  1. 1. 30 – 2026 Changes Part 1

    1
    Service equipment beyond what is specified in 230.2 A shall be _______. (With the changing times, service equipment may need to be modified or custom-built in the field.)
    Reference:230.2 B
  2. 2. 180 – 2026 Changes Part 1

    1
    An EES that uses a single on?site power source must include a permanent switching means to connect a portable or temporary on?site power source. Which of the following is REQUIRED?(Temporary power source connection refers to an intern power source used in the primary power source is unavailable or during maintenance )
    Reference:517.30 E 4
  3. 3. 86 – 2026 Changes Part 1

    1
    A new exception was added for Metal-Clad Cable (Type MC) with ________ which is now permitted in a damp or wet location. (These resist oxidation and galvanic corrosion effectively.)
    Reference:330.10 A
  4. 4. 194 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED when multiple relocatable structure sections are physically connected together?(This update Provides much needed clarity for grounding relocatable structures by confirming the grounding electrode systems are not required aligning practice with that for mobile and manufactured homes )
    Reference: 545.20 D 545.26
  5. 5. 55 – 2026 Changes Part 1

    1
    A new NEC section now covers the method required to establish an effective ground fault path when installing a nonmetallic enclosure with metallic raceways. Generally, ________ metallic wiring method shall have bonding jumpers or fitting. (Although uncommon, there are specially designed and listed nonmetallic enclosures with built in metal bonding.)
    Reference:250.109 B2
  6. 6. 39 – 2026 Changes Part 1

    1
    The list that governs what equipment is allowed to be used on the supply side (line side) of service equipment has undergone a substantial re-organization and now also includes _________. (This reflects the increased demand for these to enhance safety also during maintenance.)
    Reference:230.82
  7. 7. 77 – 2026 Changes Part 1

    1
    The text in the NEC relating to when the neutral conductor should be counted as a current-carrying conductor for ampacity adjustment in raceways has been reorganized and also written into a list format. A neutral conductor that only carries the unbalanced current (linear load) from the other conductors in the same circuit is _______. (The current ratings of conductors has been evolving and changing in the NEC since the late 1800s.)
    Reference:310.15 E
  8. 8. 106 – 2026 Changes Part 1

    1
    When installing switches and circuit breakers, their highest position must not be more than 6 ft 7 in above which of the following?
    Reference:404.10 A 2
  9. 9. 153 – 2026 Changes Part 1

    1
    According to the 2026 NEC, the risk of ignition from optical radiation must be evaluated for which types of equipment when the radiation falls within the 380 nm to 10 ?m wavelength range and may enter a hazardous location?(Would you call this forward thinking? may be necessary in hazardous location safety. Lasers are here to stay )
    Reference:500.8 G
  10. 10. 171 – 2026 Changes Part 1

    1
    Part II of Article 517 applies to which of the following?
    Reference:517.10 A
  11. 11. 34 – 2026 Changes Part 1

    1
    There are now enhanced marking requirements for one- and two-family residential service disconnects and specifically state that the marking ______. (Some state rules also have additional requirements.)
    Reference:230.70 B2
  12. 12. 127 – 2026 Changes Part 1

    1
    Conductive pavement heating systems shall be designed as which of the following?
    Reference:426.64
  13. 13. 12 – 2026 Changes Part 1

    1
    ___________ that include cooking facilities which have permanent provisions for cooking shall now meet the kitchen small applicance branch circuit AFCI and GFCI requirements of dwelling units. (Previously only guest rooms and suites in hotels or motels were required.)
    Reference:210.17
  14. 14. 23 – 2026 Changes Part 1

    1
    Automatic controls like motion sensors or time based controllers ________ as the sole means of controlling illumination in attics, underfloor spaces, and utility rooms. (To ensure that we are not left stranded in the dark in a potentially dangerous tight space.)
    Reference:210.70 C3
  15. 15. 159 – 2026 Changes Part 1

