2026 Changes Part 1- MT Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 179 – 2026 Changes Part 11Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan ) Generating units Any power source approved by the authority having jurisdiction Only on?site generators listed for emergency systems Photovoltaic systems Reference:517.30 B 2. 164 – 2026 Changes Part 11According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________. Article 430 Part IV 501.10(A)(1) only . 500.8 only 501.3 and 505.3 Reference:513.3 A 3. 167 – 2026 Changes Part 11 Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Only adjacent to the dispensing device Inside Other than inside or adjacent to the dispensing device Only inside the dispensing device Reference:514.13 4. 48 – 2026 Changes Part 11The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.) Is allowed only with express consent from the AHJ Is no longer allowed Is allowed if a rock bottom is encountered when a rod is driven at a 45 degree angle Is allowed at all times Reference:250.53 A4 5. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion It must be bonded with a #12 copper conductor to any nearby metal object Reference:547.44 B 6. 180 – 2026 Changes Part 11An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance ) The connection may require modification of permanent wiring if approved by the AHJ Interlocking is optional if the temporary source is supervised by qualified personnel The connection point must be marked with phase rotation and system bonding requirements The temporary source may be smaller than the on?site source if load shedding is used Reference:517.30 E 4 7. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Interrupting capacity Switchboards Locations Arc-Flash ratings Reference:230.71 B 8. 122 – 2026 Changes Part 11 Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 250.114 — Equipment grounding conductor requirements 406.12 — Tamper‑resistant receptacles section 410.184 A and/or B 210.12 — AFCI protection Reference:410.184 9. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment must be reinspected by the AHJ only The equipment may be reused if insulation resistance tests pass The equipment shall be replaced unless the installer certifies it The equipment shall be evaluated and approved by the original manufacturer Reference:408.3 A 10. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) Located outdoors Provided under engineering supervision In a campus environment Based on temperature rise Reference:265.19 B 11. 25 – 2026 Changes Part 11Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.) Break and quiet rooms All occupancies Emergency service facility sleeping quarters like police stations All commercial occupancies Reference:215.18 A 12. 158 – 2026 Changes Part 11In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed ) Commercial Ordinary table 501.10 A 1. & Restricted Temporary Reference:501.1 13. 146 – 2026 Changes Part 11According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies? Equipment rated not over 15 All equipment over 1 Only equipment over 52 Reference:495.2 AB 14. 162 – 2026 Changes Part 11Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies? Mercantile occupancies only Industrial or storage occupancies only Assembly Business occupancies only Reference:512.6 15. 199 – 2026 Changes Part 11Which of the following is TRUE regarding service equipment for a mobile home under Article 550? It shall not be mounted in or on the mobile home and must be within sight of the home it serves It must be located at least 50 ft from the mobile home It may be mounted on the exterior wall of the mobile home if weatherproof It cannot serve as the emergency disconnect Reference:550.51 16. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 8 amperes 10 amperes 12 amperes 15 amperes Reference:Table 210.24(2) 17. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) NEMA GD 1-2019 Section 300.11 NECA publication 1-23 EEE Chapter 7 Reference:300.4 C 18. 181 – 2026 Changes Part 11 When an EES uses more than one on-site power source, which of the following is REQUIRED when any single on-site source is disabled for service? The temporary connection must be sized to accommodate the largest power source Integration of the temporary source may delay transfer switch timing if supervised Interlocking is optional if the temporary source is monitored by qualified personnel The temporary source may be connected only after modifying permanent wiring Reference:517.30 F 1 19. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 21C Type 2C or 11C Type 11 Type 25 or 21 S Reference:300.13 E 20. 133 – 2026 Changes Part 11Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit ) Listed as a field installable accessory Inspected by the AHJ (Authority having jurisdiction ) Purchased from the manufacturer of the HVAC unit being worked on None of these answers are correct Reference:440.2 21. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Individual branch circuits Branch circuits supplied from emergency sources Branch circuits with AFCI protection Multiwire branch circuits Reference:517.15 22. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) Service disconnects rated under 30 amperes The disconnection of surge-protection devices A metering center A switchboard Reference:230.71 A 23. 11 – 2026 Changes Part 11Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.) 2500 2400 1500 2000 Reference:210.13 A&B 24. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 18 inches 12 inches 6 inches 24 inches Reference:210.52 A5 25. 147 – 2026 Changes Part 11According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily) Indoor dry locations only Corrosive locations only Hazardous (Class I Wet locations Reference:495.4 26. 109 – 2026 Changes Part 11 According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment ) Reconditioned wiring devices are permitted only in non‑dwelling occupancies Reconditioned wiring devices are not permitted to be used Reconditioned wiring devices are permitted if tested by a qualified person Reconditioned wiring devices are permitted if listed by a third‑party refurbisher Reference:406.3 27. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Utility disconnect Electrical disconnect Service disconnect Service switch Reference:230.70 B 28. 94 – 2026 Changes Part 11An update to Underground Feeder and Branch-Circuit Cable (Type UF) now permits the use of _______ conductors as the minimum size for this burial type cable. (This popular cable commonly used in residential and light commercial underground applications can run long distances so this change can be a considerable cost savings.) 16 AWG Copper-Clad Aluminum 14 AWG Aluminum 18 AWG Copper 14 AWG Copper-Clad Aluminum Reference:340.104 29. 59 – 2026 Changes Part 11For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.) 100 percent 110 percent 90 percent 125 percent Reference:265.20 A 30. 123 – 2026 Changes Part 11The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold? 150 volts to ground 300 volts to ground 50 volts to ground 120 volts to ground Reference:410.184 A B 31. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) Any jacket covering A messenger A copper-alloy armor Aluminum conductors Reference:330.10 A 32. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To allow reconditioned oil?filled equipment to be installed without listing To eliminate all requirements for oil?filled equipment below 15 kV To expand transformer oil?testing requirements to all electrical equipment To specify requirements for oil?filled equipment other than transformers Reference:article495 parts VI andVII 33. 156 – 2026 Changes Part 11 Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations? Only equipment located outside the hazardous location requires reconditioning evaluation Reconditioned equipment is permitted Reconditioned equipment is prohibited in all hazardous locations unless field evaluated by the AHJ All reconditioned equipment must be listed and marked Explosion Proof regardless of original classification Reference:501.3 34. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Critical branch and equipment branch; division occurs at the panelboards Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and equipment branch; division occurs at the transfer switches Life safety branch and critical branch; division occurs at the service disconnect Reference:517.42 A 35. 44 – 2026 Changes Part 11Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.) Must not be refurbished Are resettable Can be installed if refurbished Can be reused Reference:242.3 36. 98 – 2026 Changes Part 11A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.) 12 inches 6 inches 18 inches 10 inches Reference:392.18 F 37. 4 – 2026 Changes Part 11Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.) Indoor wet locations (damp locations were removed) Outdoor wet and damp locations only Indoor damp and/or wet locations Outdoor wet locations only Reference:210.8 A 38. 197 – 2026 Changes Part 11 Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) Receptacle outlets must be GFCI protected only when installed in bathrooms Only outdoor receptacles require GFCI protection GFCI protection must be provided as required in 210.8 GFCI protection is optional if the receptacle is within sight of the panelboard Reference:550.13 B 39. 150 – 2026 Changes Part 11 According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor? The combustible floor must be treated with a fire-retardant coating approved by the AHJ Noncombustible protection must be provided under any openings in the bottom of the switchgear The switchgear must be elevated at least 12 inches above the floor No special provisions are required if the switchgear is listed for indoor use Reference:495.36 40. 142 – 2026 Changes Part 11According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors? . Reconditioned resistors are permitted to be installed Reconditioned reactors are permitted to be installed Neither reconditioned reactors nor reconditioned resistors are permitted to be installed Both reconditioned reactors and reconditioned resistors are permitted to be installed Reference:470.3 A B 41. 