OR: Residential Code Review (201029) Quiz

Please sign up for the before taking this quiz.
Back
  1. 1. 200 – Industry Related Residential Version (201029)

    1
    Branch-circuit cable type UF is located in Article _____.

    IMG_3167

    Reference: 340.1
  2. 2. 199 – Industry Related Residential Version (201029)

    1
    Telephone communication wires installed in a wood framed wall generally should be separated by at least _____ inch(es) from NM cable (romex) at 120 volts.

    IMG_3205

    Reference: 800.133B
  3. 3. 198 – Industry Related Residential Version (201029)

    1
    In a residential closet, a junction box with 120-volt conductors is installed for the doorbell transformer. The Class 2 low voltage wires ___________.

    IMG_2308

    Reference: 725.136A&B
  4. 4. 196 – Industry Related Residential Version (201029)

    1
    A single family dwelling with an indoor packaged hot tub assembly may utilize romex as a wiring method if it ___________.

    IMG_1199

    Reference: 680.43
  5. 5. 194 – Industry Related Residential Version (201029)

    1
    An emergency disconnecting means is required for a hot tub not less than 5 feet and within sight.

    IMG_2290

    Reference: 680.41
  6. 6. 193 – Industry Related Residential Version (201029)

    1
    An outdoor hot tub requires a common bonding grid to eliminate any voltage gradient in the area. The bonding conductor must be at least a _____ AWG copper wire.

    IMG_2541

    Reference: 680.26B
  7. 7. 192 – Industry Related Residential Version (201029)

    1
    Which, if any, circuit conductors may be installed with the GFCI protected conductors in a nonmetallic raceway used for an underwater swimming pool light?

    IMG_2554

    Reference: 680.23F 3
  8. 8. 191 – Industry Related Residential Version (201029)

    1
    Which of the below is a true statement?

    IMG_2556

    Reference: 680.22A, 680.43A
  9. 9. 190 – Industry Related Residential Version (201029)

    1
    For an outdoor hot tub, a 125 V, 15 or 20 ampere receptacle shall be located not less than _____ feet or more than _____ feet from the inside wall of the tub or more than _____ feet above the level of the tub.

    IMG_2555

    Reference: 680.22A 1
  10. 10. 188 – Industry Related Residential Version (201029)

    1
    Insulated service drop conductors rated 120 volts to ground with a bare grounded neutral conductor is installed over a swimming pool. They shall be a minimum of _____ feet above the water level.

    IMG_2564

    Reference: Table 680.9A
  11. 11. 187 – Industry Related Residential Version (201029)

    1

    A park trailer is intended to be used for ___________.

    IMG_1188

    Reference: 552.4
  12. 12. 185 – Industry Related Residential Version (201029)

    1
    The minimum size service for a mobile home in a mobile home park is _____ amperes.

    IMG_1335

    Reference: 550.32C
  13. 13. 184 – Industry Related Residential Version (201029)

    1
    Electric ranges and clothes dryers used in mobile homes shall be ___________.

    IMG_1170

    Reference: 550.16A, 250.104
  14. 14. 182 – Industry Related Residential Version (201029)

    1
    The length of a supply cord to a 120-volt rated room air-conditioner shall not exceed _____ feet.

    IMG_3198

    Reference: 440.64
  15. 15. 181 – Industry Related Residential Version (201029)

    1

    An owner of a nice home wants to install a walk-in freezer in his garage area. It has an evaporator fan motor inside.

    IMG_2185

    Reference: 430.102, 440.14
  16. 16. 179 – Industry Related Residential Version (201029)

    1
    A residence is installing a new heating load of 28,000 watts in base board heaters on a 240-volt circuits. They are on more than 3 hours at a time so the actual continuous duty load is 35,000 watts (125%). The minimum number of 30 ampere branch circuits to supply these heaters is _____.