    1
    Modification of luminaires using retrofit kits is permitted only when the retrofit kit is __________.
    Reference:501.130 C
  16. 16. 167 – 2026 Changes Part 1

    1
    Each dispensing device shall be provided with a means to remove all external voltage sources during maintenance and service. This disconnecting means shall remove ungrounded and grounded power conductors, communication, data, and video circuits. The location of this means is permitted to be __________.
    Reference:514.13
  17. 17. 24 – 2026 Changes Part 1

    1
    A new NEC provision now includes a GFPE protection requirement for DC electrical system feeders rated at ______ or more, operating at 150 volts up to 1500 volts to ground. (Energy systems such as battery energy storage systems (BESS) and efficient building power systems now often use high level DC power systems that need protection from damage and fire.)
    Reference:215.10 B
  18. 18. 40 – 2026 Changes Part 1

    1
    Ground-Fault protection of equipment shall now also be required for solidly grounded DC systems rated at ______ or more (to address the increasing direct current (DC) systems in modern electrical systems.)
    Reference:230.95
  19. 19. 196 – 2026 Changes Part 1

    1
    The construction of an equipotential plane shall comply with which NEC subsections?(This change introduces new detailed construction requirements for a quick potential planes in agricultural buildings )
    Reference:547.44 C
  20. 20. 89 – 2026 Changes Part 1

    1
    The NEC has eliminated ________ as an option for securing Mineral-Insulated (Type MI) cable. (Type MI cable is often used for fire alarms, high temperature locations, and emergency systems. It can be vulnerable to mechanical stresses during the installation.)
    Reference:332.3
  21. 21. 13 – 2026 Changes Part 1

    1
    A new exception now states that _________ individual branch circuits are not allowed to supply receptacle loads. (Because of the standard plug and receptacle ratings there would be a potential for overloading.)
    Reference:210.22 ex
  22. 22. 124 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Exception No. 1 has been expanded to include which additional type of equipment?
    Reference:422.12 ex.#1
  23. 23. 76 – 2026 Changes Part 1

    1
    A change in the new minimum size of conductors in Chapter 3 are set at ______. (These new sizes have been used for some time by manufacturers but now offically allowed for branch circuits.)
    Reference:310.5 A
  24. 24. 95 – 2026 Changes Part 1

    1
    Intermediate Metal Conduit (IMC) is permitted in areas subject to even severe corrosive influences provided they are protected by corrosion protection approved for the condition such as _______. (Some of these locations include agricultural with fertilizer exposure, wastewater facilities, coastal areas with salt environments, and industrial sites.)
    Reference:342.10 B
  25. 25. 134 – 2026 Changes Part 1

    1
    If the disconnecting means for air?conditioning or refrigerating equipment is readily accessible to unqualified persons, what requirement applies to any enclosure door or hinged cover that exposes energized parts when opened?
    Reference:440.11
  26. 26. 174 – 2026 Changes Part 1

    1
    Receptacles and fixed equipment in wet?procedure locations shall be provided with special protection against electric shock. Where GFCI protection is used, which of the following power distribution methods is permitted?(The code now prohibits the use of shared GFCI’s this means if a gfci trip occurs it should only disable the single affected receptacle or power distribution outlet not multiple )
    Reference:517.20 A 3 a b
  27. 27. 144 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following must be grounded in stationary battery installations?(This update clarifies outdated text by adding clear requirements That are very actionable :All conductive battery rack stands cabinets and cases must be grounded)
    Reference:480.8
  28. 28. 18 – 2026 Changes Part 1

    1
    A change in determining the required receptacle outlet placement in dwelling units was a revision to exclude _________ from the wall space measurements. (The purpose was to reduce the overuse of extension cords. This should simplify the task of laying out receptacle outlet locations in the home.)
    Reference:210.52 A2(1)
  29. 29. 81 – 2026 Changes Part 1

