2026 Changes Part 1- MT Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 26 – 2026 Changes Part 11NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.) Are in addition to Overrides Reduce Substitute Reference:225.1 Note 2 2. 161 – 2026 Changes Part 11According to the NEC, an electric vehicle connector shall NOT be located within a __________ location as defined in 511.5. Class I Class III Class II Unclassified Reference:511.10 B 2 3. 40 – 2026 Changes Part 11Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.) 1000 amperes 800 amperes 400 amperes 600 amperes Reference:230.95 4. 185 – 2026 Changes Part 11Diagnostic imaging and treatment equipment shall be installed in accordance with which portion of the NEC?(The 2026 NEC revision clarifies and expands the scope of part five vertical 517 by stating that it applies to all diagnostic imaging and treatment equipment not just x-ray systems ) Article 700 Article 645 Article 760 Article 517 Reference:517.7 5. 50 – 2026 Changes Part 11A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.) When installed "in accordance with" the technical NEC requirements Only if the common electrode terminates in one of the enclosures As permitted by" a licensed electrical engineer As permitted by" the AHJ Reference:250.64 D1 6. 155 – 2026 Changes Part 11Which of the following bonding methods is not permitted for normally noncurrent?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations ) Threaded couplings made up wrench?tight Locknuts Tight threadless couplings used with metal raceways Listed bonding bushings with bonding jumpers Reference:500.30 B 7. 70 – 2026 Changes Part 11The requirement to maintain a 1 1/2 inch spacing from a roof decking for cables, raceways, and boxes now includes a decking poured with light weight concrete at least ______. (It is common during roofing repairs or replacement to use long screws that can penetrate wiring methods.) 1 3/4 inch thick 2 inches thick 1 1/2 inch thick 1 inch thick Reference:300.6 E 8. 191 – 2026 Changes Part 11Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting ) Lamps for general illumination must be protected by a luminaire or a lamp holder with a guard Egress lighting may be provided by any portable lamp or cord?and?plug device Lamp guards are optional if the wiring is GFCI?protected Bare lamps are permitted if located above 8 ft Reference:525.25 A B 9. 129 – 2026 Changes Part 11Fixed outdoor electric deicing and snow?melting equipment includes which of the following? Only embedded concrete heating mats Only factory?assembled heating systems Conductive pavement heating systems . Only roof?mounted heating cables Reference:Article 424, 425, 426 and 427 10. 89 – 2026 Changes Part 11The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.) Straps and hangers Hangers Straps Staples Reference:332.3 11. 160 – 2026 Changes Part 11According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________. Suitable for damp locations only Identified for extra?hard usage Limited to a maximum length of 3 ft Permitted only when installed in rigid metal conduit Reference:511.10 B 12. 86 – 2026 Changes Part 11A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.) A copper-alloy armor A messenger Any jacket covering Aluminum conductors Reference:330.10 A 13. 21 – 2026 Changes Part 11The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________. so the receptacle shall be located within another room to now only require for dwelling units to address both dwelling and non-dwelling units the verbiage to mandate it not be located on the load side (this requirement has been deleted) Reference:210.63 B 14. 105 – 2026 Changes Part 11Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position? 5 ft 6 in 6 ft 7 in 7 ft 0 in 6 ft 0 in Reference:404.10 A 2 15. 58 – 2026 Changes Part 11The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.) In a campus environment Based on temperature rise Provided under engineering supervision Located outdoors Reference:265.19 B 16. 154 – 2026 Changes Part 11The 2026 NEC requires which of the following bonding methods for normally noncurrent?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations? Threaded couplings/hubs made up wrench?tight Bonding is not required if the system voltage is under 50 volts Any mechanical connection Only wire?type equipment grounding conductors installed in every raceway Reference:500.3 17. 159 – 2026 Changes Part 11Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________. Listed for the location and listed for field installation with the luminaire being retrofitted Installed by a qualified person and approved by the manufacturer Marked suitable for damp locations Installed in accordance with Article 410 only Reference:501.130 C 18. 99 – 2026 Changes Part 11Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.) Copper-Clad Aluminum Conductors Pneumatic lines Surge protection devices Any conductor Reference:392.22 B 19. 130 – 2026 Changes Part 11A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts ) . Design F and Design G motors Design B(E) and Design C(E) motors Design S and Design T motors Design A and Design D motors Reference:Recognition throughout article 430 20. 81 – 2026 Changes Part 11Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.) Equipment grounding conductors Internal cable clamps Terminal blocks Wire nuts (splicing connectors) Reference:314.16 B 21. 54 – 2026 Changes Part 11The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.) Felexible sealtight and fittings Rigid Metal Conduit (RMC) only Non-flexible metallic raceways and fittings Flexible metallic raceways and fittings Reference:250.102 A 22. 