OR: Residential Code Review (201029) Quiz Please sign up for the before taking this quiz. Back Save Progress Retry Finish 1. 200 – Industry Related Residential Version (201029)1Branch-circuit cable type UF is located in Article _____. 336 340 334 338 Reference: 340.1 2. 199 – Industry Related Residential Version (201029)1Telephone communication wires installed in a wood framed wall generally should be separated by at least _____ inch(es) from NM cable (romex) at 120 volts. 1 2 3 No separation is needed. Reference: 800.133B 3. 198 – Industry Related Residential Version (201029)1In a residential closet, a junction box with 120-volt conductors is installed for the doorbell transformer. The Class 2 low voltage wires ___________. Only Class 1 low voltage wires may be ran. may be installed in the same J box may be run outside adjacent to the J box to provide separation None of these statements are true Reference: 725.136A&B 4. 196 – Industry Related Residential Version (201029)1A single family dwelling with an indoor packaged hot tub assembly may utilize romex as a wiring method if it ___________. Romex is not allowed to feed an indoor hot tub is installed in a raceway only contains a copper equipment grounding conductor sized at a minimum of 10 AWG or larger only complies with Part I and II of Article 680 Reference: 680.43 5. 195 – Industry Related Residential Version (201029)1For an indoor hot tub installation, a ceiling fan must be GFCI protected if it is located less than _____ feet above or _____ feet horizontally from the tub. 14, 5 12, 5 None of these statements are true 7 feet, 5 feet Reference: 680.43B 1 6. 194 – Industry Related Residential Version (201029)1An emergency disconnecting means is required for a hot tub not less than 5 feet and within sight. Both A and B above are true statements. For a multifamily structure. For single-family dwelling unit. None of these statements are true Reference: 680.41 7. 192 – Industry Related Residential Version (201029)1Which, if any, circuit conductors may be installed with the GFCI protected conductors in a nonmetallic raceway used for an underwater swimming pool light? None of these statements are true Both of these statements are true The 240 volt branch circuit for the pool pump motor without GFCI protection. The 120 volt branch circuit (not required to be GFCI protected) used for outside lights. Reference: 680.23F 3 8. 191 – Industry Related Residential Version (201029)1Which of the below is a true statement? All single phase, 15 and 20 amp, 120 through 240 volt receptacles that supply an outdoor hot tub motors are required to have GFCI protection regardless of their location. All 125 V receptacle located within 20 feet of an outdoor hot tub are required to be provided with GFCI protection. All of these statements are true All 125 V receptacles rated 30 amperes or less and located within 10 feet of an indoor hot tub are required to be provided with GFCI protection. Reference: 680.22A, 680.43A 9. 190 – Industry Related Residential Version (201029)1For an outdoor hot tub, a 125 V, 15 or 20 ampere receptacle shall be located not less than _____ feet or more than _____ feet from the inside wall of the tub or more than _____ feet above the level of the tub. 10, 15, 6.5 6, 20, 6.5 10, 20, 10 5, 10, 2005 Reference: 680.22A 1 10. 187 – Industry Related Residential Version (201029)1 A park trailer is intended to be used for ___________. None of these statements are true a permanent dwelling temporary office use seasonal use Reference: 552.4 11. 185 – Industry Related Residential Version (201029)1The minimum size service for a mobile home in a mobile home park is _____ amperes. 200 150 80 100 Reference: 550.32C 12. 184 – Industry Related Residential Version (201029)1Electric ranges and clothes dryers used in mobile homes shall be ___________. installed with the grounding conductor and the neutral bonded together installed with the grounded circuit conductor insulated from the grounding conductor and the metal equipment enclosures installed like in all existing dwelling units installed with the metal equipment enclosure junction box isolated Reference: 550.16A, 250.104 13. 183 – Industry Related Residential Version (201029)1Type NM cable (romex) is used as a temporary construction branch circuit. It is limited to _____ floors above grade. 4 Unlimited 5 3 Reference: 590.4C 14. 182 – Industry Related Residential Version (201029)1The length of a supply cord to a 120-volt rated room air-conditioner shall not exceed _____ feet. 6 4 10 3 Reference: 440.64 15. 180 – Industry Related Residential Version (201029)1Electric heat cable with a conductive floor covering installed in a bathroom floor shall _____. have GFCI protection be prohibited be only allowed in commercial structures be limited to 32 volts Reference: 424.44E 16. 178 – Industry Related Residential Version (201029)1Given a wall mounted oven is cord and plug connected: For the cord and plug to serve as the unit disconnect, it must be accessible. Having to pull the unit out of the wall first to get access to the plug and cord may not be considered accessible, and additional disconnecting would be required. All of these statements are true A pull out drawer in the bottom of the oven could make the cord and plug accessible. Reference: 422.33B 17. 177 – Industry Related Residential Version (201029)1A dwelling unit has a dishwasher connected with a cord and plug. The plug and receptacle is installed to facilitate removal for servicing or repairs and they are allowed to serve as the disconnect for this appliance if ____. None of these statements are true It is located behind the dishwasher requiring removal to gain access. It is accessibly located in the undercounter space adjacent to the dishwasher. A plug and receptacle are not allowed to serve as a disconnect. Reference: 422.33 18. 