2026 Changes Part 1- WA Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 142 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors?
    Reference:470.3 A B
  2. 2. 195 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments )
    Reference:547.44 B
  3. 3. 190 – 2026 Changes Part 1

    1
    Electrical wiring for lighting installed inside tents and concessions must be installed in which of the following ways?(Arco 525 previously addressed many aspects of temporary outdoor installations GFCI protection flexible cords and overcurrent devices it did not specifically address wiring inside tenant enclosures and concessions where conditions differ significantly but now it does )
    Reference:525.22
  4. 4. 165 – 2026 Changes Part 1

    1
    All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one )
    Reference:513.8
  5. 5. 4 – 2026 Changes Part 1

    1
    Ground-Fault Circuit Interrupter Protection (GFCI) requirements for dwelling units were additionally modified and separated to include ____________. (The intention was to clean up the 2023 language, which was considered confusing.)
    Reference:210.8 A
  6. 6. 156 – 2026 Changes Part 1

    1
    Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations?
    Reference:501.3
  7. 7. 144 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded)
    Reference:480.8
  8. 8. 149 – 2026 Changes Part 1

    1
    Which of the following correctly describes the requirements for grounding switches used in medium? and high?voltage equipment?(This new section brings clarity and structure to the application by mandating key safeguards that help prevent accidental energization or unsafe switching sequences )
    Reference:495.26
  9. 9. 10 – 2026 Changes Part 1

    1
    Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.)
    Reference:210.12 E
  10. 10. 74 – 2026 Changes Part 1

    1
    When cable ties are used as support for flexible conduit and tubing they shall be listed and identified for that purpose such as ________. (The 2023 edition of the NEC officially allowed the use of cable ties for cable systems.)
    Reference:300.13 E
  11. 11. 29 – 2026 Changes Part 1

    1
    The NEC requirement to list service equipment as suitable as service has been consolidated into a list format and now includes _________. (An increasing emphasis on listing ensuring product safety through third party certification. AVTs are used to verify that circuits are de-energized.)
    Reference:230.2 A
  12. 12. 8 – 2026 Changes Part 1

    1
    For a dwelling unit outdoor outlet replacement for listed HVAC equipment, _____________. (This should help this industry with unwanted tripping because standard GFCIs were incompatible.)
    Reference:210.8 F ex 3
  13. 13. 47 – 2026 Changes Part 1

    1
    The NEC essential general requirements for grounding and bonding have been restructured to provide a clear list format, restating clearly that the earth shall not be ________. (Previously this section was in one single dense paragraph. This formatting change should be helpful to all stakeholders.)
    Reference:250.4 A5
  14. 14. 119 – 2026 Changes Part 1

    1
    According to the NEC, which of the following types of equipment is not permitted to be reconditioned?
    Reference:408,3 B
  15. 15. 175 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the requirements of Article 700 shall NOT apply to which of the following?(This change addresses the impracticality of applying article 700 to all components of the electrical essentials system the change emphasizes only life safety branch of the essential electrical system must comply with 700 )
    Reference:517.26
  16. 16. 55 – 2026 Changes Part 1

    1
    A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.)
    Reference:250.109 B2
  17. 17. 22 – 2026 Changes Part 1

    1
    When a laundry area is located inside a closet or compact enclosure, both the lighting outlet and the control device _________. (To reflect common small laundry rooms such as in multifamily applications.)
    Reference:210.70 A ex 3
  18. 18. 103 – 2026 Changes Part 1

    1
    When using reconditioned switches, not all types are permitted to be installed. Which type is permitted under the 2026 National Electrical Code?
    Reference:404.3
  19. 19. 24 – 2026 Changes Part 1

    1
    A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.)
    Reference:215.10 B
  20. 20. 188 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525?
    Reference:525.21 A
  21. 21. 126 – 2026 Changes Part 1