18 – 2026 Changes Part 11A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.) Only fixed cabinets with a work surface Any fixed cabinet Only fixed cabinets with countertops Only fixed cabinets that are not recessed Reference:210.52 A2(1) 23. 5 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.) Only bait wells Open aquatic vessels or containers Any metal framed container Any aquatic vessels Reference:210.8 B 24. 49 – 2026 Changes Part 11Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation does that include burial?) Any split-bolt lug Connectors that do not comply with ANSI/UL 467 standards All set-screw style connectors A listed mechanical grounding connector Reference:250.64 C 25. 75 – 2026 Changes Part 11A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.) Does not apply to flexible conduits Applies even when you transition and combine raceway types Only applies to rigid conduit methods Only applies to each raceway type in the run Reference:300.24 26. 57 – 2026 Changes Part 11New Article 265 now specifically covers branch circuits over 1000 volts AC and 1500 volts DC but also additionally recommends _________ for additional information. (Content relocation from Article 235 to restructure low-voltage (LV) and medium voltage (MV) systems.) The National Electrical Safety Code United Laboratories (UL) Article 250 Article 266 Reference:265.1 27. 193 – 2026 Changes Part 11Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.) Alternating?current power distribution boxes Only luminaires used for egress lighting Only equipment installed in permanent studio structures Only generators rated over 15 kW Reference:530.2 28. 10 – 2026 Changes Part 11Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.) AFCI protection shall be marked at the first device The entire circuit shall now be protected AFCI protection shall be installed at the overcurrent protection device AFCI protection can be located at the first switch Reference:210.12 E 29. 31 – 2026 Changes Part 11Service entrance conductors are allowed to be spliced or tapped, and the equipment used must be both listed and marked or identified for use. The new industry-recognized abbreviation that manufacturers can use instead of the entire phrase “suitable for use on the line side of service equipment” is _______. (in the past, this was not allowed, making changes challenging. Line side equipment must meet strict additional standards because they are not protected by an overcurrent device.) SSS SUS SVC SLS Reference:230.46 note 30. 41 – 2026 Changes Part 11A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.) Class A fuses Class B fuses Class C fuses Class A Reference:240.7 31. 6 – 2026 Changes Part 11An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.) As Assured Equipment Grounding Conductor Program (AEGCP) Equipment design not compatible with GFCI protection These are all requirements for a GFCI exception. Supervision and only qualified personnel Reference:210.8 B ex 2 32. 101 – 2026 Changes Part 11There is a significant change to the scope of NEC article 404 by including __________. All of the answers are true 3-way "snap" switches Service equipment Pull out switches Reference:404.1 A 33. 55 – 2026 Changes Part 11A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.) It is recommended that at least 1 conduit A minimum of one conduit A minimum of two conduits Each Reference:250.109 B2 34. 43 – 2026 Changes Part 11New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.) Permissible Permissible in residential applications only Strictly prohibitted Permissible in commercial applications only Reference:240.24 E 35. 38 – 2026 Changes Part 11The NEC code section that governs the maximum number of disconnects each service can have (the two to six rule) has also been updated regarding how the disconnects can be physically arranged including _____________. (To also address maintenance safety and arc-flash protection.) Locations Arc-Flash ratings Interrupting capacity Switchboards Reference:230.71 B 36. 37 – 2026 Changes Part 11The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.) A switchboard Service disconnects rated under 30 amperes A metering center The disconnection of surge-protection devices Reference:230.71 A 37. 107 – 2026 Changes Part 11Knife switches used for isolating rated less than ______ shall be considered general?use switches. 1000 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts 750 amps at 750 volts all these answers are true 1200 amps at 250 volts or less and at over 1000 amps at 251 to 1000 volts Reference:404.13 C 38. 15 – 2026 Changes Part 11If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.) 8 amperes 12 amperes 10 amperes 15 amperes Reference:Table 210.24(1) 39. 114 – 2026 Changes Part 11On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met? The receptacle is located more than 12 inches from a sink and AFCI The receptacle is part of a listed assembly specifically designed for face?up installation Reference:406.14 G 40. 195 – 2026 Changes Part 11Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments ) It must be bonded to the grounding electrode system or an equipment grounding terminal using a solid copper conductor not smaller than #8 AWG It must be bonded with a #12 copper conductor to any nearby metal object It must be connected only to the service neutral It may be bonded with aluminum conductors if not subject to corrosion Reference:547.44 B 41. 