176 – Industry Related Residential Version (201029)1When a gas-fired central heating furnace is installed in a dwelling unit, is a disconnect required for the 1/8 HP blower motor? No, only if the blower motor is 1/4 HP or more. No, the disconnect would be impracticable. Yes, unless the branch circuit breaker is within sight. A disconnect is not required, but recommended. Reference: 422.31A 19. 175 – Industry Related Residential Version (201029)1If the overcurrent protective device rating is marked on the name plate of the appliance, the branch circuit overcurrent device shall be no more than _____ of the rating. 80% 100% 125% 50% Reference: 422.11A 20. 174 – Industry Related Residential Version (201029)1Branch circuit conductors within _____ inches of a ballast, within the ballast compartment shall be recognized for use at temperatures not lower than 90 degree C. 1 3 2 4 Reference: 410.68 21. 172 – Industry Related Residential Version (201029)1 Which types of luminaries (light fixtures) are not permitted in clothes closets? Incandescents with an open lamp. All of these statements are true Incandescents with partially enclosed lamps. Pendant mounted luminaries. Reference: 410.16C 22. 170 – Industry Related Residential Version (201029)1The defined space in a bathtub zone may not necessarily rise all the way up to the ceiling. In a clothes closet, the area defined as storage space rises up to _____ feet above the shelf. 4 2 3 In a clothes closet, the area defined as storage space rises to the ceiling regardless of the ceiling height. Reference: 410.16A Figure 23. 166 – Industry Related Residential Version (201029)1Receptacles rated _____ amperes or less directly connected to aluminum conductors shall be marked CO/ALR. 30 25 40 20 Reference: 406.3C 24. 164 – Industry Related Residential Version (201029)1Snap switches are required to be grounded ___________. only when a metal coverplate is used whether or not a metal coverplate is installed only when installed in a dwelling unit only when installed in a metal J box Reference: 404.9B 25. 163 – Industry Related Residential Version (201029)1Snap switches can be grouped or ganged in outlet boxes if voltages between adjacent switches do not exceed _____ volts. 300 400 250 150 Reference: 404.8B 26. 162 – Industry Related Residential Version (201029)1The height of a circuit breaker used as a switch shall not exceed _____ above the floor. 4.5 feet 5 feet 6 feet, 7 inches 6 feet Reference: 404.8A 27. 161 – Industry Related Residential Version (201029)13-way and 4-way switches shall be wired so that all the switching is done in the ___________ conductor. grounding ungrounded neutral grounded Reference: 404.2 28. 157 – Industry Related Residential Version (201029)1A 1-inch Rigid Nonmetalic Conduit (RNC or PVC) has a field bend made with a blanket bender. The radius of the curve to the centerline shall not be less than _____ inches. 8 inches 10 inches What’s shown in Table 2, Chapter 9 7 inches Reference: 352.24 29. 156 – Industry Related Residential Version (201029)1Power conductors in type NMC cable are manufactured in copper sizes ___________. #14-#4 #12-#2 #14-#2 #14-#6 Reference: 334.104 30. 155 – Industry Related Residential Version (201029)1Type NM cable (romex) is permitted to connect fluorescent light fixtures in a residence in a dropped ceiling grid without support to a maximum length of not more than _____ feet. 4.5 3.5 3 4 Reference: 334.30 B2 31. 154 – Industry Related Residential Version (201029)1The overall covering for type NMC cable shall be ___________. flame retardant corrosion resistent All of these statements are true moisture resistant Reference: 334.116B 32. 153 – Industry Related Residential Version (201029)1 NMB cable (romex) is required to be protected from physical damage when exposed. Two of these statements are true When run across the top of the truss joists in an accessible attic, the cable shall be protected by guard strips. When passing through a floor the cable shall be enclosed in conduit extending at least 6 inches above the floor. None of these statements are true Reference: 334.15B, 23 33. 151 – Industry Related Residential Version (201029)1A luminaire (light fixture) weighs over 50 pounds and it is supported from an outlet box. The code requires _____. The fixture be independently supported unless the box is listed over 50 pounds. This installation be specifically approved by the authority having jurisdiction. None of these statements are true An outlet box cannot be used as support of the fixture. Reference: 314.27A 34. 149 – Industry Related Residential Version (201029)1In a combustible wall, the front edge of an outlet box may be set back no more than _____ inches from the finished surface. 1/2 1/8 0 1/4 Reference: 314.20 35. 147 – Industry Related Residential Version (201029)1A #4 copper conductor used for a residential dwelling unit feeder panel is rated for at least _____ amperes. 85 110 100 115 Reference: Table 310.12 36. 146 – Industry Related Residential Version (201029)1A 400 amp, single phase, 120/240 Volt parallel run could be composed of _____. All of these statements are true 2, 3/0 copper conductors in parallel for A phase and 2, 3/0 copper conductors in parallel for B phase 2, 250 KCMIL aluminum conductors in parallel for A phase and 2, 250 KCMIL aluminum conductors in parallel for B phase 2, 3/0 copper conductors in parallel for A phase and 2, 250 KCMIL aluminum conductors in parallel for B phase Reference: 310.10G 37. 