    1
    Fixed storage type water heaters 120 gallons or less are now classified as ? (Finally, clarity sometimes we need that )
    Reference:422.13
  22. 22. 140 – 2026 Changes Part 1

    1
    A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision?
    Reference:450.3
  23. 23. 5 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements for non-dwelling units clarified ___________ such as an aquarium is required where receptacles are installed within 6 feet. (Revised to reduce confusion and possible unnecessary installation of GFCI protection.)
    Reference:210.8 B
  24. 24. 181 – 2026 Changes Part 1

    1
    When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service?
    Reference:517.30 F 1
  25. 25. 158 – 2026 Changes Part 1

    1
    In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed )
    Reference:501.1
  26. 26. 80 – 2026 Changes Part 1

    1
    Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.)
    Reference:314.2
  27. 27. 185 – 2026 Changes Part 1

    1
    Diagnostic imaging and treatment equipment shall be installed in accordance with which portion of the NEC?(The 2026 NEC revision clarifies and expands the scope of part five vertical 517 by stating that it applies to all diagnostic imaging and treatment equipment not just x-ray systems )
    Reference:517.7
  28. 28. 62 – 2026 Changes Part 1

    1
    The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.)
    Reference:267.1
  29. 29. 153 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay )
    Reference:500.8 G
  30. 30. 182 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________.
    Reference:517.41 A
  31. 31. 164 – 2026 Changes Part 1

    1
    According to the 2026 NEC, reconditioned equipment permitted to be installed in Zone?classified locations shall comply with the requirements of __________.
    Reference:513.3 A
  32. 32. 155 – 2026 Changes Part 1

    1
    Which of the following bonding methods is not permitted for normally non–current?carrying metal parts in hazardous classified locations?(Vision grounding and bonding requirements for hazardous locations were found in three different locations )
    Reference:500.30 B
  33. 33. 148 – 2026 Changes Part 1

    1
    According to 2026 which of the following correctly describes the requirements for isolating means used to completely isolate equipment from all ungrounded conductors (other than service conductors)?
    Reference:495.22
  34. 34. 170 – 2026 Changes Part 1

    1
    All activities, systems, and equipment that are new or altered in patient care spaces shall be designed and installed to meet the requirements of which of the following?(NFPA 99 category 1 failure likely to cause major injury or death category two failure could cause minor injury category three failure unlikely to cause injury but may cause discomfort category 4 failure has no impact on safety or care )
    Reference:517.7 & Informational note
  35. 35. 118 – 2026 Changes Part 1

    1
    Switchboards and switchgear are permitted to be reconditioned if damaged by fire. According to the NEC, what condition must be met before reinstallation?
    Reference:408.3 A
  36. 36. 167 – 2026 Changes Part 1

    1
    Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________.
    Reference:514.13
  37. 37. 151 – 2026 Changes Part 1

    1
    What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment )
    Reference:article495 parts VI andVII
  38. 38. 131 – 2026 Changes Part 1

    1
    Reconditioned motors are permitted to be installed only if the reconditioning has been performed in accordance with which of the following?
    Reference:430.3
  39. 39. 20 – 2026 Changes Part 1

    1
    As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.)
    Reference:210.52 C4
  40. 40. 160 – 2026 Changes Part 1

    1
    According to the NEC, electrical equipment and wiring for electric vehicle power transfer systems shall be installed in accordance with Article 625 Part III, except as modified by 511.10(B)(2) and 511.10(B)(3). Flexible cords used in these systems shall be __________.
    Reference:511.10 B
  41. 41. 113 – 2026 Changes Part 1

    1
    Non grounding type receptacles with no grounding conductor present can be replaced with_______.
    Reference:406.12 D 1
  42. 42. 88 – 2026 Changes Part 1

    1
    For Mineral-Insulated, Metal-Sheathed Cable (Type MI) the _________ is not required to be listed and identified. (There is an increasing demand for these systems’ reliability and safety.)
    Reference:332.2
  43. 43. 122 – 2026 Changes Part 1

