2026 Changes Part 1- OR Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 183 – 2026 Changes Part 1

    1
    The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content )
    Reference:517.42 A
  2. 2. 173 – 2026 Changes Part 1

    1
    Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads )
    Reference:517.15
  3. 3. 141 – 2026 Changes Part 1

    1
    According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”)
    Reference:460.3
  4. 4. 97 – 2026 Changes Part 1

    1
    A new mandate requires that when a raceway such as IMC with threads enters an enclosure, a locknut or fitting ______ be installed on the inside and outside of the enclosure. (This rule was buried in the bonding and grounding section so was sometimes not installed as required.)
    Reference:342.29
  5. 5. 98 – 2026 Changes Part 1

    1
    A revised section for cable trays now requires a minimum space of ________ above the cable tray for access unless an exception is met. (In many commercial, industrial, and data centers these trays can become very congested.)
    Reference:392.18 F
  6. 6. 35 – 2026 Changes Part 1

    1
    In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.)
    Reference:230.70 D
  7. 7. 18 – 2026 Changes Part 1

    1
    A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.)
    Reference:210.52 A2(1)
  8. 8. 4 – 2026 Changes Part 1

    1
    Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.)
    Reference:210.8 A
  9. 9. 121 – 2026 Changes Part 1

    1
    A new NEC revision adds requirements for identification and labeling of switchboards, switchgear, and panelboards. Under this revision, which section must these assemblies comply with?
    Reference:408.10 F
  10. 10. 188 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525?
    Reference:525.21 A
  11. 11. 195 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments )
    Reference:547.44 B
  12. 12. 102 – 2026 Changes Part 1

    1
    A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switches—such as snap switches, dimmers, and electronic controls—were moved to Article 406 as part of a structural reorganization.)
    Reference:404.1 B
  13. 13. 6 – 2026 Changes Part 1

    1
    An exception for Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for an industrial establishment requires _________. (The electrical industry has been complaining about overapplication of GFCI requirements; this revision reflects that.)
    Reference:210.8 B ex 2
  14. 14. 9 – 2026 Changes Part 1

    1
    When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.)
    Reference:210.8 F ex 3
  15. 15. 99 – 2026 Changes Part 1

    1
    Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.)
    Reference:392.22 B
  16. 16. 7 – 2026 Changes Part 1

    1
    As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.)
    Reference:210.8 F
  17. 17. 178 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________.
    Reference:517.30 A
  18. 18. 127 – 2026 Changes Part 1

    1
    Conductive pavement heating systems shall be designed as which of the following?
    Reference:426.64
  19. 19. 126 – 2026 Changes Part 1

    1
    Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that )
    Reference:422.13
  20. 20. 54 – 2026 Changes Part 1

    1
    The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.)
    Reference:250.102 A
  21. 21. 109 – 2026 Changes Part 1

    1
    According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment )
    Reference:406.3
  22. 22. 149 – 2026 Changes Part 1

    1
    Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences )
    Reference:495.26
  23. 23. 69 – 2026 Changes Part 1

    1
    Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.)
    Reference:300.6 E
  24. 24. 77 – 2026 Changes Part 1

    1
    The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.)
    Reference:310.15 E
  25. 25. 144 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded)
    Reference:480.8
  26. 26. 52 – 2026 Changes Part 1

    1
    A grounding electrode conductor ________ through ventilation, mounting slots, or weep holes of an enclosure like a transformer. (To address a common misapplication in the field risking mechanical damage to the GEC, affecting water drainage, and GEC support.)
    Reference:250.64 G
  27. 27. 60 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.)
    Reference:265.63 B
  28. 28. 131 – 2026 Changes Part 1

    1
    Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following?
    Reference:430.3
  29. 29. 78 – 2026 Changes Part 1

    1
    In the ampacity tables, the temperature rating of conductor type XHWN has been changed and it now sits in the _________ column of the table. (An example of a correction because XHWN was in the wrong column in previous code cycles.)
    Reference:310.16
  30. 30. 118 – 2026 Changes Part 1

    1
    Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation?
    Reference:408.3 A
  31. 31. 190 – 2026 Changes Part 1

    1
    Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does )
    Reference:525.22
  32. 32. 137 – 2026 Changes Part 1

    1
    If overcurrent protection is not provided at the generator, conductors from generator to the first overcurrent protective device must have an ampacity of at least_________. (This requirement accounts for possible operational overloads or transient surges )
    Reference:445.13
  33. 33. 125 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit?
    Reference:422.12
  34. 34. 22 – 2026 Changes Part 1

    1
    When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.)
    Reference:210.70 A ex 3
  35. 35. 143 – 2026 Changes Part 1

    1
    Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations )
    Reference:480.1
  36. 36. 115 – 2026 Changes Part 1