    1
    Chapter 3 addresses maximum box fill and has been revised stating ________ are not included in box fill calculations. (This now officialy clarified this long-debated issue because they physically occupied space in the box.)
    Reference:314.16 B
  30. 30. 9 – 2026 Changes Part 1

    1
    When a dwelling unit HVAC outdoor outlet is replaced and Special Purpose SPGFCI protection is used, ___________. (Special SPGFCIs marked HF are higher frequency weighted that help with inherent leakage currents like HVAC equipment which have had issues with tripping and system lockouts resulting in service calls.)
    Reference:210.8 F ex 3
  31. 31. 75 – 2026 Changes Part 1

    1
    A new section in Article 300 clarified that the 360 degree limitations on raceway bends between pulling points ______. (Before the 360 degree limitation was only mentioned in each conduit or tubing article and was not clear.)
    Reference:300.24
  32. 32. 176 – 2026 Changes Part 1

    1
    A sign must be placed at the service?entrance equipment indicating the type and location of each on?site power source. Which of the following is exempt from this signage requirement?
    Reference:517.28 A ex.
  33. 33. 19 – 2026 Changes Part 1

    1
    The residential installation of receptacle outlets on the walls of cabinets with countertops or work surfaces shall now be installed no less than _______ below that countertop. (Recent code cycles restricted the number and locations because of the large number of inuries to crumb crunchers as a result of pulling the appliance cords. Kitchen appliance cords are 2 feet long.)
    Reference:210.52 A5
  34. 34. 154 – 2026 Changes Part 1

    1
    The 2026 NEC requires which of the following bonding methods for normally non–current?carrying metal parts of electrical equipment, raceways, metal?clad cable, and metal enclosures in hazardous classified locations?
    Reference:500.3
  35. 35. 168 – 2026 Changes Part 1

    1
    In addition to the off?site utility electrical service, which of the following sources are permitted to supplement the service and supply the entire electrical load of a healthcare facility, based on reliability?(This is great for electrical services and healthcare faculties allowing alternative and distributed energy systems such as microgids fuel cells and energy storage systems to legally supplement electrical supply this enables healthcare systems to improve reliability and energy independence beyond traditional utilities )
    Reference:517.4
  36. 36. 35 – 2026 Changes Part 1

    1
    In ___________ installations with multiple energy sources, those sources not located adjacent to the service disconnect must now be marked and identified on the plaque or directory with their location. (Many of these more common disconnects are installed in locations such as garages, sheds, basements, and rooftops.)
    Reference:230.70 D
  37. 37. 37 – 2026 Changes Part 1

    1
    The NEC section that governs the maximum number of disconnects each service can have has been revised and clarifies that ______ does not have to be counted as one of the permitted service disconnects. (There was confusion about disconnects that served as protection rather than load-serving functions.)
    Reference:230.71 A
  38. 38. 199 – 2026 Changes Part 1

    1
    Which of the following is TRUE regarding service equipment for a mobile home under Article 550?
    Reference:550.51
  39. 39. 80 – 2026 Changes Part 1

    1
    Information on electrical equipment that is required to be listed scattered throughout Chapter 3 has been relocated into one new section and now includes ________. (The term listed means a product that has been tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL or ETL.)
    Reference:314.2
  40. 40. 3 – 2026 Changes Part 1

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) requirements in dwelling units have made adjustments to include storage and work areas not intended as habitable rooms ______________. This modification is intended to decrease hazards.
    Reference:210.8 A
  41. 41. 156 – 2026 Changes Part 1

    1
    Which of the following statements correctly reflects the revised requirements for reconditioned equipment used in hazardous (classified) locations?
    Reference:501.3
  42. 42. 182 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads must be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________, and additional sources are permitted to be __________.
    Reference:517.41 A
  43. 43. 17 – 2026 Changes Part 1