    1
    Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following?
    Reference:410.184
  44. 44. 44 – 2026 Changes Part 1

    1
    Surge protective devices (SPDs) and surge arresters used for critical overvoltage protection ________. (This change brings SPD in line with other NEC code sections.)
    Reference:242.3
  45. 45. 60 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC that can require servicing, a 125 volt single phase 15- or 20-ampere receptacle outlet shall be available __________. (Generally the receptacle shall not be powered from the load side of the equipment.)
    Reference:265.63 B
  46. 46. 169 – 2026 Changes Part 1

    1
    Additional sources of electrical service permitted to supplement the utility service in healthcare facilities shall have the capacity and rating to meet the maximum actual demand likely to be produced by the connected load. Demand calculations for sizing these systems shall be based on one or more of the following EXCEPT __________.
    Reference:517.4 B
  47. 47. 2 – 2026 Changes Part 1

    1
    New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.)
    Reference:206.1
  48. 48. 143 – 2026 Changes Part 1

    1
    Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations )
    Reference:480.1
  49. 49. 12 – 2026 Changes Part 1

    1
    ___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.)
    Reference:210.17
  50. 50. 90 – 2026 Changes Part 1

    1
    Nonmetallic-Sheathed Cable (Types NM and NMC, Romex) now requires listed products such as _______ be used during installation. (One of the most widely used wiring methods can be damaged by sharp edges or improper sizing.)
    Reference:334.2
  51. 51. 187 – 2026 Changes Part 1

    1
    Where multiple services or separately derived systems supply a portable structure and the sources are separated by less than 3.7 m (12 ft), which of the following is REQUIRED?(Generators are commonly used in these types of areas due to limited or inaccessible permelectrical infrastructure and this new language establishes clear consolidated requirements for grounding and protection that was previously all over other sections in the National Electric Code )
    Reference:525.12
  52. 52. 9 – 2026 Changes Part 1

    1
    When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.)
    Reference:210.8 F ex 3
  53. 53. 138 – 2026 Changes Part 1

    1
    According to 2026 NEC when a generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors are permitted to be tapped from the load side of the protected terminals under which condition?
    Reference:445.13 B
  54. 54. 114 – 2026 Changes Part 1

    1
    On work surfaces, receptacles shall not be installed in a face?up position unless which condition is met?
    Reference:406.14 G
  55. 55. 171 – 2026 Changes Part 1

    1
    Part II of Article 517 applies to which of the following?
    Reference:517.10 A
  56. 56. 92 – 2026 Changes Part 1

    1
    Nonmetallic-Sheathed Cable (Type NM and NMC, Romex) shall not officially be used _________. (Prior editions of the NEC did not specifically prohibit this.)
    Reference:334.12
  57. 57. 71 – 2026 Changes Part 1

    1
    Wording was changed to clarify that ________ direct buried conductors and raceways buried at least 18 inches shall have their location identified by a warning label. (It was a common misconception that this rule only applied to directly buried conductors and not also buried raceways.)
    Reference:300.7 D3
  58. 58. 199 – 2026 Changes Part 1

    1
    Which of the following is TRUE regarding service equipment for a mobile home under Article 550?
    Reference:550.51
  59. 59. 50 – 2026 Changes Part 1

    1
    A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.)
    Reference:250.64 D1
  60. 60. 141 – 2026 Changes Part 1

    1
    According to 2026 NEC why are reconditioned capacitors not permitted to be installed?(The 2026 NEC introduces a new provision ,reconditioning which makes a Definitive and safety driven statement” reconditioned capacitors must not be installed”)
    Reference:460.3
  61. 61. 116 – 2026 Changes Part 1

    1
    Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet?
    Reference:406.16 D
  62. 62. 125 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit?
    Reference:422.12
  63. 63. 79 – 2026 Changes Part 1