    IMG_2604

    Reference: 424.4
  17. 17. 178 – Industry Related Residential Version (201029)

    1
    Given a wall mounted oven is cord and plug connected:

    IMG_2600

    Reference: 422.33B
  18. 18. 177 – Industry Related Residential Version (201029)

    1
    A dwelling unit has a dishwasher connected with a cord and plug. The plug and receptacle is installed to facilitate removal for servicing or repairs and they are allowed to serve as the disconnect for this appliance if ____.

    IMG_4167

    Reference: 422.33
  19. 19. 176 – Industry Related Residential Version (201029)

    1
    When a gas-fired central heating furnace is installed in a dwelling unit, is a disconnect required for the 1/8 HP blower motor?

    IMG_2597

    Reference: 422.31A
  20. 20. 175 – Industry Related Residential Version (201029)

    1
    If the overcurrent protective device rating is marked on the name plate of the appliance, the branch circuit overcurrent device shall be no more than _____ of the rating.

    CEIMG_019

    Reference: 422.11A
  21. 21. 172 – Industry Related Residential Version (201029)

    1

    Which types of luminaries (light fixtures) are not permitted in clothes closets? CEIMG_062

    Reference: 410.16C
  22. 22. 171 – Industry Related Residential Version (201029)

    1
    A large clothes closet includes an area where both sides of the clothes hanging rods are exposed and accessible in the center of the closet. This storage space is considered _____ inches on either side of the hanging rods.

    IMG_3784

    Reference: 410.16C
  23. 23. 169 – Industry Related Residential Version (201029)

    1

    Is it permissible to install a 15 or 20 ampere, 125 V receptacle outlet in a dwelling unit within 3 feet or more from a bathtub or shower stall?

    IMG_1238

    Reference: 406.9C
  24. 24. 168 – Industry Related Residential Version (201029)

    1
    A homeowner wants a track light installed over the bathtub in his residence.

    IMG_1237

    Reference: 410.10D
  25. 25. 167 – Industry Related Residential Version (201029)

    1
    A 20 ampere, 120-volt receptacle installed outdoors and subject to beating rain and water runoff shall have an enclosure that is weatherproof when the attachment plug cap is inserted in ___________.

    IMG_2846

    Reference: 406.9A
  26. 26. 166 – Industry Related Residential Version (201029)

    1
    Receptacles rated _____ amperes or less directly connected to aluminum conductors shall be marked CO/ALR.

    IMG_1316

    Reference: 406.3C
  27. 27. 163 – Industry Related Residential Version (201029)

    1
    Snap switches can be grouped or ganged in outlet boxes if voltages between adjacent switches do not exceed _____ volts.

    CEIMG_021

    Reference: 404.8B
  28. 28. 162 – Industry Related Residential Version (201029)

    1
    The height of a circuit breaker used as a switch shall not exceed _____ above the floor.

    IMG_0037

    Reference: 404.8A
  29. 29. 161 – Industry Related Residential Version (201029)

    1
    3-way and 4-way switches shall be wired so that all the switching is done in the ___________ conductor.

    CEIMG_043

    Reference: 404.2
  30. 30. 160 – Industry Related Residential Version (201029)

    1
    Flexible cord cannot be used as the ___________ wiring of a structure.

    IMG_2566

    Reference: 400.12
  31. 31. 159 – Industry Related Residential Version (201029)

    1
    Concealed knob & tube wiring is not allowed in the hollow space of a wall where the space ___________.

    IMG_2415

    Reference: 394.12
  32. 32. 158 – Industry Related Residential Version (201029)

    1

    Rigid Nonmetalic Conduit (RNC or PVC) is installed in a trench for a new service lateral. The local power company supplies the properly listed conduit in both gray and orange colors for the service and optics. The service lateral conduit can be ___________.

    IMG_3947

    Reference: 352.6 352.10
  33. 33. 157 – Industry Related Residential Version (201029)

    1
    A 1-inch Rigid Nonmetalic Conduit (RNC or PVC) has a field bend made with a blanket bender. The radius of the curve to the centerline shall not be less than _____ inches.