    1
    If a 14 AWG Copper-Clad Aluminum Conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is ___________. (This major change is the NEC response and solution to lower power usage. Copper-Clad seems lighter and more flexible to use but more subjectable to damage. This circuit is not allowed to supply receptacle outlets.)
    Reference:Table 210.24(2)
  44. 44. 197 – 2026 Changes Part 1

    1
    Which of the following best describes the updated GFCI requirement for receptacle outlets in Article 550?(Instead of specifying certain appliances and locations in a mobile or manufactured home the language Changed to reference section 210.8 This completely removes any differences between the old mobile home requirements And stick built home requirements )
    Reference:550.13 B
  45. 45. 25 – 2026 Changes Part 1

    1
    Surge-Protection Devices (SPDs) on feeders has been expanded beyond residential occupancies to now include __________. (To safeguard electronic equipment in sleeping and living quarters such as smoke alarms.)
    Reference:215.18 A
  46. 46. 82 – 2026 Changes Part 1

    1
    Restoring and reconditioning Medium Voltage (MV 2,000 to 35,000 Volts AC) electrical equipment for re-use such as _________ is now prohibited. (MV equipment is very vulnerable to degradation. Restoring has become popular to cut costs.)
    Reference:315.3
  47. 47. 129 – 2026 Changes Part 1

    1
    Fixed outdoor electric deicing and snow?melting equipment includes which of the following?
    Reference:Article 424, 425, 426 and 427
  48. 48. 165 – 2026 Changes Part 1

    1
    All underground wiring in aircraft hangars shall comply with 513.8(A), 513.8(B), or 513.8(C). Where such wiring is located in vaults, pits, or ducts, adequate drainage shall be provided and the installation shall comply with the requirements for __________ locations.(This revised text removes the requirement to classify underground installation At aircraft hangers solely as Class one, Division one )
    Reference:513.8
  49. 49. 181 – 2026 Changes Part 1

    1
    When an EES uses more than one on?site power source, which of the following is REQUIRED when any single on?site source is disabled for service?
    Reference:517.30 F 1
  50. 50. 122 – 2026 Changes Part 1

    1
    Lighting equipment identified for horticultural use shall be supplied by outlets protected in accordance with which of the following?
    Reference:410.184
  51. 51. 10 – 2026 Changes Part 1

    1
    Whenever an existing branch-circuit wiring that now requires Arc-Fault Circuit-Interrupter Protection (AFCI) is modified, ____________. (The NEC considers this an opportunity to increase safety in older systems.)
    Reference:210.12 E
  52. 52. 125 – 2026 Changes Part 1

    1
    The NEC requires central heating equipment to be supplied by an individual branch circuit. Under the 2026 revision, which additional load is permitted on the same branch circuit?
    Reference:422.12
  53. 53. 143 – 2026 Changes Part 1

    1
    Article 480 applies to which of the following battery installations? (The term standby has been removed to clarify that requirements apply to all battery installations )
    Reference:480.1
  54. 54. 58 – 2026 Changes Part 1

    1
    The NEC created a new code section for branch circuits over 1000 volts AC that allows conductor sizing to be determined by other than the NEC tables if the installation is __________. (This acknowledges that these can be complicated systems requiring flexibility.)
    Reference:265.19 B
  55. 55. 50 – 2026 Changes Part 1

    1
    A building service with multiple disconnecting means in separate enclosures is allowed to use a common grounding electrode, with a tap to each disconnect __________. (The format also changed from a dense paragraph to the list-style because of common misapplications and inconsistent interpretations.)
    Reference:250.64 D1
  56. 56. 113 – 2026 Changes Part 1

    1
    Non grounding type receptacles with no grounding conductor present can be replaced with_______.
    Reference:406.12 D 1
  57. 57. 158 – 2026 Changes Part 1

    1
    In Class I, Division 1 locations, one or more of the wiring methods in__________ shall be used in accordance with the requirements of the sections in the reference column and with the respective wiring?method requirements applied. For example, Type P cable is permitted only in __________ industrial establishments.(This update puts the code into table form for improve usability enabling installers to more clearly determine which wiring methods are allowed )
    Reference:501.1
  58. 58. 151 – 2026 Changes Part 1