144 – Industry Related Residential Version (201029)1NMB (romex) cable is installed in a standard 2 x 4 inch plastic nail-on junction box. All of these statements are true Equipment grounding conductors are also required to meet this free conductor length requirement. The measurement of free conductor length in this junction box is taken from the back of the box where conductors emerge from the sheath. A minimum of 6 inches of free conductor length is required for make-up and/or connection to devices. Reference: 300.14 38. 143 – Industry Related Residential Version (201029)1A 24-volt landscape lighting system installed with UF cable in the yard of a residence is permitted with a minimum cover of _____ inches. 18 6 24 12 Reference: Table 300.5 39. 139 – Industry Related Residential Version (201029)1Which is not a true statement about equipment grounding conductors? An equipment grounding conductor may be required to be larger than the hot wires. Equipment grounding conductors shall be increased in size to compensate for voltage drop when the circuit conductors are. Equipment grounding conductors may be run in parallel. One equipment grounding conductor may serve multiple circuits. Reference: 250.122A 40. 138 – Industry Related Residential Version (201029)1If the service entrance conductors are 350 KCMIL copper, what is the minimum size copper grounding electrode conductor if this is the sole connection to a metal water pipe electrode? 1/0 #2 #6 #4 Reference: Tab250.66, 66A 41. 133 – Industry Related Residential Version (201029)1A structure has 2 separate services supplying the building. Only one service would require a separate grounding electrode system. More than one service on a structure is never allowed. Each service requires a separate grounding electrode system. Each service can have a separate grounding electrode system as long as they are bonded together to create one system. Reference: 250.58 42. 130 – Industry Related Residential Version (201029)1Some metal water piping systems can deteriorate with time and may even end up being replaced with a nonmetallic system. This is one reason the code requires a supplemental grounding electrode as a backup. If a ground rod is used as this supplemental electrode, how many are required? 2 1 (Resistance to ground is more than 25 ohms) Rods are not allowed to supplement the piping system. 0 Reference: 250.53 43. 128 – Industry Related Residential Version (201029)1If an equipment grounding conductor is installed with a feeder to a separate structure, the equipment grounding conductor shall not be bonded to the ___________. Grounded conductor The disconnect enclosure None of these statements are true Grounding electrode conductor Reference: 250.32B 44. 127 – Industry Related Residential Version (201029)1If the allowable current carrying capacity of a conductor does not correspond to the rating of a standard size overcurrent device, the next larger size may be used provided the current does not exceed _____ amps. 800 1000 600 400 Reference: 240.4B 45. 125 – Industry Related Residential Version (201029)1Service conductors that run above the top level of a window shall be permitted to be less than the _____ foot requirement. 4 3 6 8 Reference: 230.9A 46. 124 – Industry Related Residential Version (201029)1An outbuilding on residential property is wired with one 20 ampere, 120-volt feeder for lighting and outlets. No disconnecting means is required for this situation. The required disconnecting means shall be red. The required disconnecting means shall be located near the point of entry. A snap switch is allowed for the required disconnecting means. Reference: 225.36 47. 123 – Industry Related Residential Version (201029)1The height of a wall switch for a lighting outlet in a dwelling unit can be no more than _____. 4 feet 6 feet 5 feet 6 feet 7 inches Reference: 404.8 A 48. 122 – Industry Related Residential Version (201029)1A living room in a dwelling unit has 3 entry points (doorways) into the room. What is the minimum requirement for the number of lighting outlet switches? 3, 2 to 3-way and 1 4-way switch 2, 3-way switches 0 1 Reference: 210.70A 1 49. 121 – Industry Related Residential Version (201029)1A wall switch in a dwelling unit can be installed ____. Inside the room it serves Both of these statements are true None of these statements are true Outside the room it serves Reference: 210.70A 50. 120 – Industry Related Residential Version (201029)1Which rooms in a dwelling unit may have a receptacle outlet controlled by a switch used for lighting instead of a lighting outlet? Bathroom None of these statements are true Dining room Kitchen Reference: 210.70A 1 51. 119 – Industry Related Residential Version (201029)1A dwelling unit dining room has a receptacle controlled by a wall switch instead of a lighting outlet. None of these statements are true This is allowed when the switch is supplied by the small appliance branch circuit required to serve this room. This is allowed when the switch is supplied by a general purpose branch circuit and it is installed in addition to the required small appliance branch circuit. Both A and B above are true statements. Reference: 210.70, 52B 1 52. 118 – Industry Related Residential Version (201029)1A homeowner wants an occupancy sensor installed in his home office for lighting. This is allowed for one mounted on the ceiling if a wall switch is also installed. None of these statements are true Both of these statements are true This is allowed if the occupancy sensor replaces the wall switch if it is equipped with a manual override that allows it to function as a wall switch. Reference: 210.70A 1 53. 117 – Industry Related Residential Version (201029)1In order for the required receptacle outlet in the back of a dwelling unit to serve also as the required outlet for the air-conditioning equipment on the side of the home, it must be located within _____ feet of the unit. 25 10 30 50 Reference: 210.63 54. 