173 – 2026 Changes Part 11Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads ) Multiwire branch circuits Branch circuits with AFCI protection Branch circuits supplied from emergency sources Individual branch circuits Reference:517.15 42. 196 – 2026 Changes Part 11The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings ) 250.8(A)(1) through (A)(6) 110.26(A)(1) through (A)(3) 300.5(A) through (A)(4) 547.44(C)(1) through 547.44(C)(4) Reference:547.44 C 43. 151 – 2026 Changes Part 11What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment ) To allow reconditioned oil?filled equipment to be installed without listing To specify requirements for oil?filled equipment other than transformers To expand transformer oil?testing requirements to all electrical equipment To eliminate all requirements for oil?filled equipment below 15 kV Reference:article495 parts VI andVII 44. 137 – 2026 Changes Part 11If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges ) None of these answers are correct except this one 125 percent 100 percent 115 percent Reference:445.13 45. 169 – 2026 Changes Part 11Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________. Connected loads The nameplate rating of the largest single piece of equipment only Prudent demand factors and historic data Feeder calculations Reference:517.4 B 46. 122 – 2026 Changes Part 11Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following? 406.12 Tamper?resistant receptacles section 410.184 A and/or B 250.114 Equipment grounding conductor requirements 210.12 AFCI protection Reference:410.184 47. 61 – 2026 Changes Part 11New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.) A licensed administrator Any engineer A qualified individual A master electrician Reference:266.4 C 48. 84 – 2026 Changes Part 11__________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.) Wraps Staples Brackets Screws Reference:320.30 A 49. 92 – 2026 Changes Part 11Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.) When bundled In crawl spaces When fished between acess points and concealed Directly buried in the earth Reference:334.12 50. 95 – 2026 Changes Part 11Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.) Using galvanized steel Adding caution tape Coating the raceway Sealing the raceway Reference:342.10 B 51. 13 – 2026 Changes Part 11A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.) 15 ampere 30 ampere 20 ampere 10 ampere Reference:210.22 ex 52. 192 – 2026 Changes Part 11Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception ) At any convenient point in the portable structure At the load terminals of the transfer switch Only at the service disconnect At the generator or the first disconnecting means supplied by the generator Reference:525.31 53. 115 – 2026 Changes Part 11Receptacles shall not be installed in a face?up position in which of the following locations? (The NEC prohibits installing receptacles face?up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard) Under raised floors in IT rooms On work surfaces In a laundry area . On walls adjacent to countertops Reference:406.14 G 54. 36 – 2026 Changes Part 11The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.) Can qualify if listed Does not qualify Qualifiers Can qualify if listed SVC Reference:230.70 F 55. 19 – 2026 Changes Part 11The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.) 24 inches 6 inches 12 inches 18 inches Reference:210.52 A5 56. 91 – 2026 Changes Part 11A new exception allows nonhabitable grade level storage buildings less than _______ with Type V construction to use NM cable without a 15-minute thermal barrier. A 15-minute thermal barrier typically is a gypsum wallboard (sheetrock) covering. 1750 square feet 1500 square feet 2400 square feet 2000 square feet Reference:334.1 57. 46 – 2026 Changes Part 11Requiring listing for overcurrent protection on systems rated over 1000 volts AC (medium voltage systems) is a new addition to the NEC with an effective date of _________ for devices 15,000 volts or less. (Historically not listed utility-grade components are now more commonly installed on private premises. The additional time allows for the infrastructure to catch up.) 1.1.2026 1.1.2027 1.1.2029 1.1.2028 Reference:245.2 58. 135 – 2026 Changes Part 11According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following? The manufacturers installation instructions for both indoor and outdoor units The minimum circuit ampacity and maximum fuse size for the outdoor unit The location of all indoor units it supplies Reference:440.15 59. 132 – 2026 Changes Part 11Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center? 110.21(B) Field?applied hazard markings 408.4 Circuit directory and identification 110.16 Arc?flash hazard warning 430.102 Disconnecting means for motors Reference:430.98 A 60. 68 – 2026 Changes Part 11The NEC now requires a replacement to conductors that have been damaged , for example, overheating and now also references to industry standards _________ to help us evaluate those conductors. (Previously this section focused on conductor protection by physical damage.) NEMA GD 1-2019 Section 300.11 NECA publication 1-23 EEE Chapter 7 Reference:300.4 C 61. 143 – 2026 Changes Part 11Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations ) Only lithium?ion battery systems installed indoors Only standby battery systems used for emergency power ll stationary battery installations with a capacity greater than 3.6 MJ (1 kWh) Only battery systems connected to renewable?energy equipment Reference:480.1 62. 