    CEIMG_050

    Reference: 352.24
  34. 34. 155 – Industry Related Residential Version (201029)

    1
    Type NM cable (romex) is permitted to connect fluorescent light fixtures in a residence in a dropped ceiling grid without support to a maximum length of not more than _____ feet.

    CEIMG_024

    Reference: 334.30 B2
  35. 35. 153 – Industry Related Residential Version (201029)

    1

    NMB cable (romex) is required to be protected from physical damage when exposed. CEIMG_003

    Reference: 334.15B, 23
  36. 36. 152 – Industry Related Residential Version (201029)

    1
    A building has hallways with suspended T-bar ceilings to conceal air conditioning ducts. Open runs of NM (romex) are allowed in the dropped ceiling area if it is not used for environmental air-handling and the structure is classified as ___________.

    IMG_2387

    Reference: 334.12A
  37. 37. 151 – Industry Related Residential Version (201029)

    1
    A luminaire (light fixture) weighs over 50 pounds and it is supported from an outlet box. The code requires _____.

    IMG_2282

    Reference: 314.27A
  38. 38. 149 – Industry Related Residential Version (201029)

    1
    In a combustible wall, the front edge of an outlet box may be set back no more than _____ inches from the finished surface.

    IMG_4157

    Reference: 314.20
  39. 39. 147 – Industry Related Residential Version (201029)

    1
    A #4 copper conductor used for a residential dwelling unit feeder panel is rated for at least _____ amperes.

    CEIMG_076

    Reference: Table 310.12
  40. 40. 146 – Industry Related Residential Version (201029)

    1
    A 400 amp, single phase, 120/240 Volt parallel run could be composed of _____.

    CEIMG_075

    Reference: 310.10G
  41. 41. 145 – Industry Related Residential Version (201029)

    1

    There are 4 separate raceways used to enclose paralleled conductors.

    IMG_3809

    Reference: 310.10G
  42. 42. 144 – Industry Related Residential Version (201029)

    1
    NMB (romex) cable is installed in a standard 2 x 4 inch plastic nail-on junction box.

    CEIMG_027

    Reference: 300.14
  43. 43. 143 – Industry Related Residential Version (201029)

    1
    A 24-volt landscape lighting system installed with UF cable in the yard of a residence is permitted with a minimum cover of _____ inches.

    CEIMG_049

    Reference: Table 300.5
  44. 44. 142 – Industry Related Residential Version (201029)

    1
    What is the minimum burial depth of a Rigid Nonmetalic Conduict (PVC) when it is encased by 3 inches of concrete when it is ran under a road?

    CEIMG_022

    Reference: Table 300.5
  45. 45. 140 – Industry Related Residential Version (201029)

    1

    The smoke detectors in a home are required to be interconnected by the building department which will necessitate a signaling conductor. This can be done by running ___________ romex cable(s) between the smoke detectors. IMG_3815

    Reference: 300.3B
  46. 46. 139 – Industry Related Residential Version (201029)

    1
    Which is not a true statement about equipment grounding conductors?

    IMG_3814

    Reference: 250.122A
  47. 47. 138 – Industry Related Residential Version (201029)

    1
    If the service entrance conductors are 350 KCMIL copper, what is the minimum size copper grounding electrode conductor if this is the sole connection to a metal water pipe electrode?

    IMG_3808

    Reference: Tab250.66, 66A
  48. 48. 137 – Industry Related Residential Version (201029)

    1
    A 400 ampere residential service is installed with 2, 200 amp panels each fed with 4/0 AL ungrounded service entrance conductors. A grounding electrode conductor is needed for the metal plumbing piping system.