    1
    Receptacles shall not be installed in a face?up position in which of the following locations? (The NEC prohibits installing receptacles face?up on work surfaces because liquids can spill directly into the device,debris can fall into the openings and It creates a shock and contamination hazard)
    Reference:406.14 G
  37. 37. 175 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 )
    Reference:517.26
  38. 38. 179 – 2026 Changes Part 1

    1
    Power sources for the Essential Electrical System (EES) shall be one or more of the following: (These updates ensure that both on site and off site power sources are designed for sufficient reliability to support the faculties emergency operation plan )
    Reference:517.30 B
  39. 39. 20 – 2026 Changes Part 1

    1
    As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.)
    Reference:210.52 C4
  40. 40. 37 – 2026 Changes Part 1

    1
    The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.)
    Reference:230.71 A
  41. 41. 76 – 2026 Changes Part 1

    1
    A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.)
    Reference:310.5 A
  42. 42. 171 – 2026 Changes Part 1

    1
    Part II of Article 517 applies to which of the following?
    Reference:517.10 A
  43. 43. 12 – 2026 Changes Part 1

    1
    ___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.)
    Reference:210.17
  44. 44. 145 – 2026 Changes Part 1

    1
    According to 2026 NEC what provision must be included in stationary battery installations to prevent damage and hazards?( this updates battery safety requirement , to control Thermal runaway especially in lithium-ion chemistry , gas buildup inventing in lead acid and nickel cadium systems , swelling, fire, or explosions and to keep battery life at its maximum )
    Reference:480.14
  45. 45. 168 – 2026 Changes Part 1

    1
    In addition to the off?site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities )
    Reference:517.4
  46. 46. 39 – 2026 Changes Part 1

    1
    The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.)
    Reference:230.82
  47. 47. 128 – 2026 Changes Part 1

    1
    The NEC requirement for listing in Article 424 has been expanded in the 2026 edition to include which of the following?
    Reference:424.2
  48. 48. 44 – 2026 Changes Part 1

    1
    Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.)
    Reference:242.3
  49. 49. 104 – 2026 Changes Part 1

    1
    When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General?use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices )
    Reference:404.3 B
  50. 50. 124 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment?
    Reference:422.12 ex.#1
  51. 51. 142 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors?
    Reference:470.3 A B
  52. 52. 83 – 2026 Changes Part 1

    1
    Armored Cable is now required to be supported with approved and listed _________. (Non listed devices can degrade with time under heat.)
    Reference:320.2
  53. 53. 154 – 2026 Changes Part 1

    1
    The 2026 NEC requires which of the following bonding methods for normally non–current?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations?
    Reference:500.3
  54. 54. 63 – 2026 Changes Part 1

    1
    New NEC Article 268 covers services over 1000 volts AC or 1500 volts DC and acknowledges that supervised installations can have grounding and bonding designed by _______. (A formal introduction of customized conductor sizing for high voltage systems.)
    Reference:268.42 C
  55. 55. 80 – 2026 Changes Part 1

    1
    Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.)
    Reference:314.2
  56. 56. 56 – 2026 Changes Part 1

    1
    Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.)
    Reference:250.119 A2
  57. 57. 67 – 2026 Changes Part 1

    1
    A new NEC section identifies conductors that are considered damaged and now would require replacement including _________. (This damage can compromise insulation ratings and cause short circuits.)
    Reference:300.4 C
  58. 58. 75 – 2026 Changes Part 1

    1
    A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.)
    Reference:300.24
  59. 59. 157 – 2026 Changes Part 1

    1
    Section 501.3(B) of the 2026 NEC is ____________.
    Reference:501.3 B
  60. 60. 81 – 2026 Changes Part 1

    1
    Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.)
    Reference:314.16 B
  61. 61. 163 – 2026 Changes Part 1

    1
    Where cannabis oil booths are provided with a gas detection system installed in accordance with 500.7(K) or 505.8(I), electrical equipment listed for __________ shall be permitted.
    Reference:512.21
  62. 62. 8 – 2026 Changes Part 1

    1
    For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.)
    Reference:210.8 F ex 3
  63. 63. 187 – 2026 Changes Part 1

    1
    Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code )
    Reference:525.12
  64. 64. 112 – 2026 Changes Part 1

    1
    A non–grounding?type receptacle with no grounding conductor present may be replaced with which of the following?
    Reference:406.12 D 1
  65. 65. 130 – 2026 Changes Part 1

    1
    A key update in Article 430 of the 2026 NEC consists of officially recognizing which motor designs throughout the article? (These motors are very efficient and introduce new ways to calculate lock rotor current and properly sized circuit parts )
    Reference:Recognition throughout article 430
  66. 66. 71 – 2026 Changes Part 1

