Oregon Rule and Law Version 2023 Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 157 – Oregon Rule and Law Version 2023

    1
    A properly licensed electrical contractor may use a minor label permit for a circuit extension of not more than ________ electrical circuits limited to 30 amps and not more than 300 volts to ground.
    Reference : 918-309-0220(7)
  2. 2. 155 – Oregon Rule and Law Version 2023

    1
    Generally, a limited energy contractor can use a limited minor electrical permit for a new installation of up to ________ in new construction.
    Reference : 918-309-0220(6)
  3. 3. 043 – Oregon Rule and Law Version 2023

    1
    Type MC cable ________ secured and supported by cable ties
    Reference : Table 1-E , 330.30(A)
  4. 4. 080 – Oregon Rule and Law Version 2023

    1
    An example of a condition requirement for product use in a system that generates and distributes electricity that is not certified includes the ________.
    Reference : 918-261-0030
  5. 5. 049 – Oregon Rule and Law Version 2023

    1
    Need to be specifically approved by a supervisor
    Reference : Table 1-E , 445.19(C)
  6. 6. 106 – Oregon Rule and Law Version 2023

    1
    Ground-Fault Circuit-Interrupter Protection (GFCI) for personnel was modified in the NEC to cover all receptacles for electric vehicle charging locations. The Oregon amendments
    Reference : Table 1-E 625.54
  7. 7. 118 – Oregon Rule and Law Version 2023

    1
    When corrections have been issued to a permitted electrical installation, those corrections must be completed within ________ of the notification.
    Reference : 918-309-000(8)
  8. 8. 057 – Oregon Rule and Law Version 2023

    1
    In an elevator pit, sump pumps are required to be protected with Class A GFCI protection for personnel, unless ________.
    Reference : Table 1-E , 620.6(C)
  9. 9. 071 – Oregon Rule and Law Version 2023

    1
    When an electrical item is Labeled, it will have an identifying mark by ________.
    Reference : 918-251-0090
  10. 10. 036 – Oregon Rule and Law Version 2023

    1
    Receptacle outlets shall be installed for a dwelling unit kitchen island
    Reference : Table 1-E , 210.52(C)(2)
  11. 11. 137 – Oregon Rule and Law Version 2023

    1
    A temporary electrical work permit must be signed by ________.
    Reference : 918-309-0080(4)
  12. 12. 090 – Oregon Rule and Law Version 2023

    1
    The 2023 NEC expanded the requirements for GFCI protection for appliances, the Oregon Specialty Code clarified GFCI protection for _________.
    Reference : Table 1-E210.8(D)
  13. 13. 124 – Oregon Rule and Law Version 2023

    1
    If an electrical contractor begins the electrical installation before a required plan review is completed ________.
    Reference : 918-309-0025(1)
  14. 14. 114 – Oregon Rule and Law Version 2023

    1
    As a general rule, an electrical permit issued to one firm is ________ .
    Reference : 918-309-000(5)
  15. 15. 023 – Oregon Rule and Law Version 2023

    1
    An Alcove in the Oregon Specialty Electrical Code is additionally defined as an area with a ________.
    Reference : Table 1-E, 100
  16. 16. 142 – Oregon Rule and Law Version 2023

    1
    If the rules on temporary electrical work permits are violated, civil penalties may be assessed. The contractor may also be ________ from using these in the future.
    Reference : 918-309-0080(8)
  17. 17. 027 – Oregon Rule and Law Version 2023

    1
    Indoor damp and wet locations of dwelling units are ________ GFCI protection for 125 volt, 15 and 20 ampere receptacles.
    Reference : Table 1-E , 210.8(A)
  18. 18. 117 – Oregon Rule and Law Version 2023

    1
    Electrical work permits issued under the Oregon Specialty Code become null and void if the electrical work has been suspended or abandoned for a period of _________.
    Reference : 918-309-000(7)
  19. 19. 128 – Oregon Rule and Law Version 2023

    1
    The electrical work permit fee for a manufactured dwelling unit (mobile home) ________.
    Reference : 918-309-0030(5)
  20. 20. 144 – Oregon Rule and Law Version 2023

    1
    A master electrical permit covers ________ electrical installations
    Reference : 918-309-0100(4)
  21. 21. 044 – Oregon Rule and Law Version 2023

    1
    Receptacles shall not be installed within or above a bathtub,
    Reference : Table 1-E , 406.9(C)
  22. 22. 109 – Oregon Rule and Law Version 2023

    1
    Feeder taps for Interconnected Electric Power Production Sources (Multiple sources operating in parallel with the primary electric source.) shall not be less that one-third the overcurrent device plus the ratings of any others connected. The State of Oregon Rules ________.
    Reference : Table 1-E 705.12(A)(3)
  23. 23. 146 – Oregon Rule and Law Version 2023

    1
    A covered facility can obtain and use a master electrical permit only if ________.
    Reference : 918-309-0100(5)
  24. 24. 112 – Oregon Rule and Law Version 2023

    1
    In the State of Oregon, an electrical work permit is required ________.
    Reference : 918-309-000(3)
  25. 25. 131 – Oregon Rule and Law Version 2023

    1
    Any person that commences and starts the electrical work before an electrical work permit is issued will be subject to ________.
    Reference : 918-309-0070(12)
  26. 26. 149 – Oregon Rule and Law Version 2023

    1

    A minor permit label in Oregon is an alternative option for smaller installations instead of a standard electrical permit. A minor label may be used for ________.