    1
    What was the purpose of adding Parts VI and VII to Article 495 in the 2026 NEC?(The 2026 NEC introduces two entirely new parts article 495 parts VI and VII , expanding coverage beyond just transformers to include other types of oil insulated medium and high voltage equipment )
    Reference:article495 parts VI andVII
  59. 59. 192 – 2026 Changes Part 1

    1
    Where must the equipment grounding conductor (EGC) be connected for a separately derived system such as a generator? (Stated an article 525 exception it reads this section 525.31 shall not apply to portable generators used in accordance with 445.20 A exception )
    Reference:525.31
  60. 60. 102 – 2026 Changes Part 1

    1
    A significant change to NEC Article 404 in the 2026 edition is: (The 2026 NEC narrows Article 404 to cover only equipment?type switches. Device?type switches—such as snap switches, dimmers, and electronic controls—were moved to Article 406 as part of a structural reorganization.)
    Reference:404.1 B
  61. 61. 104 – 2026 Changes Part 1

    1
    When using reconditioned switches, not all types are permitted to be installed. Which one is not permitted under the 2026 National Electrical Code?(General?use snap switches fall under the category of wiring devices, and the NEC explicitly prohibits reconditioning of wiring devices )
    Reference:404.3 B
  62. 62. 54 – 2026 Changes Part 1

    1
    The NEC has officially added _________ as a permissible bonding jumper type behind the traditional wire or bus conductors. (This method has been widely used in the field for some time. It is important to use listed fittings and to torque them to manufacturers’ specifications.)
    Reference:250.102 A
  63. 63. 183 – 2026 Changes Part 1

    1
    The Essential Electrical System (EES) shall be divided into which branches, and where shall the division occur when more than one transfer switch is required? (The 2026 NEC edition this section’s title was updated to essential electrical systems and the terms nursing home and limited care faculties were removed the title now better reflects its content )
    Reference:517.42 A
  64. 64. 15 – 2026 Changes Part 1

    1
    If a 16 AWG copper conductor is used to supply a branch circuit, the maximum overcurrent protection (circuit breaker) device rating is __________. (This circuit is not allowed to supply receptacle outlets.)
    Reference:Table 210.24(1)
  65. 65. 1 – 2026 Changes Part 1

    1
    A new list item now permits grounded neutral conductors sized 6 AWG and smaller with white or gray insulation to have a ________. (This should help match a neutral to the corresponding phase conductors in a raceway with other conductors. ( This has already been done in other countries.)
    Reference:200.7 A
  66. 66. 14 – 2026 Changes Part 1

    1
    In a major change, there is now a new size limitation to permit a ________ minimum size copper conductor to serve lighting outlets and exhaust fans in bathrooms and laundry rooms. (Current demand can now be relatively lower in homes with LED lighting and compact fan units are standard)
    Reference:210.24(1)
  67. 67. 186 – 2026 Changes Part 1

    1
    Article 525 of the 2026 NEC covers the installation of portable wiring and equipment for which of the following?( Revised article 525 clarify the requirements for temporary power systems in entertainment settings these changes are not only editorial but structural making the article easier to navigate implement and enforce in high risk venues ware public safety is essential)
    Reference:525.1
  68. 68. 178 – 2026 Changes Part 1

    1
    Essential electrical system (EES) loads shall be served by two or more independent sources or sets of power sources and feeders. At least one of these sources must be __________.
    Reference:517.30 A
  69. 69. 136 – 2026 Changes Part 1

    1
    According to 2026 NEC when overcurrent protection is not provided at the generator terminals, the ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall be not less than which of the following?
    Reference:445.13
  70. 70. 72 – 2026 Changes Part 1