    1
    Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.)
    Reference:300.7 D3
  67. 67. 136 – 2026 Changes Part 1

    1
    According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following?
    Reference:445.13
  68. 68. 152 – 2026 Changes Part 1

    1
    According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments )
    Reference:500.5
  69. 69. 2 – 2026 Changes Part 1

    1
    New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.)
    Reference:206.1
  70. 70. 79 – 2026 Changes Part 1

    1
    A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.)
    Reference:312.3
  71. 71. 21 – 2026 Changes Part 1

    1
    The requirement for a receptacle to serve electrical equipment for servicing and maintenance activities has been revised __________.
    Reference:210.63 B
  72. 72. 123 – 2026 Changes Part 1

    1
    The NEC restructuring of horticultural lighting into Sections (A) and (B) is based on which voltage threshold?
    Reference:410.184 A B
  73. 73. 134 – 2026 Changes Part 1

    1
    If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened?
    Reference:440.11
  74. 74. 196 – 2026 Changes Part 1

    1
    The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings )
    Reference:547.44 C
  75. 75. 85 – 2026 Changes Part 1

    1
    New listing requirements for Metal-Clad Cable (Type MC) now requires ________ to be listed and identified for use. (Based on the UL standard 2239 for safety of hardware.)
    Reference:330.2
  76. 76. 59 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.)
    Reference:265.20 A
  77. 77. 93 – 2026 Changes Part 1

    1
    There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.)
    Reference:338.24
  78. 78. 100 – 2026 Changes Part 1

    1
    Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.)
    Reference:393.14 A
  79. 79. 30 – 2026 Changes Part 1

    1
    Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.)
    Reference:230.2 B
  80. 80. 176 – 2026 Changes Part 1

    1
    A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement?
    Reference:517.28 A ex.
  81. 81. 191 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting )
    Reference:525.25 A B
  82. 82. 27 – 2026 Changes Part 1

    1
    Outside feeders to one- and two-family dwelling units required a disconnect and an emergency disconnect, a clarification states ______. (Meant to reduce added costs and complexity with simple structures like residential workshops and detached garages.)
    Reference:225.31 A, 4 1
  83. 83. 108 – 2026 Changes Part 1

    1
    In the electrical trade, the term wiring devices commonly refers to which of the following?
    Reference:Article 406 and Definitions
  84. 84. 50 – 2026 Changes Part 1

    1
    A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.)
    Reference:250.64 D1
  85. 85. 26 – 2026 Changes Part 1

    1
    NEC Article 225 covering outside branch circuits or feeders _______ the requirements in Article 210 covering inside branch circuits and Article 215 which convers inside feeders. (This clarification should help installers not to assume that only Article 225 applies to installations.)
    Reference:225.1 Note 2
  86. 86. 160 – 2026 Changes Part 1

    1
    According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________.
    Reference:511.10 B
  87. 87. 88 – 2026 Changes Part 1

    1
    For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.)
    Reference:332.2
  88. 88. 84 – 2026 Changes Part 1

    1
    __________ are a securing method for Armored Cable that was added to the list of items that shall be listed and identified. (Improper fastening over the long term can cause damage to the conductor insulation.)
    Reference:320.30 A
  89. 89. 32 – 2026 Changes Part 1

    1
    A recent section change requiring barriers to protect contact to service terminals has been revised to require that these barriers be ______. (To help protect from shock or arc-flush hazards during maintenance or troubleshooting.)
    Reference:230.62 C
  90. 90. 64 – 2026 Changes Part 1

    1
    For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.)
    Reference:268.91 B
  91. 91. 65 – 2026 Changes Part 1

    1
    The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.)
    Reference:270.20 C
  92. 92. 5 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.)
    Reference:210.8 B
  93. 93. 181 – 2026 Changes Part 1

    1
    When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service?
    Reference:517.30 F 1
  94. 94. 193 – 2026 Changes Part 1

    1
    Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.)
    Reference:530.2
  95. 95. 40 – 2026 Changes Part 1

    1
    Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.)
    Reference:230.95
  96. 96. 177 – 2026 Changes Part 1

    1
    A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state?
    Reference:517.28 B
  97. 97. 36 – 2026 Changes Part 1

    1
    The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.)
    Reference:230.70 F
  98. 98. 49 – 2026 Changes Part 1

    1
    Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation…does that include burial?)
    Reference:250.64 C
  99. 99. 47 – 2026 Changes Part 1

    1
    The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.)
    Reference:250.4 A5
  100. 100. 110 – 2026 Changes Part 1

    1
    In the 2026 NEC, wiring?device–type switch requirements were relocated from Article 404 to which Article?
    Reference:406