157 – 2026 Changes Part 11Section 501.3(B) of the 2026 NEC is ____________. Reserved for future use A prohibition on reconditioned equipment in hazardous locations A requirement for wiring methods in Class I A new requirement for intrinsically safe systems Reference:501.3 B 63. 145 – 2026 Changes Part 11According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum ) A cooling fan that operates whenever the battery is charging A timer?based charging system that limits charging to off?peak hours A secondary disconnecting means located within sight of the battery room Overcharge control provisions to prevent the batteries from becoming overcharged Reference:480.14 64. 3 – 2026 Changes Part 11Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards. Only that have a floor located at grade level Only that have a floor located at grade or below grade level Only that have a floor located below grade level Regardless of grade level Reference:210.8 A 65. 152 – 2026 Changes Part 11According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments ) Any location containing Class I or Class II materials Those locations specifically identified in 500.5(D)(1)(a) through 500.5(D)(1)© Only locations where combustible dusts are present in suspension Only locations where ignitable fibers are manufactured Reference:500.5 66. 74 – 2026 Changes Part 11When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.) Type 25 or 21 S Type 21C Type 2C or 11C Type 11 Reference:300.13 E 67. 125 – 2026 Changes Part 11The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit? A supplemental electric baseboard heater A whole?house humidifier Lighting outlets required by 210.70 C and receptacles required by 210.63 A . A ductless mini?split indoor unit Reference:422.12 68. 62 – 2026 Changes Part 11The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.) Outside services Indoor branch circuits and feeders All branch circuits and feeders Outside branch circuits and feeders Reference:267.1 69. 33 – 2026 Changes Part 11Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.) Electrical disconnect Service switch Utility disconnect Service disconnect Reference:230.70 B 70. 131 – 2026 Changes Part 11Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following? The motor nameplate data and conductor ampacity tables The manufacturers instructions The reconditioning contractors documented quality?control program The installers field evaluation or local AHJ preference Reference:430.3 71. 134 – 2026 Changes Part 11If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened? It must automatically de?energize the equipment when opened It must be locked or require a tool to be opened It must be interlocked with the controller to prevent operation Reference:440.11 72. 39 – 2026 Changes Part 11The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.) Video monitoring systems Type 3 surge-protection devices Listed smoke detection systems AVTs (absence of voltage testers) Reference:230.82 73. 183 – 2026 Changes Part 11The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content ) Critical branch and delayed?automatic branch; division occurs at the generator terminals Life safety branch and critical branch; division occurs at the service disconnect Critical branch and equipment branch; division occurs at the panelboards Life safety branch and equipment branch; division occurs at the transfer switches Reference:517.42 A 74. 103 – 2026 Changes Part 11When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code? General?use snap switches GFCI?type switching devices Dimmer switches Knife switches Reference:404.3 75. 35 – 2026 Changes Part 11In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.) One- and two-family dwelling units only Commercial and industrial only All types of One- and two-family dwelling and multifamily only Reference:230.70 D 76. 102 – 2026 Changes Part 11A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switchessuch as snap switches, dimmers, and electronic controlswere moved to Article 406 as part of a structural reorganization.) The relocation of most device?type switches The increase of allowable switch voltage ratings to 2000 volts The expansion of Article 404 to include all wiring devices such as receptacles and GFCIs The elimination of Article 404 and redistribution of its content into Chapter 2 Reference:404.1 B 77. 128 – 2026 Changes Part 11The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following? Electric baseboard heaters Embedded snow?melting mats Unit heater fan motors Baseboard heater raceways Reference:424.2 78. 188 – 2026 Changes Part 11Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525? It may expose uninsulated live parts when opened without any additional restrictions It must be located at least 15 ft from the operator station to prevent accidental operation It must be within sight and within 6 ft of the operator station and readily accessible during operation It must be located inside a locked room accessible only to qualified personnel Reference:525.21 A 79. 1 – 2026 Changes Part 11A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.) Double stripe Green colored stripe Color painted on Single colored stripe other than green Reference:200.7 A 80. 118 – 2026 Changes Part 11Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation? The equipment must be reinspected by the AHJ only The equipment shall be evaluated and approved by the original manufacturer The equipment may be reused if insulation resistance tests pass The equipment shall be replaced unless the installer certifies it Reference:408.3 A 81. 