116 – Industry Related Residential Version (201029)1An air-conditioner is located at grade level on the back of a residence. A receptacle outlet is also located on the back of a residence at a deck which is 3 feet above grade, within 10 feet of the AC equipment. This receptacle outlet can serve as the required outlet for the AC equipment. This receptacle outlet cannot serve as the required outlet for the AC equipment. (must be on the same level) This receptacle outlet does not have to be GFCI protected. This receptacle outlet must be marked to indicate this dual usage. Reference: 210.63 55. 115 – Industry Related Residential Version (201029)1A receptacle outlet must be installed at an accessible location for servicing rooftop heat pump equipment in ___________. commercial buildings All of these statements are true one family dwellings two family dwellings Reference: 210.63 56. 114 – Industry Related Residential Version (201029)1Which receptacle outlet location is permitted but not counted as a required receptacle location? Over 6 feet above the floor. All of these statements are true Inside a kitchen cabinet. An outlet that is part of a luminaire (light fixture). Reference: 210.52 57. 112 – Industry Related Residential Version (201029)1Receptacles located over _____ feet above the floor are not counted in the required number of receptacles along the wall. 6 4.5 5.5. 4 Reference: 210.52 58. 111 – Industry Related Residential Version (201029)1 The residential small appliance branch circuit in a kitchen area ___________. may not include power for an electric clock receptacle in the kitchen. may not include power for a gas-fired cooktop receptacle. may include a plug connected microwave oven receptacle installed on the countertop. may not include a countertop microwave oven load. Reference: 210.52B 59. 110 – Industry Related Residential Version (201029)1 Given an island cabinet in a dwelling unit kitchen where the countertop is flat and you can’t mount a receptacle within 20 inches above the countertop, the receptacle can be a maximum of _____ inches below the countertop and still count as one of the required outlets. 6 This receptacle is no longer required 18 3 Reference: 210.52 C2 60. 109 – Industry Related Residential Version (201029)1In dwelling unit bathrooms, at least one receptacle outlet shall be installed within _____ inches of the outside edge of each basin. 18 36 48 24 Reference: 210.52D 61. 108 – Industry Related Residential Version (201029)1The rating of a cord and plug connected central vacuum unit assembly shall not exceed _____ percent of the branch circuit rating it is installed on. 50 70 80 100 Reference: 210.23B1 62. 106 – Industry Related Residential Version (201029)1 Dwelling unit receptacle outlets shall be protected by arc-fault circuit interrupter protection ___________. even for bathroom receptacles. None of these statements are true Even for sunroom receptacles. even for outside receptacles. Reference: 210.12B 63. 104 – Industry Related Residential Version (201029)1 Does a duplex receptacle installed in a dwelling type occupancy for the refrigerator require GFCI protection? Not if it is a single receptacle on the yoke installed for the refrigerator. Not when it is installed on the wall behind the location for the refrigerator. No, never Yes, all kitchen receptacles Reference: 210.8A 6 64. 103 – Industry Related Residential Version (201029)1In a dwelling unit, a multiwire branch circuit supplying a split-wired receptacle is required to ___________. have a separate neutral for each ungrounded conductor. have color coded wires to help identify. have a provision at the source to simultaneously disconnect all ungrounded conductors. have at least 2 neutrals. Reference: 210.4B 65. 102 – Industry Related Residential Version (201029)1A 10-2 romex is used as a 240-volt branch circuit for a hot water tank. The white insulated conductor shall be re-identified as a hot ungrounded conductor at the terminations. This can be done with black phase tape. Both of these statements are true None of these statements are true This can be done with a black felt pen marker. Reference: 200.7C 66. 101 – Industry Related Residential Version (201029)1Is a circuit breaker without a HACR marking suitable as a disconnecting means for an outdoor air conditioner? If the marking on the unit indicates fuses, the circuit breaker does have to be a HACR type If the marking on the unit indicates fuses or HACR circuit breaker, the breaker does not have to be a HACR type if no fuses are used. If the marking on the unit specifies fuses or circuit breaker, the breaker does not have to be a HACR type if fuses are used. None of these statements are true Reference: 110.3B 67. 100 – Industry Related Residential Version (201029)1Flexible Metal Conduit (FMC or Flex) can be used in a wet location if… Flexible metal conduit cannot be used in a wet location. None of these statements are true The branch circuit conductors are rated for a wet location. The run prevents water from entering the enclosure. Reference: 348.12 68. 099 – Industry Related Residential Version (201029)1For each yoke or strap containing one or more devices, a ______ volume allowance is made based on the largest conductor connected to the device to calculate box fill. Single. Triple. Double. No allowance is needed for devices. Reference: 314.16B 4 69. 098 – Industry Related Residential Version (201029)1What is the minimum direct burial depth of Rigid Nonmetallic Conduit (RNC/PVC) on a residential 15 amp GFCI protected circuit rated 120 volts or less? 12 inches. 