    1
    A new section now clearly states that _________ cannot be reconditioned and installed. (Seems to come up more frequently now as our electrical equipment ages and natural disasters occur.)
    Reference:312.3
  64. 64. 93 – 2026 Changes Part 1

    1
    There was a change for Service Entrance Cables (SE and USE) to allow relief for flat cables when bent on the flat side of the cable. _______________. (these flat versions are very common in residential applications.)
    Reference:338.24
  65. 65. 3 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards.
    Reference:210.8 A
  66. 66. 186 – 2026 Changes Part 1

    1
    Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential)
    Reference:525.1
  67. 67. 100 – 2026 Changes Part 1

    1
    Terminology for Low-Voltage Suspended Ceiling Power Distribution Systems was replaced, now requiring that all components shall be _________. (Careful installation is needed to avoid damage or fire risks for these increasingly common systems.)
    Reference:393.14 A
  68. 68. 7 – 2026 Changes Part 1

    1
    As a general rule, in dwelling units, outdoor circuits rated at 150 volts or less to ground require GFCI protection for __________. (This increase addresses the trend for larger HVAC units now being installed in residential applications.)
    Reference:210.8 F
  69. 69. 176 – 2026 Changes Part 1

    1
    A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement?
    Reference:517.28 A ex.
  70. 70. 96 – 2026 Changes Part 1

    1
    For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.)
    Reference:342.14
  71. 71. 30 – 2026 Changes Part 1

    1
    Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.)
    Reference:230.2 B
  72. 72. 36 – 2026 Changes Part 1

    1
    The NEC clarified that a remote control device a service disconnect ____ as the service disconnect itself is meeting those requirements (such as push buttons, relay circuits, or wireless controllers.)
    Reference:230.70 F
  73. 73. 61 – 2026 Changes Part 1

    1
    New Article 266 covers feeders over 1000 volts AC or 1500 volts DC. The concept of “supervised installations” was added and permits a reduction in standard conductor sizing. The work of a supervised installation must be performed by ________. (The NEC is working to accommodate these unique high voltage systems.)
    Reference:266.4 C
  74. 74. 66 – 2026 Changes Part 1

    1
    A revision to Chapter 3 also now clearly shows what is not covered and includes ________ (to give a clear explanation and framework for compliance and installation.)
    Reference:300.1
  75. 75. 89 – 2026 Changes Part 1

    1
    The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.)
    Reference:332.3
  76. 76. 101 – 2026 Changes Part 1

    1
    There is a significant change to the scope of NEC article 404 by including __________.
    Reference:404.1 A
  77. 77. 192 – 2026 Changes Part 1

    1
    Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception )
    Reference:525.31
  78. 78. 183 – 2026 Changes Part 1

    1
    The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content )
    Reference:517.42 A
  79. 79. 193 – 2026 Changes Part 1

    1
    Which of the following equipment used in motion picture and television studios and remote locations is REQUIRED to be listed under Article 530?(These listing requirements ensure that all portable power and lighting equipment used in production environments meets tested safety standards, especially where temporary wiring, high?intensity lighting, and rapid setup/teardown create elevated hazards.)
    Reference:530.2
  80. 80. 135 – 2026 Changes Part 1

    1
    According to 2026 NEC the outdoor disconnecting means for a split?system HVAC unit in other than one? and two?family dwellings must be marked with which of the following?
    Reference:440.15
  81. 81. 200 – 2026 Changes Part 1

    1
    Service equipment is permitted to be installed in or on a manufactured home only if which condition is met?
    Reference:550.51 B 1-7
  82. 82. 95 – 2026 Changes Part 1

    1
    Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.)
    Reference:342.10 B
  83. 83. 65 – 2026 Changes Part 1

    1
    The NEC created Article 270 to cover grounding and bonding for systems over 1000 volts AC or 1500 volts DC. Grounding for systems _________ is now also covered. (These systems can be specialized with increased risk of ground touch potential.)
    Reference:270.20 C
  84. 84. 33 – 2026 Changes Part 1

