight and within 6 ft of the operator station and readily accessible during operation It must be located inside a locked room accessible only to qualified personnel Reference:525.21 A 96. 21 – 2026 Changes Part 11The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________. to address both dwelling and non-dwelling units to now only require for dwelling units the verbiage to mandate it not be located on the load side (this requirement has been deleted) so the receptacle shall be located within another room Reference:210.63 B 97. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Any aquatic vessels Any metal framed container Only bait wells Open aquatic vessels or containers Reference:210.8 B 98. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Listed or field evaluated Field evaluated only Listed as suitable for service only Additionally certified Reference:230.2 B 99. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 90 percent 100 percent 125 percent 110 percent Reference:265.20 A 100. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) Provided under engineering supervision Based on temperature rise Located outdoors In a campus environment Reference:265.19 B Back Save Progress Retry Finish