6 inches. 24 inches. 18 inches. Reference: Table 300.5 70. 096 – Industry Related Residential Version (201029)1In a dwelling unit, one wall switch for a light is required at each floor level of a stairway with… 6 steps or more. 7 steps or more. 10 steps or more. 8 steps or more. Reference: 210.70A 2 71. 095 – Industry Related Residential Version (201029)1As a general rule, conductors of Class II wiring as for a thermostat circuit ____ placed in any enclosure, box, raceway, etc., with conductors of electric light, power, Class I, and non-power limited fire alarm circuits. Can be if 300 volt insulation. Shall not be. Can be. Can be if 600 volt insulation. Reference: 725.136A 72. 093 – Industry Related Residential Version (201029)1Which shall have ground fault circuit interrupter protection? An indoor hot tub supplied by an outlet. A hydromassage bathtub. All of the installations require GFCI protection. An outdoor fountain. Reference: 680.43, 56A, 71 73. 092 – Industry Related Residential Version (201029)1 An outdoor hot tub is installed… Requires a receptacle to be 6' 6" or lower. Requires a receptacle shall be located not further than 20 feet away. All of these statements are true. Requires a receptacle shall be located at least 6 feet away. Reference: 680.22A 74. 091 – Industry Related Residential Version (201029)1In case someone gets stuck under water on the intake opening, an emergency shutoff or control is required for a hot tub…. Within sight of the tub. All of these statements are true And is not required for single-family dwellings. At least 5 feet away. Reference: 680.41 75. 090 – Industry Related Residential Version (201029)1Which is not a requirement for swimming pool bonding? The bonding conductor shall be attached to the remote service equipment. All of these statements are true The bonding conductor shall be attached to the electrode. The bonding conductor shall be attached to the remote panelboard. Reference: 680.26 76. 089 – Industry Related Residential Version (201029)1The number 8 solid copper conductor required for swimming pool bonding in the grid can be installed with… Listed pressure connectors. Aluminum clamps. Indoor type water pipe clamps. Any creative fitting. Reference: 680.26B, 250.8 77. 088 – Industry Related Residential Version (201029)1A swimming pool pump motor supplied by a receptacle 6 feet away from the inside pool wall… Requires GFCI protection except for dwelling units. Does not require GFCI protection. Requires GFCI protection if 15 to 20-amp three phase only. Requires GFCI protection. Reference: 680.22A 78. 087 – Industry Related Residential Version (201029)1The junction “deck box” for a no-niche luminaire (lighting fixture) for a swimming pool shall… Not be less than 8 inches above pool water level. Not be less than 4 inches above ground level. Not be located in a walkway without protection. All of these statements are true Reference: 680.24A2 79. 085 – Industry Related Residential Version (201029)1 An outside mobile home disconnect shall… A disconnect is not required for a mobile home. Be within 40 feet. Be within sight of the home. Be within 30 feet of the home. Reference: 550.32A 80. 082 – Industry Related Residential Version (201029)1As a general rule, the disconnecting means for air conditioning equipment shall… Can be installed on the unit. Be within sight from the unit. Be readily accessible from the unit. All of these statements are true Reference: 440.14 81. 081 – Industry Related Residential Version (201029)1Dishwasher nameplate, 8 amps (Continuous Duty, 125%)… Disposal nameplate, 3 amps… (Intermittent Duty, 85%) Can these be on the same 20-amp circuit and what is the total ampacity? No, 15 amps. Yes, 12.55 amps. Yes, 11 amps. Yes, 13 amps. Reference: 430.24 82. 080 – Industry Related Residential Version (201029)1Baseboard heaters… Generally are not allowed to be installed below a receptacle outlet as per the manufacturers instructions. May be installed below receptacle outlets if over 15 ft. long. May be installed below receptacle outlets if over 12 ft. long. May be installed below receptacle outlets. Reference: 424.10 notes 83. 079 – Industry Related Residential Version (201029)1If a typical residential hot water tank is connected… A circuit breaker capable of being locked in the open position can be used as a disconnect. All of these statements are true A lockable disconnect can be used. A circuit breaker within sight of the hot water tank can be used as a disconnect. Reference: 422.31B 84. 078 – Industry Related Residential Version (201029)1Which ceiling paddle fan installation meets code? A fan less than 40 lbs. supported by an outlet box. A fan less than 35 lbs. supported by an outlet box listed for such a use. A fan less than 50 lbs. supported by an outlet box. None of these statements are true Reference: 422.18 85. 076 – Industry Related Residential Version (201029)1If a fluorescent light is mounted on the wall above a dwelling unit clothes closet door, the minimum clearance to storage space is… 6 inches. 4 inches. 12 inches. 10 inches. Reference: 410.16D 86. 075 – Industry Related Residential Version (201029)1Which type of fixture is not allowed in a clothes closet? A fluorescent with an enclosed lamp. A fluorescent with an open lamp. All of these statements are true An incandescent with an enclosed lamp. Reference: 410.16C 87. 071 – Industry Related Residential Version (201029)1On a circuit, a 2-wire non-grounding existing receptacle is replaced with a GFCI type. It needs to be marked… Not grounded. No Grounded Conductor GFCI Protected. No Equipment Ground. Reference: 406.4D 88. 069 – Industry Related Residential Version (201029)1A switch needs to be located so that the operating handle when installed will not be higher than… 6 ft. 6 inches. 