    1
    A new option item ________ was added to address areas where raceways were subject to temperature changes that can cause condensation. (The circulation of warm area such as into a cold storage is the primary cause of condensation in raceways that can then drip into electrical enclosures.)
    Reference:300.9 A
  71. 71. 150 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following requirements applies when switchgear is installed over a combustible floor?
    Reference:495.36
  72. 72. 41 – 2026 Changes Part 1

    1
    A new section in NEC article 240 identifies what overcurrent protective devices (OCPDs) are suitable and approved for providing branch-circuit, feeder service conductors and electrical equipment including _________. (The intent was to create one location for users that identified the types of breakers and fuses that the NEC recognized.)
    Reference:240.7
  73. 73. 59 – 2026 Changes Part 1

    1
    For branch circuits over 1000 volts AC, Medium Voltage equipment shall be rated not less than ________ of the sum of all loads. (In contrast to the 80% default load rating used in low voltage applications.)
    Reference:265.20 A
  74. 74. 56 – 2026 Changes Part 1

    1
    Unless a low voltage exception is met, the NEC now has strengthened the rules for equipment grounding conductors color identification, and it affirms that a _________ cannot be used as an equipment grounding conductor. (This rule applies to field wiring only and is still common in factory-manufactured built systems like HVAC, appliances, and control panels.)
    Reference:250.119 A2
  75. 75. 173 – 2026 Changes Part 1

    1
    Branch circuits serving life?safety lighting and power circuits shall NOT be installed as which of the following?(Multi wire branch circuits are generally allowed in many types of installations however their use of life safety system pose risks especially in critical environments like hospitals for instance a single open neutral could disable multiple circuits simultaneously reliability and Redundancy are paramount for life and safety loads )
    Reference:517.15
  76. 76. 177 – 2026 Changes Part 1

    1
    A warning sign is required where removal of a grounding or bonding connection in power?source equipment would interrupt the grounding?electrode?conductor or grounded?conductor connection to another energized source. What must the sign state?
    Reference:517.28 B
  77. 77. 48 – 2026 Changes Part 1

    1
    The NEC section regarding ground rod and pipe electrodes has been revised. Burying the electrode in a trench 30 inches deep ___________. (Arguably the most common use in residential and commercial applications, this revision should clarify the previous intent.)
    Reference:250.53 A4
  78. 78. 140 – 2026 Changes Part 1

    1
    A key 2026 NEC update revises transformer overcurrent protection requirements to improve clarity and usability. Which of the following best reflects the nature of this revision?
    Reference:450.3
  79. 79. 152 – 2026 Changes Part 1

    1
    According to the 2026 NEC clarification to 500.5(D)(1), Class III, Division 1 locations include which of the following?( This adjustment brings greater clarity to the user especially in areas involving dust and fiber hazard classifications in industrial environments )
    Reference:500.5
  80. 80. 33 – 2026 Changes Part 1

    1
    Service disconnects in other than one- and two-family dwellings shall now be marked _______. (To also help reduce delays and confusion for first responders and utilities, especially with services with multiple disconnects such as solar.)
    Reference:230.70 B
  81. 81. 142 – 2026 Changes Part 1

    1
    According to 2026 NEC which of the following statements correctly describes the rules for installing reconditioned reactors and resistors?
    Reference:470.3 A B
  82. 82. 147 – 2026 Changes Part 1

    1
    According to 2026 enclosures installed in damp or wet locations must be weatherproof. For enclosures in wet locations, raceways or cables entering above the level of uninsulated live parts must use fittings listed for which type of location?(Previously in section 495.3 These requirements are now clearly presented under section 495.4 with a specific title allowing designers, installers and inspectors to identify the applicable rules for damp and what locations easily)
    Reference:495.4
  83. 83. 43 – 2026 Changes Part 1