    IMG_3825

    Reference: Tab250.66, 64D1
  49. 49. 136 – Industry Related Residential Version (201029)

    1
    A 200 ampere residential service is installed with 4/0 AL ungrounded service entrance conductors and needs a grounding electrode conductor installed to the metal plumbing piping system. This conductor can be sized _____.

    IMG_3807

    Reference: Tab. 250.66, 64
  50. 50. 135 – Industry Related Residential Version (201029)

    1
    The grounding electrode conductor generally shall be installed without a splice, but ___________.

    IMG_3990

    Reference: 250.64C
  51. 51. 132 – Industry Related Residential Version (201029)

    1
    A supplementary electrode is installed for a lighting pole because this equipment may be subject to lightning strikes. If a ground rod is used as this supplementary electrode, how many are required?

    IMG_3787

    Reference: 250.54
  52. 52. 130 – Industry Related Residential Version (201029)

    1
    Some metal water piping systems can deteriorate with time and may even end up being replaced with a nonmetallic system. This is one reason the code requires a supplemental grounding electrode as a backup. If a ground rod is used as this supplemental electrode, how many are required?

    IMG_3776

    Reference: 250.53
  53. 53. 129 – Industry Related Residential Version (201029)

    1
    The electrical service for a small building is grounded to an existing underground metal water pipe where it enters the structure. This location has no other electrodes available. What is the minimum number of driven ground rods that are required for a supplementary grounding electrode?

    IMG_3775

    Reference: 250.53D 2
  54. 54. 126 – Industry Related Residential Version (201029)

    1
    For a single family dwelling, the minimum size service disconnecting means shall be _____ amperes.

    IMG_3748

    Reference: 230.79C
  55. 55. 125 – Industry Related Residential Version (201029)

    1
    Service conductors that run above the top level of a window shall be permitted to be less than the _____ foot requirement.

    IMG_3751

    Reference: 230.9A
  56. 56. 124 – Industry Related Residential Version (201029)

    1
    An outbuilding on residential property is wired with one 20 ampere, 120-volt feeder for lighting and outlets.

    IMG_3750

    Reference: 225.36
  57. 57. 123 – Industry Related Residential Version (201029)

    1
    The height of a wall switch for a lighting outlet in a dwelling unit can be no more than _____.

    IMG_3746

    Reference: 404.8 A
  58. 58. 122 – Industry Related Residential Version (201029)

    1
    A living room in a dwelling unit has 3 entry points (doorways) into the room. What is the minimum requirement for the number of lighting outlet switches?

    IMG_3746

    Reference: 210.70A 1
  59. 59. 121 – Industry Related Residential Version (201029)

    1
    A wall switch in a dwelling unit can be installed ____.

    IMG_3745

    Reference: 210.70A
  60. 60. 120 – Industry Related Residential Version (201029)

    1
    Which rooms in a dwelling unit may have a receptacle outlet controlled by a switch used for lighting instead of a lighting outlet?

    IMG_3744

    Reference: 210.70A 1
  61. 61. 119 – Industry Related Residential Version (201029)

    1
    A dwelling unit dining room has a receptacle controlled by a wall switch instead of a lighting outlet.

    IMG_3743

    Reference: 210.70, 52B 1
  62. 62. 118 – Industry Related Residential Version (201029)

    1
    A homeowner wants an occupancy sensor installed in his home office for lighting.

    IMG_2109

    Reference: 210.70A 1
  63. 63. 115 – Industry Related Residential Version (201029)

    1
    A receptacle outlet must be installed at an accessible location for servicing rooftop heat pump equipment in ___________.

    IMG_3005

    Reference: 210.63
  64. 64. 114 – Industry Related Residential Version (201029)

    1
    Which receptacle outlet location is permitted but not counted as a required receptacle location?

    IMG_3742

    Reference: 210.52
  65. 65. 113 – Industry Related Residential Version (201029)

    1
    Floor boxes shall be considered to meet the requirement of the spacing receptacles on walls if they are ___________.