6 ft. 6 ft. 7 inches. 6 ft. 8 inches. Reference: 404.8 89. 068 – Industry Related Residential Version (201029)1A light fixture mounted on a junction box is located near the ground for landscape lighting. Rigid Nonmetallic Conduit (RNC or PVC) is not allowed to support a fixture. 2 threaded rigid metal conduits wrench tight supported within 18" can be the sole support for the box.,Wrong:2 threaded intermediate metal conduits wrench tight supported within 18" can be the sole support for the box. All of these statements are true Reference: 352.10 (I), 314.23F 90. 067 – Industry Related Residential Version (201029)1Rigid Nonmetallic Conduit (RNC or PVC) expands and contracts when installed outdoors. If this change is _____ or greater in a strait run between securely mounted items, expansion fittings are needed. .25 inches. 1 inch. .5 inches. Any change requires an expansion fitting. Reference: 352.44 91. 066 – Industry Related Residential Version (201029)1When installing a (RNC or PVC) Rigid Nonmetallic Conduit expansion joint… All of these statements sound like good ideas. Do not install it all the way open or closed, compensate for today's temperature. If installing in direct sunlight, compensate for temperature. If installing it on a vertical run, put the joint down so water won't run down inside. Reference: 352.44 92. 065 – Industry Related Residential Version (201029)12-inch Rigid Nonmetallic Conduit (RNC or PVC) shall be supported at least every… 5 ft. 6 ft. 10 ft. 8 ft. Reference: 352.30B 93. 064 – Industry Related Residential Version (201029)1Flexible Metal Conduit (FMC or Flex) may have up to ____ quarter bends per run. 4 6 5 3 Reference: 348.24B 94. 063 – Industry Related Residential Version (201029)1A # 8 copper Nonmetallic-Sheathed Cable (romex) conductor is rated at ___ amps using the ___ column of Table 310-16. 40, 60 degree C. 55, 90 degree C. None of these statements are true 50, 75 degree C. Reference: 334.80, Table 310.16 95. 062 – Industry Related Residential Version (201029)1Flat Nonmetallic-Sheathed Cable (Romex) cannot… Be stapled on edge. Be secured by straps. Be secured by cable ties. Be secured by staples. Reference: 334.40 96. 061 – Industry Related Residential Version (201029)1Where Nonmetallic-Sheathed Cable (romex) cable is installed within ___ ft. of an attic access without a permanent ladder, it shall be protected by running boards. 3 7 6 5 Reference: 334.23 97. 060 – Industry Related Residential Version (201029)1Where Nonmetallic-Sheathed Cable (romex) passes through a floor, it shall be protected by a conduit at least ___ inches above the floor. 8 4 5 6 Reference: 334.15B 98. 059 – Industry Related Residential Version (201029)1 Type Nonmetallic-Sheathed Cable (romex) can be used in a residential building if it is ________ and the proper type construction. 3 floors above grade, with a basement 40% above grade 3 floors above grade 4 floors but the 1st level is a parking garage All of these statements are true Reference: 334.10 99. 054 – Industry Related Residential Version (201029)1Nonmetallic Sheathed Cable (romex) installed in a residential dwelling unit… None of these statements are true Cannot be installed in the long dimension of an air handling space. Both of these statements are true Can be installed perpendicular to the long dimension of an air handling space. Reference: 300.22C_ex 100. 053 – Industry Related Residential Version (201029)1In a multiwire branch circuit… None of these statements are true The ungrounded conductors (hots) shall be made up so if a device is removed it will not interrupt continuity. Both A & B above are true. The grounded conductors (Neutrals) shall be made up so if a device is removed it will not interrupt continuity. Reference: 300.13B 101. 051 – Industry Related Residential Version (201029)1When direct burial cable emerges from the ground, unless 30 volts or less or 20 amp residential GFCI circuits, it shall be protected by a raceway ___ inches below grade and up to ___ feet above grade. 24; 10. 24; 8. 18; 8. 18; 10. Reference: 300.5D 1 102. 050 – Industry Related Residential Version (201029)1Given an underground service lateral from a power company transformer to a customer owned service that you need to install. If not encased in concrete, a warning ribbon must be placed in the trench along side with the installation. None of these statements are true If not encased in concrete, a warning ribbon must be placed in the trench at least 12 inches above the installation. If not encased in concrete, a warning ribbon must be placed in the trench at least 6 inches above the installation. Reference: 300.5D 3 103. 049 – Industry Related Residential Version (201029)1When installing Nonmetallic Sheathed Cable (Romex) through metal stud framing members… A bushing or grommet is required only for factory cut holes. A bushing or grommet is required in the opening. Nonmetallic-Sheathed Cable (Romex) is not allowed in metal stud framing. A bushing or grommet is required only for field-punched holes. Reference: 300.4B 1 104. 048 – Industry Related Residential Version (201029)1When determining a proper depth of a ditch for an underground conduit. There is no specific requirement. Measure from the top of the conduit. Measure from the bottom of the ditch. Measure from the center of the conduit. Reference: Table 300.5_notes 105. 047 – Industry Related Residential Version (201029)1 A new installation of a branch circuit supplying a single-phase clothes dryer requires… Either A or B above. None of these statements are true A 4 wire cable including an equipment ground. A 3 wire cable including an insulated neutral. Reference: 250.140 106. 