    1
    New panelboards are not allowed in a bathroom, addition additional supplementary circuit breakers to an existing panelboard is _________. (Prior to the 1993 code cycle it was common and allowed to install panels and subpanels in homes.)
    Reference:240.24 E
  84. 84. 188 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a moving ride or amusement attraction under Article 525?
    Reference:525.21 A
  85. 85. 189 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for the disconnecting means of a non?moving attraction or portable structure such as a tent, concession, inflatable, or slide?
    Reference:525.21 B
  86. 86. 120 – 2026 Changes Part 1

    1
    As a general rule (disregarding exceptions), only which of the following conductors are permitted to be located within a switchboard or switchgear section?
    Reference:408.10 2
  87. 87. 110 – 2026 Changes Part 1

    1
    In the 2026 NEC, wiring?device–type switch requirements were relocated from Article 404 to which Article?
    Reference:406
  88. 88. 117 – 2026 Changes Part 1

    1
    Tamper?resistant receptacle requirements have expanded to include which of the following locations in addition to dwelling units?
    Reference:406.26
  89. 89. 69 – 2026 Changes Part 1

    1
    Generally, wiring methods and materials installed under ________ has been revised and still must maintain a separation of no less than 1 1/2 inch from the roof decking. (This section was also re-written in the 2023 NEC.)
    Reference:300.6 E
  90. 90. 20 – 2026 Changes Part 1

    1
    As a general rule, receptacle outlets shall now not be installed within ________ of residential kitchen cabinets with countertops or work surfaces. (Apparently we installers would place these receptacles close so the power supply cord of an appliance could reach in the absence of suitable wall space.)
    Reference:210.52 C4
  91. 91. 2 – 2026 Changes Part 1

    1
    New Article 206 outlines the general requirements for ________. (Non-Powered-Limited circuits can pose a bigger risk for fire and shock. Previously this content was limited to Chapter 3.)
    Reference:206.1
  92. 92. 96 – 2026 Changes Part 1

    1
    For Intermediate Metal Conduit (IMC) __________ now permitted as an acceptable means to prevent galvanic corrosion when joining dissimilar metals. (This comes up in retrofits such as industrial expansions or changes.)
    Reference:342.14
  93. 93. 62 – 2026 Changes Part 1

    1
    The scope of new NEC Article 267 covers _______ operating at 1000 volts AC or 1500 volts DC. (Previously located in Article 235 along with other higher voltage systems.)
    Reference:267.1
  94. 94. 195 – 2026 Changes Part 1

    1
    Which of the following is REQUIRED for bonding an equipotential plane under NEC 547?(This change makes it clear and enforceable standard for constructing equipped potential planes in agricultural environments )
    Reference:547.44 B
  95. 95. 162 – 2026 Changes Part 1

    1
    Cannabis extraction operations shall NOT be located in any building containing which of the following occupancies?
    Reference:512.6
  96. 96. 64 – 2026 Changes Part 1

    1
    For services over 1000 volts AC or 1500 volts DC, if the short circuit protection device (OCPD) is not an integral part of the service disconnecting means, it ________ (to assure that the disconnect is readily accessible.)
    Reference:268.91 B
  97. 97. 116 – 2026 Changes Part 1

    1
    Which of the following is required for a faceplate that incorporates a night light and is installed over a receptacle outlet?
    Reference:406.16 D
  98. 98. 109 – 2026 Changes Part 1

    1
    According to the NEC, which of the following statements about reconditioned wiring devices is correct?(Wiring devices cannot be reconditioned because they’re inexpensive are safety critical have internal components that cannot be inspected and are not designed for refurbishment )
    Reference:406.3
  99. 99. 146 – 2026 Changes Part 1

    1
    According to the 2026 NEC which of the following correctly describes the new listing requirements and effective dates for high?voltage switchgear and industrial control assemblies?
    Reference:495.2 AB
  100. 100. 49 – 2026 Changes Part 1

    1
    Grounding electrode conductors shall generally be continuous without a splice. A new exception to that rule includes ______ that is accessible. (Please note that this new option must be accessible for inspection and maintenance after installation…does that include burial?)
    Reference:250.64 C