    Reference : 918-309-0220(3)
  27. 27. 116 – Oregon Rule and Law Version 2023

    1
    Electrical work permits issued under the Oregon
    Specialty Code become null and void if the electrical work is not started within ________.
    Reference : 918-309-000(7)
  28. 28. 052 – Oregon Rule and Law Version 2023

    1
    Part II of NEC Article 517 shall not apply to ________ areas.
    Reference : Table 1-E , 517.10(B)
  29. 29. 130 – Oregon Rule and Law Version 2023

    1
    Bulk electrical permit labels are sold ________ at $25.00 per label
    Reference : 918-309-0040(9)
  30. 30. 132 – Oregon Rule and Law Version 2023

    1
    A stop-work order may only be issued for ________ violations of the minimum electrical safety standards.
    Reference : 918-309-0075(2)
  31. 31. 016 – Oregon Rule and Law Version 2023

    1
    A licensed journey-level limited sign electrician is not permitted to
    Reference : 918-282-0220
  32. 32. 091 – Oregon Rule and Law Version 2023

    1
    The Oregon State rules modified the 2023 NEC arc fault requirements for dormitory unit receptacles ________ areas.
    Reference : Table 1-E 210.12(C)
  33. 33. 059 – Oregon Rule and Law Version 2023

    1
    When a swimming pool pump motor is replaced, the pump motor
    Reference : Table 1-E , 680.21(D)
  34. 34. 156 – Oregon Rule and Law Version 2023

    1
    A properly licensed electrical contractor may use a minor label permit for a circuit extension of not more than ________ electrical circuits limited to 60 amps and not more than 150 volts to ground.
    Reference : 918-309-0220(7)
  35. 35. 072 – Oregon Rule and Law Version 2023

    1
    A Limited Energy System can mean a system that includes ________.
    Reference : 918-251-0090
  36. 36. 099 – Oregon Rule and Law Version 2023

    1
    The 2023 NEC has begun to address remotely adjusting Adjustable-Trip Circuit Breakers via the internet. In Oregon the permit holder ________ demonstrate compliance with this requirement.
    Reference : Table 1-E 240.6(D)
  37. 37. 094 – Oregon Rule and Law Version 2023

    1
    The 2023 NEC required that a low voltage residential lighting switch not exclusively rely on batteries unless the lights would automatically energize if the batteries failed. The State of Oregon Rules ________.
    Reference : Table 1-E 210.70
  38. 38. 002 – Oregon Rule and Law Version 2023

    1
    Minor labels sold by the division for electrical installations shall be sold ___________.
    Reference : 918-100-0030
  39. 39. 101 – Oregon Rule and Law Version 2023

    1
    The Oregon State Electrical Specialty Code amendments now allow Electrical Nonmetallic Tubing in buildings exceeding three floors above grad ________.
    Reference : Table 1-E 362.10
  40. 40. 047 – Oregon Rule and Law Version 2023

    1
    Sump and sewage pumps are generally required to be protected with Class A GFCI protection for personnel, unless
    Reference : Table 1-E , 422.5(A)(6)
  41. 41. 077 – Oregon Rule and Law Version 2023

    1
    There is an exemption from permits for the repair or replacement of an HVAC ________.
    Reference : 918-261-0020
  42. 42. 154 – Oregon Rule and Law Version 2023

    1
    A limited energy contractor can use a limited minor electrical permit for ________.
    Reference : 918-309-0220(6)
  43. 43. 084 – Oregon Rule and Law Version 2023

    1
    The 2023 NEC has now begun to address cybersecurity for network-connected life safety equipment. In Oregon the permit holder ________ demonstrate compliance with this requirement for this type of installation.
    Reference : Table 1-E 110.3(A)(8)
  44. 44. 082 – Oregon Rule and Law Version 2023

    1
    A new clarification of the NEC definition of a structure in Oregon now includes ________.
    (Important when it comes to floating a neutral or not.)
    Reference : Table 1-E 100 Definitions
  45. 45. 042 – Oregon Rule and Law Version 2023

    1
    An interior of a raceway installed in a wet location shall also be considered a wet location, unless _____
    Reference : Table 1-E , 300.9 ex
  46. 46. 051 – Oregon Rule and Law Version 2023

    1
    If electrical switchgear has been damaged by fire or water, it shall be evaluated by ________ prior to being returned to service
    Reference : Table 1-E , 490.49
  47. 47. 026 – Oregon Rule and Law Version 2023

    1
    In Oregon State, ________ in a dwelling unit are not required to have GFCI protection for all 125 volt, single phase, 15-20 ampere receptacles
    Reference : Table 1-E , 210.8(A)(6)
  48. 48. 040 – Oregon Rule and Law Version 2023

    1
    For dwelling units, an outdoor disconnect is required as an emergency disconnect. The disconnect can be a
    Reference : Table 1-E , 230.85
  49. 49. 034 – Oregon Rule and Law Version 2023

    1
    In a dwelling unit, AFCI protection shall not be required for 120 volt, single phase, 15 and 20 ampere branch circuits supplying receptacles located in
    Reference : Table 1-E , 210.12(B)ex 4
  50. 50. 066 – Oregon Rule and Law Version 2023

    1
    In Oregon, the Electrical Specialty Code means ________.
    Reference : 918-251-0090
Back