52 – 2026 Changes Part 11A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.) Can be installed with AHJ guidance Can be installed Shall not be installed Can be installed if the enclosure is indoors Reference:250.64 G 42. 165 – 2026 Changes Part 11All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one ) Class II Class I Unclassified Reference:513.8 43. 9 – 2026 Changes Part 11When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.) The HVAC disconnect shall be marked with a warning label The panel circuit breaker shall be marked with a warning label Both the panel circuit breaker and HVAC shall be marked with a warning label Marking labels are recommended Reference:210.8 F ex 3 44. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Only locations where ignitable fibers are manufactured Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Any location containing Class I or Class II materials Only locations where combustible dusts are present in suspension Reference:500.5 45. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 600 amperes 800 amperes 400 amperes 1000 amperes Reference:230.95 46. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It may expose uninsulated live parts when opened without any additional restrictions It must be within sight and within 6 ft of the operator station and readily accessible during operation It must be located at least 15 ft from the operator station to prevent accidental operation It must be located inside a locked room accessible only to qualified personnel Reference:525.21 A 47. 120 – 2026 Changes Part 11As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section? Only conductors intended for termination within that section Any control conductors associated with the same building Only grounding and bonding conductors associated with the service Any feeder conductors passing through to adjacent equipment Reference:408.10 2 48. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. 750 amps at 750 volts 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts all these answers are true 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 49. 103 – 2026 Changes Part 11 When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? Dimmer switches GFCI‑type switching devices General‑use snap switches Knife switches Reference:404.3 50. 47 – 2026 Changes Part 11The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.) Used for dissipation of lightning Considered a ground-fault path Used for a voltage reference Used for dissipation of surges Reference:250.4 A5 51. 119 – 2026 Changes Part 11According to the NEC, which of the following types of equipment is not permitted to be reconditioned? . Switchboards Switchgear Panelboards Motor control centers Reference:408,3 B 52. 185 – 2026 Changes Part 11Diagnostic imaging and treatment equipment shall be installed in accordance with which portion of the NEC?(The 2026 NEC revision clarifies and expands the scope of part five vertical 517 by stating that it applies to all diagnostic imaging and treatment equipment not just x-ray systems ) Article 517 Article 645 Article 700 Article 760 Reference:517.7 53. 172 – 2026 Changes Part 11Part II of Article 517 does NOT apply to which of the following spaces? Patient sleeping rooms in nursing homes wired under Chapters 14 and used exclusively for sleeping Patient care areas used for direct preparation and care Imaging suites used for diagnostic procedures Category 1 treatment rooms used for invasive procedures Reference:517.10 B 54. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site but sized only for the life?safety branch; on?site only On?site and sized to supply the entire EES; either on?site or off?site Off?site and sized to supply the entire EES; on?site only Off?site; off?site only Reference:517.41 A 55. 170 – 2026 Changes Part 11All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care ) Only the category assigned by the authority having jurisdiction Category 1 through Category 4 requirements NFPA 99 health care faculties code chapter 4 Only Category 1 and Category 2 spaces Only Category 3 and Category 4 spaces Reference:517.7 & Informational note 56. 111 – 2026 Changes Part 11In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish: – **Wiring?devicetype switches** – **Receptacles and cord connectors** – **Attachment plugs (caps)** ) 5 2 3 4 Reference:406 57. 28 – 2026 Changes Part 11The NEC section requiring emergency disconnects for feeders to structures for one- and two-family dwellings was revised for clarity. The disconnect can be installed on the structure or within sight which is now _______ in this situation . (There were proposals to allow the emergency disconnects to be installed with an unlimited distance.) 100 feet 50 feet 60 feet 75 feet Reference:225.41 A1 58. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 15 ampere 10 ampere 20 ampere 30 ampere Reference:210.22 ex 59. 