046 – Industry Related Residential Version (201029)1Listed Flexible Metallic (Flex) Conduit is an approved grounding means when… The total lengths of flex in a combined run are not longer than 6 feet. All of these statements are true Conductors installed in the flex are rated 30 amps and on a 30 amp breaker maximum. The longest section of flex in a combined run is 6 feet. Reference: 250.118 5 107. 045 – Industry Related Residential Version (201029)1Which is a true statement? A metal conduit, which contains a grounding electrode conductor, does not need to be bonded. A metal conduit, which contains a grounding electrode conductor, needs to be bonded at one end only. A metal conduit, which contains a grounding electrode conductor, needs to be bonded at both ends. An EMT conduit, which contains a grounding electrode conductor, needs to be bonded at one end only. Reference: 250.64E 108. 044 – Industry Related Residential Version (201029)1If a made electrode (ground rod) is to be used to ground a service…. All of these statements are true If practicable, they need to be installed below moisture level. They can, as a last resort, be buried in a 2 1/2 ft. deep ditch. They can be driven at a 45* angle if rock is found. Reference: 250.53A 4 109. 043 – Industry Related Residential Version (201029)1 Ground rods must be driven and can have… 6 inches above grade level for the clamp 6 inches below grade level for the clamp 2 inches above grade level for the clamp. 0 inches above grade level for the clamp. Reference: 250.53A 4 110. 041 – Industry Related Residential Version (201029)1If it is available on the job site, a metal water pipe that enters the building and is in direct contact with earth for ___ feet or more shall be connected as an electrode within ___ from emergence from the ground. 5, 10 feet 10, 20 feet 10, anywhere 5, 5 feet Reference: 250.52A, 250.68C 111. 039 – Industry Related Residential Version (201029)1Conductors for a feeder where the ampere rating does not match with a standard circuit breaker… Must be used with a breaker the next lower standard size. All of these statements are true Can be used with the next higher standard breaker size if it is under 800 amps. Can be used with the next higher standard breaker size. Reference: 240.4B 112. 037 – Industry Related Residential Version (201029)1Which is not an acceptable grouping of service disconnects? 2 disconnects installed together outside. 2 disconnects installed together inside and one 50 ft. away outside for a fire pump. 2 disconnects installed together inside. 1 disconnect installed outside and 3 inside. Reference: 230.72 113. 036 – Industry Related Residential Version (201029)1 As a general rule, overhead service weatherheads… Shall be above the point of attachment of the service drop. Can be both above or below within 30 inches of the attachment of the service drop. Shall be at the point of attachment of the service drop. Shall be below the point of attachment of the service drop. Reference: 230.54C 114. 035 – Industry Related Residential Version (201029)1Service entrance conductors… Cannot be spliced unless the authority having jurisdiction gives express permission. Can be spliced. None of these statements are true Cannot be spliced. Reference: 230.46 115. 034 – Industry Related Residential Version (201029)1A house with a separate structure like a shop has one service location with one service lateral with the meter attached to the home. You can have one disconnect at and for the home and another at and for the shop. (A meter loop.) None of these statements are true At the meter, you can have 2 disconnects grouped together outside, one for the home, the other for the shop. Both of these statements are true Reference: 230.40 ex 3 116. 032 – Industry Related Residential Version (201029)1Open service conductors installed on buildings require… 3 feet minimum clearance from windows. 3 feet minimum clearance from windows if they can be opened. 4 feet minimum clearance from windows if they can be opened. 4 feet minimum clearance from windows. Reference: 230.9A 117. 031 – Industry Related Residential Version (201029)1An outside pole light… Requires a disconnect on or at the pole. None of these statements are true Requires a lockout at the panel. Does not require a disconnect on or at the pole. Reference: 225.31 ex 4 118. 030 – Industry Related Residential Version (201029)1Which is not a true statement of an outside feeder from one building to another? If building #2 is supplied by more than one feeder, permanent identification is required. The disconnect in (A) above must be suitable for use as service equipment. Building #2 is limited to 8 disconnects grouped in one location. A disconnect is required at building #2. Reference: 225.31, 36, 37 119. 027 – Industry Related Residential Version (201029)1 A required dwelling unit wall light switch for a room… Is required within 6 feet of a doorway. Is required within 5 feet of a doorway. Is required within 4 feet of a doorway. Has no specific location requirement, just near an entrance. Reference: 210.70A 120. 026 – Industry Related Residential Version (201029)1An air conditioner… Requires an outlet within 25 Ft. Requires an outlet on the same level for servicing it. Requires an outlet if it is a 2 family dwelling. All of these statements are true. Reference: 210.63 121. 025 – Industry Related Residential Version (201029)1If installed in an attic, does a furnace require a 15 – 20 amp rated outlet for servicing the unit? No, only on rooftops within 25 ft. Yes, but only for dwelling units. No, only on rooftops and in crawl spaces. Yes, accessible and on the same level within 25 ft. Reference: 210.63 122. 