    IMG_3170

    Reference: 210.52A 3
  66. 66. 111 – Industry Related Residential Version (201029)

    1

    The residential small appliance branch circuit in a kitchen area ___________. IMG_2598

    Reference: 210.52B
  67. 67. 110 – Industry Related Residential Version (201029)

    1

    Given an island cabinet in a dwelling unit kitchen where the countertop is flat and you can’t mount a receptacle within 20 inches above the countertop, the receptacle can be a maximum of _____ inches below the countertop and still count as one of the required outlets.

    IMG_2588

    Reference: 210.52 C2
  68. 68. 109 – Industry Related Residential Version (201029)

    1
    In dwelling unit bathrooms, at least one receptacle outlet shall be installed within _____ inches of the outside edge of each basin.

    IMG_3741

    Reference: 210.52D
  69. 69. 107 – Industry Related Residential Version (201029)

    1
    Tap conductors for household cooking equipment supplied from a 50-amp branch circuit shall have an ampacity of not less than _____.

    IMG_3812

    Reference: 210.19C
  70. 70. 106 – Industry Related Residential Version (201029)

    1

    Dwelling unit receptacle outlets shall be protected by arc-fault circuit interrupter protection ___________.

    IMG_3811

    Reference: 210.12B
  71. 71. 105 – Industry Related Residential Version (201029)

    1
    A dwelling unit has a single bathroom roughed in with a dedicated 20-ampere branch circuit which serves an outlet, light and exhaust fan in that room.

    IMG_3813

    Reference: 210.11C 3 ex
  72. 72. 104 – Industry Related Residential Version (201029)

    1

    Does a duplex receptacle installed in a dwelling type occupancy for the refrigerator require GFCI protection?

    IMG_2587

    Reference: 210.8A 6
  73. 73. 102 – Industry Related Residential Version (201029)

    1
    A 10-2 romex is used as a 240-volt branch circuit for a hot water tank. The white insulated conductor shall be re-identified as a hot ungrounded conductor at the terminations.

    IMG_2595

    Reference: 200.7C
  74. 74. 098 – Industry Related Residential Version (201029)

    1
    What is the minimum direct burial depth of Rigid Nonmetallic Conduit (RNC/PVC) on a residential 15 amp GFCI protected circuit rated 120 volts or less?

    IMG_3146

    Reference: Table 300.5
  75. 75. 097 – Industry Related Residential Version (201029)

    1
    As a general rule, unless an exception is met, when one structure is fed from another…

    IMG_2630

    Reference: 225.30
  76. 76. 096 – Industry Related Residential Version (201029)

    1
    In a dwelling unit, one wall switch for a light is required at each floor level of a stairway with…

    IMG_2492

    Reference: 210.70A 2
  77. 77. 094 – Industry Related Residential Version (201029)

    1
    A hydromassage bathtub…

    IMG_1274

    Reference: 680.71, 73, 74
  78. 78. 093 – Industry Related Residential Version (201029)

    1
    Which shall have ground fault circuit interrupter protection?

    IMG_4256

    Reference: 680.43, 56A, 71
  79. 79. 091 – Industry Related Residential Version (201029)

    1
    In case someone gets stuck under water on the intake opening, an emergency shutoff or control is required for a hot tub….

    IMG_4154

    Reference: 680.41
  80. 80. 089 – Industry Related Residential Version (201029)

    1
    The number 8 solid copper conductor required for swimming pool bonding in the grid can be installed with…

    IMG_3922

    Reference: 680.26B, 250.8
  81. 81. 088 – Industry Related Residential Version (201029)

    1
    A swimming pool pump motor supplied by a receptacle 6 feet away from the inside pool wall…

    IMG_3917

    Reference: 680.22A
  82. 82. 087 – Industry Related Residential Version (201029)

    1
    The junction “deck box” for a no-niche luminaire (lighting fixture) for a swimming pool shall…

    IMG_3147

    Reference: 680.24A2
  83. 83. 086 – Industry Related Residential Version (201029)