110 – 2026 Changes Part 11In the 2026 NEC, wiring?devicetype switch requirements were relocated from Article 404 to which Article? article 406 Article 210 Article 314 Article 110 Reference:406 82. 30 – 2026 Changes Part 11Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.) Field evaluated only Listed as suitable for service only Additionally certified Listed or field evaluated Reference:230.2 B 83. 22 – 2026 Changes Part 11When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.) shall be located inside the laundry area adjacent to the door must be located outside of the laundry area can now be located outside of the laundry area shall be marked at the switch Reference:210.70 A ex 3 84. 184 – 2026 Changes Part 11Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a faults duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent ) 0.05 second 0.1 second 1.0 second 0.01 second Reference:517.42 F 85. 87 – 2026 Changes Part 11A new list item added as an approved method for supporting and securing Metal-Clad Cable (Type MC) is _________. (Designed to restrain cables from whipping during a fault condition which can cause damage.) Jacketing Blocking Cable cleats Any hangers Reference:330.30 A 86. 182 – 2026 Changes Part 11Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________. On?site and sized to supply the entire EES; either on?site or off?site On?site but sized only for the life?safety branch; on?site only Off?site; off?site only Off?site and sized to supply the entire EES; on?site only Reference:517.41 A 87. 136 – 2026 Changes Part 11According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following? 115% of the generator nameplate current rating 125% of the generator nameplate current rating 80% of the generator nameplate current rating 100% of the generator nameplate current rating under all conditions Reference:445.13 88. 187 – 2026 Changes Part 11Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code ) . Each source must have an isolated equipment grounding conductor The equipment grounding conductors of all sources must be bonded together at the portable structure using a copper bonding conductor sized per Table 250.122 Bonding is optional if all generators are rated less than 15 kW Only the largest source must be bonded to the structures grounding electrode Reference:525.12 89. 83 – 2026 Changes Part 11Armored Cable is now required to be supported with approved and listed _________. (Non listed devices can degrade with time under heat.) Hangers only Straps only Staples 2 hole straps only Reference:320.2 90. 17 – 2026 Changes Part 11If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.) 15 amperes 10 amperes 12 amperes 8 amperes Reference:Table 210.24(2) 91. 133 – 2026 Changes Part 11Heat strips installed inside HVAC enclosures shall be________. (This change was prompted by the sale and widespread reports of supply houses selling heat strips not for specific applications compromising the listing of the entire unit ) Purchased from the manufacturer of the HVAC unit being worked on Listed as a field installable accessory Inspected by the AHJ (Authority having jurisdiction ) None of these answers are correct Reference:440.2 92. 167 – 2026 Changes Part 11Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________. Inside . Only inside the dispensing device Only adjacent to the dispensing device Other than inside or adjacent to the dispensing device Reference:514.13 93. 121 – 2026 Changes Part 11A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with? Section 408.3 Support and arrangement of busbars Section 250.8 Equipment grounding conductor identification 110.21 B Identification of disconnecting means Section 90.7 Examination of equipment for safety Reference:408.10 F 94. 73 – 2026 Changes Part 11When raceways are installed in a wet location above grade level they now shall _______. (Moisture accumulation can be an issue in environments such as food processing plants, car washes, and swimming pools.) Use listed fittings that prevent condensation Be designed to drain Be nonmetallic Have drip loops Reference:300.11 B 95. 93 – 2026 Changes Part 11There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.) Five times the major diameter dimension can be used. Three times the major diameter dimension is recommended. Five times the minor diameter dimension can be used. Three times the minor diameter dimension is allowed. Reference:338.24 96. 77 – 2026 Changes Part 11The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.) Considered as current carrying but does not need to be counted Counted unless under engineering supervision Not considered as current carrying Considered as current carrying and shall be counted Reference:310.15 E 97. 197 – 2026 Changes Part 11Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements ) GFCI protection must be provided as required in 210.8 GFCI protection is optional if the receptacle is within sight of the panelboard Receptacle outlets must be GFCI?protected only when installed in bathrooms Only outdoor receptacles require GFCI protection Reference:550.13 B 98. 7 – 2026 Changes Part 11As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.) 70 amperes or less 80 amperes or less 60 amperes or less 100 amperes or less Reference:210.8 F 99. 163 – 2026 Changes Part 11Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted. Class II Class I Unclassified locations only Reference:512.21 100. 106 – 2026 Changes Part 11When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following? The floor or working platform . The nearest doorway The top of the equipment enclosure The ceiling height Reference:404.10 A 2 Back Save Progress Retry Finish