024 – Industry Related Residential Version (201029)1In a guest room of hotel or motel, does the number of receptacle outlets installed need to comply as in a dwelling unit of Section 210-52? No, that Section does not apply. Yes, and they need to be located as per those requirements. No, number of outlets is determined by customer preference. Yes, but they can be relocated because of furniture layout. Reference: 210.60 B 123. 022 – Industry Related Residential Version (201029)1For a one family dwelling where part of the basement is finished but another portion is not…. An additional outlet is not required in the unfinished portion. Two additional outlets are required in the unfinished portion. An additional outlet is required in the unfinished portion. None of these statements are true. Reference: 210.52G 124. 021 – Industry Related Residential Version (201029)1Two family dwellings (duplex) require how many grade level accessible outside receptacles? Two, one for each unit, one in the front and the other in the back. One for both units. None are required. Four, two for each unit, two in the front and the two in the back. Reference: 210.52E 125. 020 – Industry Related Residential Version (201029)1In a dwelling unit bathroom, a receptacle is required on the wall next to the sink within… 12 inches. 18 inches. 36 inches. 24 inches. Reference: 210.52D 126. 019 – Industry Related Residential Version (201029)1 In a dwelling unit kitchen where the exception allows a receptacle to be installed below the countertop, to count, the counter lip shall extend no more than ___ beyond the counter. This no longer counts. 8 inches. 12 inches. 10 inches. Reference: 210.52C 3 127. 018 – Industry Related Residential Version (201029)1The two or more required kitchen 20-amp appliance circuits can include… A clock in the breakfast room. Dining room receptacles. Pantry receptacles. All of these statements are true. Reference: 210.52B 1&2 128. 017 – Industry Related Residential Version (201029)1A GFCI protected 20-amp small appliance branch circuit… May not serve more than one kitchen. All of these statements are true May serve more than one kitchen. May serve more than one but it is not recommended. Reference: 210.52B 3 129. 016 – Industry Related Residential Version (201029)1A dwelling unit small appliance branch circuit for the kitchen cannot… Include a receptacle for a gas fired range. Include an outside outlet. All of these statements are true Include a receptacle for a refrigerator. Reference: 210.52B 2 130. 015 – Industry Related Residential Version (201029)1A receptacle outlet for a dwelling refrigerator…. Can be included on the 20-amp small appliance branch circuit. Is not exempted from the GFCI requirements. Can be served by an individual 15-amp circuit. All of these statements are true. Reference: 210.52B1, 210.8 131. 012 – Industry Related Residential Version (201029)1Given, 4 lights at 120 volts at 4.2 amps each on for over 3 hours at a time. How many minimum 20-amp circuits are needed to serve this load? 2 4 3 1 Reference: 210.20A 132. 009 – Industry Related Residential Version (201029)1Which does not require a GFCI protection device for a dwelling unit? One duplex receptacle for a freezer in a garage. All of these require GFCI protection. Workbench outlet in a garage. A single receptacle for a freezer in a garage. Reference: 210.8A 133. 008 – Industry Related Residential Version (201029)1In a dwelling garage, a non-GFCI outlet installed for a Central Vacuum system shall be… Installed at least 7' above the floor. A duplex receptacle. Now not allowed, it must be GFCI protected. Marked "not GFCI protected. Reference: 210.8A 134. 007 – Industry Related Residential Version (201029)1A branch circuit for a dwelling unit is ran out for a small storage building for an inside 120-volt outlet at grade level. If this receptacle is 15-amp, it shall not be GFCI protected. If this receptacle is 15 or 20 amp, it shall be GFCI protected If this receptacle is 20-amp, it shall not be GFCI protected. This receptacle is not required to be GFCI protected, but it is recommended. Reference: 210.8A 135. 006 – Industry Related Residential Version (201029)1A multiwire branch circuit for a hot water tank using a line-to-line load requires… Two single pole breakers with an approved handle tie. Both of these statements are true A double pole circuit breaker. None of these statements are true Reference: 240.15B, 210.4B 136. 005 – Industry Related Residential Version (201029)1If you use a 12-3 romex as travelers between 3-way switches with the white used to supply the switch. The white conductor shall be white with a colored green stripe. None of these statements are true The white conductor does not have to be re-identified. The white conductor must be permanently re-identified where visible. Reference: 200.7C 137. 004 – Industry Related Residential Version (201029)1A neutral conductor sizes ____ or smaller shall be identified by continuous gray or white insulation. #4. #8. #10. #6. Reference: 200.6A 138. 003 – Industry Related Residential Version (201029)1The minimum working space for indoor electrical equipment is from the floor to ____ feet above the equipment or structural ceiling if lower. 6.5 15 25 10 Reference: 110.26A 3 139. 002 – Industry Related Residential Version (201029)1When the term “In sight from” is used in the Code, what is the maximum distance permitted? 30 feet. 50 feet. 25 feet. 75 feet. Reference: Definitions 140. 001 – Industry Related Residential Version (201029)1An area is considered a bathroom if… It includes a sink and a tub. It includes a sink and a shower. All of these statements are true It includes a sink and a toilet. Reference: Definitions Back Save Progress Retry Finish