    1
    What is the minimum mounting height of an outdoor mobile home disconnect?

    IMG_1170

    Reference: 550.32F
  84. 84. 082 – Industry Related Residential Version (201029)

    1
    As a general rule, the disconnecting means for air conditioning equipment shall…

    IMG_3007

    Reference: 440.14
  85. 85. 081 – Industry Related Residential Version (201029)

    1
    Dishwasher nameplate, 8 amps (Continuous Duty, 125%)… Disposal nameplate, 3 amps… (Intermittent Duty, 85%) Can these be on the same 20-amp circuit and what is the total ampacity?

    IMG_4156

    Reference: 430.24
  86. 86. 080 – Industry Related Residential Version (201029)

    1
    Baseboard heaters…

    IMG_1319

    Reference: 424.10 notes
  87. 87. 078 – Industry Related Residential Version (201029)

    1
    Which ceiling paddle fan installation meets code?

    IMG_2523

    Reference: 422.18
  88. 88. 077 – Industry Related Residential Version (201029)

    1
    Recessed fixtures (can lights)…

    IMG_2497

    Reference: 410.116A&B
  89. 89. 075 – Industry Related Residential Version (201029)

    1
    Which type of fixture is not allowed in a clothes closet?

    IMG_1278

    Reference: 410.16C
  90. 90. 071 – Industry Related Residential Version (201029)

    1
    On a circuit, a 2-wire non-grounding existing receptacle is replaced with a GFCI type. It needs to be marked…

    IMG_2415

    Reference: 406.4D
  91. 91. 070 – Industry Related Residential Version (201029)

    1
    As a general rule, a new installation of a snap switch….

    IMG_1168

    Reference: 404.9B
  92. 92. 068 – Industry Related Residential Version (201029)

    1
    A light fixture mounted on a junction box is located near the ground for landscape lighting.

    IMG_3923

    Reference: 352.10 (I), 314.23F
  93. 93. 067 – Industry Related Residential Version (201029)

    1
    Rigid Nonmetallic Conduit (RNC or PVC) expands and contracts when installed outdoors. If this change is _____ or greater in a strait run between securely mounted items, expansion fittings are needed.

    IMG_3944

    Reference: 352.44
  94. 94. 066 – Industry Related Residential Version (201029)

    1
    When installing a (RNC or PVC) Rigid Nonmetallic Conduit expansion joint…

    IMG_3989

    Reference: 352.44
  95. 95. 065 – Industry Related Residential Version (201029)

    1
    2-inch Rigid Nonmetallic Conduit (RNC or PVC) shall be supported at least every…

    IMG_2629

    Reference: 352.30B
  96. 96. 064 – Industry Related Residential Version (201029)

    1
    Flexible Metal Conduit (FMC or Flex) may have up to ____ quarter bends per run.

    IMG_2502

    Reference: 348.24B
  97. 97. 063 – Industry Related Residential Version (201029)

    1
    A # 8 copper Nonmetallic-Sheathed Cable (romex) conductor is rated at ___ amps using the ___ column of Table 310-16.

    IMG_2589

    Reference: 334.80, Table 310.16
  98. 98. 062 – Industry Related Residential Version (201029)

    1
    Flat Nonmetallic-Sheathed Cable (Romex) cannot…

    IMG_2594

    Reference: 334.40
  99. 99. 061 – Industry Related Residential Version (201029)

    1
    Where Nonmetallic-Sheathed Cable (romex) cable is installed within ___ ft. of an attic access without a permanent ladder, it shall be protected by running boards.

    IMG_2596

    Reference: 334.23
  100. 100. 060 – Industry Related Residential Version (201029)

    1
    Where Nonmetallic-Sheathed Cable (romex) passes through a floor, it shall be protected by a conduit at least ___ inches above the floor.