    1
    Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.)
    Reference:230.70 B
  85. 85. 106 – 2026 Changes Part 1

    1
    When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following?
    Reference:404.10 A 2
  86. 86. 99 – 2026 Changes Part 1

    1
    Updated language for cable trays now allows ________ rated 2000 volts or less in the trays. (The terminology “evenly distributed across the cable tray” was eliminated, replacing it with conductor count and size. That term was used to encourage proper heat dissipation but it was hard to enforce.)
    Reference:392.22 B
  87. 87. 108 – 2026 Changes Part 1

    1
    In the electrical trade, the term wiring devices commonly refers to which of the following?
    Reference:Article 406 and Definitions
  88. 88. 178 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________.
    Reference:517.30 A
  89. 89. 105 – 2026 Changes Part 1

    1
    Article 404 requires switches to be installed in easily accessible locations. What is the maximum permitted height to the center of the grip of the operating handle when the switch is in its highest position?
    Reference:404.10 A 2
  90. 90. 25 – 2026 Changes Part 1

    1
    Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.)
    Reference:215.18 A
  91. 91. 184 – 2026 Changes Part 1

    1
    Overcurrent protective devices serving the Essential Electrical System (EES) must be coordinated for the period of time that a fault’s duration extends beyond which of the following?(The addition of subsection F is a critical enhancement to the National Electric Code in 2026 as it addresses the need for precise coordination of over current protective devices in EES ‘s. This author thinks precise coordination is needed in all applications, who wants a main fuse blowing or circuit breaker turning off everything that you are addressing in whichever system you’re addressing? Life safety of course is more urgent )
    Reference:517.42 F
  92. 92. 111 – 2026 Changes Part 1

    1
    In the 2026 NEC, the new code section for wiring devices is reorganized into how many distinct parts? (The new layout breaks the material into **three clearly separated parts**, making it easier to distinguish:

    – **Wiring?device–type switches**
    – **Receptacles and cord connectors**
    – **Attachment plugs (caps)** )

    Reference:406
  93. 93. 11 – 2026 Changes Part 1

    1
    Branch-circuit disconnecting means rated 1000 amperes or more, solidly grounded, but not exceeding ____ volts line to line now mandates GFCI protection even for DC systems. (The NEC is trying to keep up with the increased usage of DC power such as in data centers, EV charging, energy storage systems, and large scale solar.)
    Reference:210.13 A&B
  94. 94. 110 – 2026 Changes Part 1

    1
    In the 2026 NEC, wiring?device–type switch requirements were relocated from Article 404 to which Article?
    Reference:406
  95. 95. 162 – 2026 Changes Part 1

    1
    Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies?
    Reference:512.6
  96. 96. 132 – 2026 Changes Part 1

    1
    Motor control centers supplied by a feeder shall be marked in accordance with which section to identify the location of all means necessary to disconnect power to the motor control center?
    Reference:430.98 A
  97. 97. 40 – 2026 Changes Part 1

    1
    Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.)
    Reference:230.95
  98. 98. 191 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for lighting installed inside tents, concessions, and similar temporary structures?(Including section 525.25 in the 2026 NEC aims to improve safety . Carnivals circuses fairs and similar outdoor events temporary wiring and lighting system are used often. the 2026 NEC has made two sections with new requirements lamp protection and luminaries for egress lighting )
    Reference:525.25 A B
  99. 99. 180 – 2026 Changes Part 1

    1
    An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance )
    Reference:517.30 E 4
  100. 100. 51 – 2026 Changes Part 1

    1
    In an enhancement to the grounding and bonding rules the NEC has added ________ to the list of raceways that shall be bonded at both ends if it contains a grounding electrode conductor. (Nonferrous metals like aluminum do not produce significant magnetic properties or heat so do not create the same risk during a fault condition.)
    Reference:250.64 E1
Back