115 – 2026 Changes Part 11 Receptacles shall not be installed in a face‑up position in which of the following locations? (The NEC prohibits installing receptacles face‑up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) On walls adjacent to countertops In a laundry area Under raised floors in IT rooms On work surfaces Reference:406.14 G 60. 88 – 2026 Changes Part 11For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.) Straps and hangers Type MI fittings Type MI Cable Reference:332.2 61. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) All types of One- and two-family dwelling and multifamily only One- and two-family dwelling units only Commercial and industrial only Reference:230.70 D 62. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? Article 110 Article 314 Article 210 article 406 Reference:406 63. 14 – 2026 Changes Part 11In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard) 14 AWG 18 AWG 20 AWG 16 AWG Reference:210.24(1) 64. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 90.7 Examination of equipment for safety Section 408.3 Support and arrangement of busbars Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Reference:408.10 F 65. 168 – 2026 Changes Part 11 In addition to the off‑site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities ) Power production sources, fuel cell systems, energy storage systems, and healthcare microgrids Only energy storage systems listed for standby use Only generators listed for emergency systems Photovoltaic systems only Reference:517.4 66. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Listed as suitable for service only Additionally certified Field evaluated only Listed or field evaluated Reference:230.2 B 67. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Non-flexible metallic raceways and fittings Flexible metallic raceways and fittings Felexible sealtight and fittings Rigid Metal Conduit (RMC) only Reference:250.102 A 68. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) Article 250 United Laboratories (UL) The National Electrical Safety Code Article 266 Reference:265.1 69. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Any hangers Jacketing Blocking Cable cleats Reference:330.30 A 70. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside branch circuits and feeders Indoor branch circuits and feeders Outside services All branch circuits and feeders Reference:267.1 71. 51 – 2026 Changes Part 11In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.) Nonferrous metal enclosures All metallic raceways All raceways Ferrous metal cable armor raceways Reference:250.64 E1 72. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) A minimum of one conduit It is recommended that at least 1 conduit Each A minimum of two conduits Reference:250.109 B2 73. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2027 1.1.2029 1.1.2028 1.1.2026 Reference:245.2 74. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Connectors that do not comply with ANSI/UL 467 standards All set-screw style connectors Any split-bolt lug A listed mechanical grounding connector Reference:250.64 C 75. 76 – 2026 Changes Part 11A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.) 18 AWG Copper 14 AWG Aluminum 16 AWG Copper 16 AWG Copper-Clad Aluminum Reference:310.5 A 76. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A qualified individual A licensed administrator Any engineer A master electrician Reference:266.4 C 77. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 100 amperes or less 60 amperes or less 80 amperes or less 70 amperes or less Reference:210.8 F 78. 102 – 2026 Changes Part 11A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switchessuch as snap switches, dimmers, and electronic controlswere moved to Article 406 as part of a structural reorganization.) The increase of allowable switch voltage ratings to 2000 volts The relocation of most device?type switches The expansion of Article 404 to include all wiring devices such as receptacles and GFCIs The elimination of Article 404 and redistribution of its content into Chapter 2 Reference:404.1 B 79. 65 – 2026 Changes Part 11The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.) Over 500 volts DC Over 500 volts AC That supply portable or mobile equipment For utilities Reference:270.20 C 80. 171 – 2026 Changes Part 11Part II of Article 517 applies to which of the following? Only hospitals and ambulatory surgical centers Patient care spaces of all healthcare facilities Only Category 1 and Category 2 treatment rooms Only facilities with essential electrical systems Reference:517.10 A 81. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Considered as current carrying and shall be counted Counted unless under engineering supervision Not considered as current carrying Considered as current carrying but does not need to be counted Reference:310.15 E 82. 127 – 2026 Changes Part 11Conductive pavement heating systems shall be designed as which of the following? shall have a plan review Standard off?the?shelf listed assemblies Field?assembled systems supervised by the installer Site?specific engineered designs by both civil and electrical engineers Reference:426.64 83. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Adding caution tape Using galvanized steel Sealing the raceway Coating the raceway Reference:342.10 B 84. 148 – 2026 Changes Part 11 According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)? Isolating means are required unless the equipment can be deenergized by other methods such as draw out units non load break isolating switches must be interlocked with a series interrupting device or field marked with a warning Only service disconnects are required to provide isolation; isolating switches are optional and need no markings or interlocks Isolating switches may be opened or closed under load if the operator is qualified and PPE is worn Isolating switches must always be load?break rated and are required for all equipment regardless of design Reference:495.22 85. 24 – 2026 Changes Part 11A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.) 800 amperes 600 amperes 1000 amperes 500 amperes Reference:215.10 B 86. 112 – 2026 Changes Part 11A nongrounding?type receptacle with no grounding conductor present may be replaced with which of the following? A grounding?type receptacle supplied through a GFCI device all of these anwsers are true only a non-grounding receptacle Any grounding?type receptacle as long as it is labeled No Equipment Ground Reference:406.12 D 1 87. 113 – 2026 Changes Part 11Non grounding type receptacles with no grounding conductor present can be replaced with_______. 20 amp grounding type receptacles AFCI receptacles Grounding type receptacles All of these answers are false Reference:406.12 D 1 88. 138 – 2026 Changes Part 11 According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition? Only if the tap conductors comply with 240.21(B), and taps are not permitted for portable generators rated 15 kW or less where field wiring terminals are not accessible Only if the tap conductors are less than 10 ft in length Only if the tap conductors are supervised by an AHJ‑approved maintenance program Only if the tap conductors are installed in rigid metal conduit Reference:445.13 B 89. 143 – 2026 Changes Part 11 Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only standby battery systems used for emergency power Only battery systems connected to renewable-energy equipment Only lithium?ion battery systems installed indoors Reference:480.1 90. 194 – 2026 Changes Part 11Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes ) They must be bonded with a minimum #12 copper conductor if GFCI protection is provided D. No bonding is required if each section has its own feeder disconnect They must be bonded together with a solid copper conductor not smaller than #8 AWG They must be bonded together using a solid copper conductor sized per Table 250.122 Reference: 545.20 D 545.26 91. 157 – 2026 Changes Part 11Section 501.3(B) of the 2026 NEC is ____________. A prohibition on reconditioned equipment in hazardous locations A new requirement for intrinsically safe systems A requirement for wiring methods in Class I Reserved for future use Reference:501.3 B 92. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class A Class A fuses Class B fuses Class C fuses Reference:240.7 93. 79 – 2026 Changes Part 11A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.) Meter socket enclosures All electrical equipment Fittings Electrical mechanical supports Reference:312.3 94. 125 – 2026 Changes Part 11 The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A whole‑house humidifier A supplemental electric baseboard heater A ductless mini‑split indoor unit Lighting outlets required by 210.70 C and receptacles required by 210.63 A Reference:422.12 95. 186 – 2026 Changes Part 11Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential) Carnivals Commercial amusement parks with permanent rides Permanent theatrical stages only Industrial manufacturing plants Reference:525.1 96. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) In crawl spaces When fished between acess points and concealed Directly buried in the earth When bundled Reference:334.12 97. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure Only at the service disconnect At the load terminals of the transfer switch At the generator or the first disconnecting means supplied by the generator Reference:525.31 98. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Does not apply to flexible conduits Only applies to rigid conduit methods Only applies to each raceway type in the run Applies even when you transition and combine raceway types Reference:300.24 99. 200 – 2026 Changes Part 11Service equipment is permitted to be installed in or on a manufactured home only if which condition is met? All NEC conditions for location It is mounted on the roof It is installed in a bedroom closet It is installed by the utility Reference:550.51 B 1-7 100. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Any mechanical connection Only wire?type equipment grounding conductors installed in every raceway Threaded couplings/hubs made up wrench?tight Bonding is not required if the system voltage is under 50 volts Reference:500.3 Back Save Progress Retry Finish