    CEIMG_017

    Reference: 334.15B
  101. 101. 057 – Industry Related Residential Version (201029)

    1
    What is the smallest size aluminum AWG size you could use for a 300-ampere residential service installation?

    IMG_2842

    Reference: 310.12A
  102. 102. 056 – Industry Related Residential Version (201029)

    1
    On a single phase, 225 amp dwelling service, the minimum ungrounded (hot) conductor size is…

    IMG_3819

    Reference: 310.12A
  103. 103. 055 – Industry Related Residential Version (201029)

    1
    If Nonmetallic-Sheathed Cable (romex) are bundled together for longer than ___ inches, they shall be derated for allowable ampacities.

    IMG_3214

    Reference: 310.15C 1
  104. 104. 054 – Industry Related Residential Version (201029)

    1
    Nonmetallic Sheathed Cable (romex) installed in a residential dwelling unit…

    IMG_3216

    Reference: 300.22C_ex
  105. 105. 052 – Industry Related Residential Version (201029)

    1
    Raceways exposed to different temperatures…

    IMG_2673

    Reference: 300.7
  106. 106. 051 – Industry Related Residential Version (201029)

    1
    When direct burial cable emerges from the ground, unless 30 volts or less or 20 amp residential GFCI circuits, it shall be protected by a raceway ___ inches below grade and up to ___ feet above grade.

    IMG_2606

    Reference: 300.5D 1
  107. 107. 050 – Industry Related Residential Version (201029)

    1
    Given an underground service lateral from a power company transformer to a customer owned service that you need to install.

    IMG_2543

    Reference: 300.5D 3
  108. 108. 049 – Industry Related Residential Version (201029)

    1
    When installing Nonmetallic Sheathed Cable (Romex) through metal stud framing members…

    IMG_2251

    Reference: 300.4B 1
  109. 109. 048 – Industry Related Residential Version (201029)

    1
    When determining a proper depth of a ditch for an underground conduit.

    IMG_2539

    Reference: Table 300.5_notes
  110. 110. 047 – Industry Related Residential Version (201029)

    1

    A new installation of a branch circuit supplying a single-phase clothes dryer requires… IMG_2529

    Reference: 250.140
  111. 111. 046 – Industry Related Residential Version (201029)

    1
    Listed Flexible Metallic (Flex) Conduit is an approved grounding means when…

    CEIMG_098

    Reference: 250.118 5
  112. 112. 045 – Industry Related Residential Version (201029)

    1
    Which is a true statement?

    IMG_4284

    Reference: 250.64E
  113. 113. 044 – Industry Related Residential Version (201029)

    1
    If a made electrode (ground rod) is to be used to ground a service….

    CEIMG_079

    Reference: 250.53A 4
  114. 114. 042 – Industry Related Residential Version (201029)

    1
    When a metal underground water pipe is used as an electrode…

    CEIMG_072

    Reference: 250.53D 2
  115. 115. 040 – Industry Related Residential Version (201029)

    1
    When an existing second building is supplied from the first, the neutral can be bonded when…

    CEIMG_077

    Reference: 250.32B ex
  116. 116. 039 – Industry Related Residential Version (201029)

    1
    Conductors for a feeder where the ampere rating does not match with a standard circuit breaker…

    CEIMG_078

    Reference: 240.4B
  117. 117. 036 – Industry Related Residential Version (201029)

    1

    As a general rule, overhead service weatherheads…

    IMG_4160

    Reference: 230.54C
  118. 118. 035 – Industry Related Residential Version (201029)

    1
    Service entrance conductors…

    IMG_3809

    Reference: 230.46
  119. 119. 034 – Industry Related Residential Version (201029)

    1
    A house with a separate structure like a shop has one service location with one service lateral with the meter attached to the home.

    IMG_3788

    Reference: 230.40 ex 3
  120. 120. 032 – Industry Related Residential Version (201029)

    1
    Open service conductors installed on buildings require…

    IMG_4134

    Reference: 230.9A
  121. 121. 031 – Industry Related Residential Version (201029)

    1
    An outside pole light…

    CEIMG_067

    Reference: 225.31 ex 4
  122. 122. 030 – Industry Related Residential Version (201029)

    1
    Which is not a true statement of an outside feeder from one building to another?

    CEIMG_053

    Reference: 225.31, 36, 37
  123. 123. 029 – Industry Related Residential Version (201029)

    1
    A dwelling lighting load demand factor is ____ % for 3001 to 120,000 watts.

    CEIMG_034

    Reference: Table 220.45
  124. 124. 027 – Industry Related Residential Version (201029)

    1

    A required dwelling unit wall light switch for a room…

    IMG_3805

    Reference: 210.70A
  125. 125. 026 – Industry Related Residential Version (201029)

    1
    An air conditioner…

    IMG_2990

    Reference: 210.63
  126. 126. 024 – Industry Related Residential Version (201029)

    1
    In a guest room of hotel or motel, does the number of receptacle outlets installed need to comply as in a dwelling unit of Section 210-52?

    IMG_3111

    Reference: 210.60 B
  127. 127. 019 – Industry Related Residential Version (201029)

    1

    In a dwelling unit kitchen where the exception allows a receptacle to be installed below the countertop, to count, the counter lip shall extend no more than ___ beyond the counter.

    IMG_2298

    Reference: 210.52C 3
  128. 128. 018 – Industry Related Residential Version (201029)

    1
    The two or more required kitchen 20-amp appliance circuits can include…

    IMG_2547

    Reference: 210.52B 1&2
  129. 129. 016 – Industry Related Residential Version (201029)

    1
    A dwelling unit small appliance branch circuit for the kitchen cannot…

    CEIMG_041

    Reference: 210.52B 2
  130. 130. 015 – Industry Related Residential Version (201029)

    1
    A receptacle outlet for a dwelling refrigerator….

    CEIMG_029

    Reference: 210.52B1, 210.8
  131. 131. 014 – Industry Related Residential Version (201029)

    1
    On a multi-family structure, which loads are permitted to be supplied from a dwelling unit?

    CEIMG_024

    Reference: 210.25B
  132. 132. 011 – Industry Related Residential Version (201029)

    1
    In a dwelling unit bathroom…

    IMG_2487

    Reference: 210.11C
  133. 133. 010 – Industry Related Residential Version (201029)

    1
    In a dwelling unit, the washing machine shall _____.

    IMG_2493

    Reference: 210.11C
  134. 134. 009 – Industry Related Residential Version (201029)

    1
    Which does not require a GFCI protection device for a dwelling unit?

    IMG_2277

    Reference: 210.8A
  135. 135. 008 – Industry Related Residential Version (201029)

    1
    In a dwelling garage, a non-GFCI outlet installed for a Central Vacuum system shall be…

    IMG_3173

    Reference: 210.8A
  136. 136. 007 – Industry Related Residential Version (201029)

    1
    A branch circuit for a dwelling unit is ran out for a small storage building for an inside 120-volt outlet at grade level.

    IMG_2304

    Reference: 210.8A
  137. 137. 006 – Industry Related Residential Version (201029)

    1
    A multiwire branch circuit for a hot water tank using a line-to-line load requires…

    IMG_2312

    Reference: 240.15B, 210.4B
  138. 138. 005 – Industry Related Residential Version (201029)

    1
    If you use a 12-3 romex as travelers between 3-way switches with the white used to supply the switch.

    IMG_3178

    Reference: 200.7C
  139. 139. 002 – Industry Related Residential Version (201029)

    1
    When the term “In sight from” is used in the Code, what is the maximum distance permitted?

    IMG_2642

    Reference: Definitions
  140. 140. 001 – Industry Related Residential Version (201029)

    1
    An area is considered a bathroom if…

    IMG_1277

    Reference: Definitions
Back